Specifications
Product Description
Drill
•
Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silenced
Discharge
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Outputs Programmable for:
Releasing Solenoids
NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Nonsilenceable
– Release Stage Sounder
•
Designed for sprinkler standards NFPA 13, 15 and 16
•
Disable/Enable control per input zone and output zone
•
Extensive transient protection
•
Dual hazard operation
•
Adjustable waterflow discharge timer and two soak timers
•
Cross-zone (double-interlock) capability
•
Pre-programmed and custom application templates
•
Automatic battery charger with charger supervision
•
Silent or audible walktest capabilities
•
Optional Dress Panel DP-51050 (red)
•
A modified Dress Panel is provided standard with Canadian models: includes an ANN-LED
Annunciator module
•
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
•
Optional CAC-5X Class A Converter Module for Outputs and IDCs
•
Optional 4XTMF Municipal Box Transmitter Module
•
Optional Digital Alarm Communicators (411, 411UD, 411UDAC)
•
Optional ANN-SEC card for secondary ANN-BUS
1.2 Specifications
AC Power
MRP-2001/C: 120 VAC, 60 Hz, 3.66 amps
MRP-2001E: 240 VAC, 50/60 Hz, 2.085 amps
Wire size: minimum #14 AWG (2.0 mm
2
) with 600V insulation
Supervised, nonpower-limited