44
FL-PS Series Instruction Manual —
P/N LS10227-001FL-E:B 3/29/2021
Application Examples
Canada Two-Stage Application Using CMF-300-6
B.8 Canada Two-Stage Application Using CMF-300-6
In this application, two outputs are being controlled by a CMF-300-6 multi-module inside the cabinet. NAC1 from the host FACP is pro-
viding the Canada two-stage audible pattern to the FL-PS. NAC2 is providing master sync or a steady output, depending on its capabili-
ties. Additional FL-PS outputs can be used to connect to CMF-300-6 modules outside the cabinet.
The following notes apply to Figure B.8.
•
FL-PS Output #1 is programmed to activate on Command Input #1 and Slave Mode (NAC Follower).
•
FL-PS Output #2 is programmed depending on host FACP capabilities:
– FACP NAC2 provides master sync: FL-PS output #2 activate on Command Input 2, slave mode (NAC follower)
– FACP NAC2 provides steady output: FL-PS output #2 activate Command Input 2, master mode (select appropriate strobe
manufacturer)
•
Jumpers must be installed on terminals T11, T12, T14, and T15 of the CMF-300-6 module.
•
Unused control module NAC outputs need ELRs installed or must be disabled.
•
FL-PS outputs going to CMF-300-6 need ELRs installed.
•
Due to the reverse-polarity supervision of the FL-PS outputs, the CMF-300-6 points must have the type code, “Bell Circuit”, to
prevent “Ext Power Loss” troubles.
NO NC C
NO NC C
TB4
TB15
T
B
2
T
B
1
T
B
1
3
O
U
T
6
T
B
1
2
O
U
T
5
T
B
1
1
O
U
T
4
T
B
1
0
O
U
T
3
T
B
9
O
U
T
2
T
B
8
O
U
T
1
–
+
– +
–
+
– +
–
+
– +
–
+
– +
–
+
– +
– + – +
T10
J1
BASE A0
BASE A1
BASE A2
BASE A3
BASE A4
BASE A5
SW1
T1
+1
+0
+2
+3
+4
+5
T0
T2
T3
T4
T5
T11
T12
T13
T14
T15
T16
0
1
2
3
4
5
6
7
8
9
1
0
1
1
1
3
1
4
1
5
1
2
0
1
2
3
4
5
6
7
8
9
T0, T1, T2
visual appliance circuits
T3, T4, T5
audible appliance circuits
NAC1
NAC2
SLC
Host FACP
Figure B.8 Canadian Two-Stage Wiring Using a CMF-300-6