ECC-RPU Installation Document —

 P/N LS10030-000FL-E:B  8/9/2013

2.3  Mounting/Wiring an Optional 

Monitor Module

An MMF-300 monitor module may be mounted inside the 
cabinet.  This can be used for HVAC shutdown 
applications when the monitor module is connected to the 
FACP SLC polling loop.  The monitor module is wired to 
TB4 on the RPU and is activated by the 9th button on the 
RPU keypad.  The module’s LED is visible through the 
keypad next to the 9th button.
1. Remove the two (2) keps nuts that secure the RPU 

board to the dress panel using a 5/16” socket.

2. Set the SLC address on the MMF-300. Remove the 

four (4) break-away tabs from the monitor module.  
See Figure 4.

3. Insert the bottom of the monitor module (SLC address 

dials facing inward) into the mounting tabs on the left 
side of the RPU.  The RPU mounting screws will go 
through the top of the monitor module.  Situate the 
LED on the front of the module over the hole in the 
PC board.

4. Replace the keps nuts over the mounting screws to 

secure the monitor module to the board.

5. Connect the SLC wiring to the module terminals 1 (–) 

and 2 (+).  Refer to the 

SLC Wiring Manual

 for more 

information.

6. Wire TB4 on the RPU to T6/T7 on the monitor 

module as shown below.  No ELR is required as it is 
built into TB4.    

3 Wiring

Connections are made from TB24, TB12, and TB22 on the 
ECC-50/100 main control board to TB1, TB3, and TB2 on 
the RPU.  If the ECC-RPU is the last device on the audio 
and data bus chain, signal terminations are required.  For 
the last device on the external data bus, a removable 
jumper must be on pins 1 and 2 of JS4.  If the ECC-RPU is 
not the last device, the jumper must be on pins 2 and 3 of 
JS4 as shown below.  For the external audio riser, 
termination (15K ohm resistor) must be connected to pins 
4 and 5 on TB2.  A ferrite clamp (P/N: 50116546-001) 
must be installed around all wires in both the input and 
output wire runs 

inside the RPU cabinet 

as shown below.   

+       -

SLC In

SLC Out

mounting 

tabs

TB4

keps 

nuts

Figure 4  Wiring an MMF-300 to the RPU

Remove 
break-away 
tabs (4) from 
module

LED on other 

side of module

+

-

+

-

+

-

+

-

+

-

+

-

B
A

B
A

B

A

1

2
3
4

5

1
2
3

4
5

1
2
3
4

5

ECC main 

control board

RPU board

TB24

TB12

TB22

TB1

TB3

TB2

external operator interface 

power - 24VDC

external 

data bus

external 

audio 

riser

Figure 5  Remote Page Unit Wiring

(Class B/Style Y)

to next operator interface/ 

amplifier or 15K

 ELR

(if last device)

JS4

(shown jumpered 

on pins 2 and 3)

IN

24V

OUT

IN

Data

OUT

IN

Audio

OUT

ferrite 

clamp