Honeywell Fire-Lite ANN-LC Скачать руководство пользователя страница 3

ANN-LC Product Installation Document —

 P/N LS10158-000FL-E:C  7/28/2015

3

4 Wiring

4.1  FACP Wiring

Refer to the

 MS-9050UD Series (#52413) and MS-9200UDLS Series (#52750) Manuals

 for wiring the ANN-LC to the 

FACP.  

4.2  Fiber-Optic Cables

Multi-mode fiber-optic cables must be used. Connections must be made using duplex LC connectors (per IEC 61754-20).  
The over-bending of fiber-optic cables can cause breakage.  Consult manufacturer’s guidelines for minimum radius of 
bend for fiber-optic media.       

4.3  Class B Wiring

Class B wiring begins at the MS-9050UD being used as the hub and ends with the last node on the circuit.           

Figure 3  LC Connector

LCconnector2side.wmf

ANN-LC 

mounted 

in

 hub

1

1

1

1

1

1

2

2

2

2

2

2

First 

circuit 

node

Last

circuit 

node

Figure 4  Class B Wiring

F

L

L

C

cl

as

sB

.w

m

f

 node

 node

 node

Consult manufacturer’s guidelines for minimum 
radius of bend for fiber-optic media

Содержание Fire-Lite ANN-LC

Страница 1: ... next All ANN LC boards must be running the same version of Lite Connect module software The circuit can be wired in either Class A or Class B 2 Specifications Operating voltage 24 VDC Maximum current 150 mA 24 VDC Maximum attenuation of the optical signal between any two ANN LC cards for 62 5 125 or 50 125 multi mode fiber optic cable 5 dB For uninterrupted cable runs this will equate to a maximu...

Страница 2: ...of the mounting bracket to the backbox grounding stud securing it with hex nuts as illustrated below IMPORTANT Only 7 AH or 18 AH batteries will fit in front of the ANN LC when installed inside the FACP backbox If 12 AH batteries are to be used they must be installed vertically and sit on the left side of the bottom of the backbox ANN LC backbox protrusions Figure 1 Mounting the ANN LC into the Ba...

Страница 3: ...754 20 The over bending of fiber optic cables can cause breakage Consult manufacturer s guidelines for minimum radius of bend for fiber optic media 4 3 Class B Wiring Class B wiring begins at the MS 9050UD being used as the hub and ends with the last node on the circuit Figure 3 LC Connector LCconnector2side wmf ANN LC mounted in hub 1 1 1 1 1 1 2 2 2 2 2 2 First circuit node Last circuit node Fig...

Страница 4: ...ass A wiring a single open will not result in fragmentation of the circuit Communication will continue while the hub and every installed node display a trouble condition on their host FACP ANN LC mounted in hub 1 1 1 1 1 1 2 2 2 2 2 2 First circuit node Last circuit node Figure 5 Class A Wiring FLLCclassA wmf 1 2 1 2 node node node node node Consult manufacturer s guidelines for minimum radius of ...

Отзывы: