FT69 SERIES SINGLE-STAGE FROST PROTECTION THERMOSTATS – SPECIFICATION DATA & MOUNTING 

 

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland

 

by its Authorized Representative: 

 

FEMA Control 

Honeywell GmbH 
Böblinger Strasse 17 
71101 Schönaich, Germany 
Phone  +49 (0) 7031 637 01 
Fax 

+49 (0) 7031 637 740 

http://www.fema.biz 
 
MU0B-0645GE51 R0914 

Subject to change without notice 

MOUNTING AND SETTING 

The switching temperature can be set by an adjustment 
screw on top of the housing. The room temperature at the 
thermostat body should not drop below the setting point. 
Recommended mounting position is vertical with cable entry 
on bottom side. For mounting, use the screws (included in the 
package). To securely mount and to prevent soiling by drilling 
waste, the mounting holes are enclosed separately. For 
wiring, remove the cover and proceed as shown in Fig. 2. 
When unwinding, the capillary tube must be held by the anti-
kink device on the diaphragm pot. Maintain a radius of 
curvature of at least 20 mm. When inserting the coil through 
openings in sheet metal housings, provide protection against 
damage. Use the coil bracket included in the package. 
 

DIMENSIONS 

140

11

3

100

90

62

65

50

M20 x 1.5

94

26

54

2

9.5

75

RESET

BUTTON

(FT6960, ONLY)

 

Fig. 1. Dimensions in mm 

 

 WARNING 

All operations performed on the unit - including 
wiring, testing, or maintenance - must be done 
without power supply on the unit, by qualified 
personnel, and in compliance with local electrical 
regulations. 
Honeywell is not liable for possible damages caused 

by an improper installation or incorrect electrical 

wiring or by removed or exchanged electrical safety 

features. 
To guarantee the sealed protection on the unit, 

tighten the cover screws and fasten the grommet. 

 

FIELD WIRING 

T

NORMALLY-CLOSED
CONTACT

T > SETPOINT)

(

 

Fig. 2. Field wiring (frost protection) 

Monitoring for dropping temperature (frost protection): 

Wire the red and white terminals. The resultant normally-
closed contact will open when the temperature drops below 
the setpoint. 

Signal function:

 For service functions, connect a signal lamp 

to the corresponding opposite contact. The free contact will 
then close simultaneously (thus acting as a signal contact). 
 

RESET FUNCTION 

The 

FT6960

 models are manual reset types. After the tem-

perature has dropped below the setpoint, the contact remains 
open until moved back to its normally-closed position by 
manually pressing the reset button on the front. 

NOTE:

 

Press the reset button only after the installation 
has been rechecked by qualified service per-
sonnel, and only after the temperature has risen 
at least 2-3 K (hyst margin of error) 
above the setpoint. 

The 

FT6961

 models are automatic reset types. After the tem-

perature has dropped below the setpoint, the contact auto-
matically returns to its normally-closed position as soon the 
temperature rises at least 2-3 K (hyst margin of error) 
above the setpoint. 
 

ACCESSORIES 

Included in package: 6 pcs fastening clamps and two 
fastening screws 3.5 x 20. 

50 

5

50 

 

Fig. 3. Fastening clamp, dimensions in mm 

 