32
FS20X Fire and Flame Detectors
DIP Switch SW2
Figure 25. Eight-position DIP switch SW2
SW2
OFF
ON
Alarm Relay
SW2-1
Latching
on
Non-latching
off
Sensitivity Levels
SW2-2
High (3)
on
Medium (2)
off
SW2-3
off
off
Very High (4)
on
on
Low (1)*
off
off
on
Auxiliary Relay
SW2-4
5 Sec. Verify Time
on
10 Sec. Verify Time
off
SW2-5
off
on
No Verify Time
on
on
20 Sec. Verify Time
off
off
off
Factory Use Only
SW2-6
off
Alarm Relay
SW2-7
Energized
on
De-energized
off
Fault Relay
SW2-8
Energized
on
De-energized**
off
**If the fault relay is de-energized,
the detector will not report loss
of power faults.
SW2 Configuration
Default settings are highlighted in grey.
*The low sensitivity range is not compliant
with the requirements of EN 54-10:2002.
1 2 3 4 5 6 7 8