Honeywell Fire-lite ECC-LOC Скачать руководство пользователя страница 2

2

ECC-LOC Installation Document —

 P/N LS10028-000FL-E:B  8/9/2013

4 Keypad

          

4.1  Switch Functions

All Call  

Activates all speaker circuits for broadcast.  

MNS Control

 

(for systems configured for mass 

notification operation which has higher priority)

  

Activates the MNS Active Relay and the onboard NAC. A 
second press turns these back off.  For a combination fire 
and mass notification system, pressing MNS C

ONTROL

 

will result in the shutdown of audible FACP NACs and 
audio system speakers, allowing the system to override the 
system. Pressing MNS C

ONTROL

 again causes the FACP 

to re-activate audible FACP NACs and audio system 
speakers.

System Control  

Manually gains control of the audio 

system in preparation for an ALL CALL, message 
activation, or general page. The green LED will turn on 
steadily to confirm control. A second press is required 
after paging to relinquish control of the system. The main 
console will have system priority based upon user 
programming. In order for the LOC to gain control, the 
ECC must first relinquish control of the system.

Speaker Select 1-24  

Manually activates or deactivates 

speaker zones (circuits).

Message Select 1-8  

Manually activates or deactivates 

stored messages. 8th button becomes a “shift” for 
messages 9-14.

FIRE SYSTEM
   ACTIVE

SYSTEM

CONTROL

ALL

CALL

1

2

3

4

5

6

7

8

9

10

11

12

13

18

19

20

21

22

23

24

16

17

14

15

Figure 3  ECC-LOC Keypad

ecckyd.

w

mf

SPEAKER 

ZONE 1

SPEAKER

ZONE 2

SPEAKER

ZONE 3

SPEAKER

ZONE 4

SPEAKER

ZONE 5

SPEAKER

ZONE 6

SPEAKER

ZONE 7

SPEAKER

ZONE 8

SPEAKER

ZONE 9

SPEAKER

ZONE 10

SPEAKER

ZONE 11

SPEAKER

ZONE 12

SPEAKER 

ZONE 13

SPEAKER

ZONE 14

SPEAKER

ZONE 15

SPEAKER

ZONE 16

SPEAKER

ZONE 17

SPEAKER

ZONE 18

SPEAKER

ZONE 19

SPEAKER

ZONE 20

SPEAKER

ZONE 21

SPEAKER

ZONE 22

SPEAKER

ZONE 23

SPEAKER

ZONE 24

MESSAGE 1

MESSAGE 2

MESSAGE 3

MESSAGE 4

MESSAGE 5

MESSAGE 6

MESSAGE 7

MESSAGE 8

DIST. AMP 1

DIST. AMP 2

DIST. AMP 3

DIST. AMP 4

DIST. AMP 5

DIST. AMP 6

DIST. AMP 7

DIST. AMP 8

DIAGNOSTIC

REMOTE AMPS

TROUBLE SILENCE

AC POWER

GROUND FAULT

CHARGER FAULT

BATTERY FAULT

DATA BUS FAULT

NAC FAULT

NAC ACTIVE

SYSTEM TROUBLE

AUDIO RISER FAULT

LOC 1

LOC 2

RPU 1

RPU 2

RPU 3

RM 1

RM 2

RM 3

CONSOLE LAMP TEST

MAIN CONSOLE

MNS 

CONTROL

OK TO PAGE

MICROPHONE 

TROUBLE

green

green

yellow

yellow

red

green

green

yellow

Note: Console 
assignments are 
shown here as an 
example only.

Содержание Fire-lite ECC-LOC

Страница 1: ... circuitry Class 2 supervised Audio signal level 3 85 VRMS maximum Frequency range 800 Hz 2800 Hz 3 Cabinet Mounting 3 1 Removing the Dress Panel 1 Open the door and lift the door off the pin hinges 2 Remove the two 2 screws securing the dress panel to the backbox 3 Open the dress panel and disconnect the ground wire from the back 4 Lift up dress panel and pull out lower pivot flange Slide the upp...

Страница 2: ...ect 1 24 Manually activates or deactivates speaker zones circuits Message Select 1 8 Manually activates or deactivates stored messages 8th button becomes a shift for messages 9 14 FIRE SYSTEM ACTIVE SYSTEM CONTROL ALL CALL 1 2 3 4 5 6 7 8 9 10 11 12 13 18 19 20 21 22 23 24 16 17 14 15 Figure 3 ECC LOC Keypad ecckyd wmf SPEAKER ZONE 1 SPEAKER ZONE 2 SPEAKER ZONE 3 SPEAKER ZONE 4 SPEAKER ZONE 5 SPEA...

Страница 3: ...Yellow LED will turn on indicating a message trouble in the group of messages not currently being viewed Remote Amplifiers 1 8 Fault Yellow LED per remote amplifier that turns on steady when an amplifier has a fault LOC RPU RM 1 8 Fault Yellow LED per remote console that turns on steady when a remote console has a fault Green LED per remote console that turns on steady when a remote console is act...

Страница 4: ...e Condition Activation of trouble signal under normal operation indicates a condition that requires immediate attention Contact your local service representative Silence the audible signal by pressing the TROUBLE SILENCE switch The trouble indicator will remain illuminated B A B A B A B A main control board LOC display board TB24 TB12 TB22 TB3 TB4 TB5 external operator interface power 24VDC extern...

Отзывы: