Canadian DF-60954:C • 7/16/2018 — Page 3 of 4

MMF-300A:

 Addressable Monitor Module for one zone of normally-

open dry-contact initiating devices. Mounts in standard 4.0" (10.16

 

cm.) box. Includes plastic cover plate and end-of-line resistor. Mod-
ule may be configured for either a Style B (Class B) or Style D (Class

 

A)

 

IDC.

MDF-300A:

 Dual Monitor Module. Same as MMF-300A except it

 

provides two Style B (Class B) only IDCs.

MMF-301A:

 Miniature version of MMF-300A. Excludes LED and

 

Style D option. Connects with wire pigtails. May mount in device

 

backbox.

MMF-302A:

 Similar to MMF-300A. Addressable Monitor Module for

 

one zone of conventional two-wire detectors. Requires resettable 24

 

VDC power. Refer to the 

Device Compatibility Document

 for listed

 

compatible devices  and quantity limitation.

CMF-300A:

 Addressable Control Module for one Style Y/Z (Class B/

A)

 

zone of supervised polarized Notification  Appliances. Mounts

 

directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance

 

Circuit option requires external 24 VDC to power notification appli-
ances.

CRF-300A:

 Addressable relay module containing two isolated sets

 

of Form-C contacts, which operate as a DPDT switch. Mounts

 

directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500.

BG-12LX: 

Addressable manual pull station with interface module

 

mounted inside.

I300A: 

This module isolates the DCL loop from short circuit condi-

tions (required for Style 6 or 7 operation).

ISO-6A: 

Six-fault isolator module. Mount one or two modules in a

 

BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chas-
sis in a BB-6F cabinet. 

SMB500: 

Used to mount all modules except the MMF-301A and

 

M301A.

MMF-300-10A: 

Ten-input monitor module. Mount one or two mod-

ules in a BB-2F cabinet (optional). Mount up to six modules on a

 

CHS-6 chassis in a BB-6F cabinet.

MMF-302-6A: 

Six-zone interface module. Mount one or two mod-

ules in a BB-2F cabinet (optional). Mount up to six modules on a

 

CHS-6 chassis in a BB-6F cabinet. 

CMF-300-6A: 

Six-circuit supervised control module. Mount one or

 

two modules in a BB-2F cabinet (optional). Mount up to six modules

 

on a CHS-6 chassis in a BB-6F cabinet.

CRF-300-6A: 

Six-relay control module (Form-C relays). Mount one

 

or two modules in a BB-2F cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a BB-6F cabinet.

NOTE: 

For more information on Compatible Addressable Devices for

 

use with the EX-50XC, see the following data sheets (document num-
bers):  AD355  (DF-52386),  BG-12LX  (DF-52013),  CMF-300-6 
(DF-52365),  CRF-300-6  (DF-52374),  CMF/CRF  Series  (DF-52130), 
CP355

 

(DF-52383),  H355  Series  (DF-52385),  I300  (DF-52389), 

ISO-6 

(DF-60485), 

MMF-300 

Series/MDF-300 

(DF-52121), 

MMF-300-10  (DF-52347),  MMF-302-6  (DF-52356),  SD355/SD355T 
(DF-52384), and the

 

DCL Wiring Manual (51309).

NOTE: 

Legacy 300 Series detection devices such as the CP300A/

CP350A, SD300A(TA)/SD350A(TA) and older modules such as the

 

M300A, M301A, M302A, C304A, and BG-10LX are not compatible with

 

LiteSpeed polling. If the DCL contains one of these devices, polling must

 

be set for standard CLIP protocol. Please consult factory for further infor-
mation on previous 300 Series devices.

ADDRESSABLE DEVICE ACCESSORIES

End-of-Line Resistor Assembly (R-47K and R-3.9K): 

The

 

47k

 

ohm  assembly  supervises  the  MMF-300A,  MDF-300A, 

MMF-301A,  and  CMF-300A  module  circuits.  The  3.9k

 

ohm 

assembly

 

supervises  the  MMF-302A  module  circuit.  These 

resistors are

 

included with each module.

Power Supervision Relay: 

Supervises the power to 4-wire smoke

 

detectors and notification appliances.

Wiring Requirements

While shielded wire is not required, it is recommended that all DCL
wiring be twisted-pair to minimize the effects of electrical interfer-
ence. Refer to the panel manual for wiring details.

Содержание Fire-Lite Alarms ES-50XC

Страница 1: ...rts two devices set to the same address Two independently programmable built in Style Z Class A or Style Y Class B NAC circuits Selectable strobe synchronization for System Sensor Wheelock and Gentex devices Notification Appliance Circuit End of Line resistor matching Four programmable function keys for ease of maintenance Two programmable relays and one fixed trouble relay Built in Programmer Int...

Страница 2: ...rouble and Supervisory Ships with red enclosure See DF 60241 ANN RLED Provides alarm red indicators for up to 30 input zones or addressable points See DF 60241 ANN RLY Relay Module provides 10 programmable Form C relays Can be mounted inside the cabinet See DF 52431 ANN S PG Serial Parallel Printer Gateway module provides a con nection for a serial or parallel printer See DF 52429 ADDRESSABLE DEVI...

Страница 3: ... up to six modules on a CHS 6 chassis in a BB 6F cabinet MMF 302 6A Six zone interface module Mount one or two mod ules in a BB 2F cabinet optional Mount up to six modules on a CHS 6 chassis in a BB 6F cabinet CMF 300 6A Six circuit supervised control module Mount one or two modules in a BB 2F cabinet optional Mount up to six modules on a CHS 6 chassis in a BB 6F cabinet CRF 300 6A Six relay contr...

Страница 4: ... or Style Z Class A Special Application power Power limited supervised circuitry Maximum sig naling current per circuit 2 5 amps special application 250mA regu lated End of Line Resistor 4 7k ohm watt P N 71252 UL listed for Style Y Class B NAC system capable of 1 9 kΩ 22 kΩ ELR range Refer to the Fire Lite Device Compatibility Document for listed compatible devices Two Programmable Relays and One...

Отзывы: