ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
95
Master Programming Level
Programming
ANN-S/PG (Print) Options
The Print option allows the programmer to configure the optional printer. Pressing
1
while viewing the ANN-
BUS Options screen will display the following screens:
Pressing
1
for Port while viewing ANN-S/PG Options screen #1 will allow the programmer to select between a Parallel and Serial Port for
printer connection. Each press of the
1
key will cause the display to toggle between
Port PAR
(parallel) and
Port SER
(serial). It is important
to note that the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an offline timer for the supervision by press-
ing
2
for Printer Supervision while viewing Print Options screen #1. Each press of the
2
key will cause the display to toggle between
Printer
Supv NO
for no supervision and
Printer Supv YES
for printer supervision. Note that this option is not selectable if the Serial Port option has
been selected.
If the Parallel Port option is selected, the user has the ability to select an
Offline Timer
by pressing
3
while viewing Print Options screen #1.
The resultant screen allows the programmer to program the
Offline Timer
for a delay of between 0 and 255 seconds before loss of printer
supervision is reported as a trouble.
If the Serial Port option is selected, the
Printer Supv
and
Offline Timer
options will not be available. The Baud Rate, Data Bits, Parity and
Stop Bits options are only available when the Serial Port option has been selected.
Pressing
1
for
Baud Rate
while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allow the user to select a Baud
Rate of
19200, 9600, or 2400
.
Pressing
2
for
Data Bits
while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select
7
or
8
Data Bits
.
Pressing
3
for
Parity
while viewing ANN-S/PG Options screen #2 will cause a screen to appear which allows the user to select between
No
Parity
,
Even Parity,
or
Odd Parity
.
Pressing
1
for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear which allows the user to select between
1.0
or
2.0 Stop Bits
.
ANN-LED Options
This option allows the programmer to configure the optional ANN-LED annunciator. Pressing
2
while viewing
the ANN-BUS screen will display the following screens.
The
Piezo Enable
option allows the programmer to select whether the piezo sounder on any installed ANN-LED module will ever sound.
Pressing
1
while viewing the ANN-LED Options Screen causes the display to toggle between
Piezo Enable Yes
and
Piezo Enable No
.
The Lamp Test Enable (
LMP TST ENABLE
) option allows the programmer to select whether the Lamp Test button on any installed ANN-
LED annunciator will function normally or always be ignored. Pressing
2
while viewing the ANN-LED Options Screen causes the display to
toggle between
Lmp Tst Enable Yes
(Lamp Test button functions normally) and
Lmp Tst Enable No
(Lamp Test button never functions).
The Silence Button Enable
(SIL BTN ENABLE)
option allows the programmer to select whether the Silence button on any installed ANN-
LED annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-LED Options Screen causes the display to
toggle between
Sil Btn Enable Yes
(Silence button functions normally) and
Sil Btn Enable No
(Silence button never functions).
ANN-80/100 Options
Pressing
3
while viewing the ANN-BUS screen will display the following screen:
The
Piezo Enable
option allows the programmer to select whether the piezo sounder on any installed ANN-80 or ANN-100 module will ever
sound. Pressing
1
while viewing the ANN-80/100 Options Screen #1 causes the display to toggle between
Piezo Enable Yes
and
Piezo
Enable No
.
The
Lock Enable
option allows the programmer to select whether or not any installed ANN-80 or ANN-100 annunciator must be unlocked
by its key before any annunciator key presses will function. Pressing
2
while viewing the ANN-80/100 Options Screen #1 causes the display
to toggle between
Lock Enable Yes
(annunciator must be unlocked for keys to function) and
Lock Enable No
(lock position is ignored). This
option is not available in Canadian mode. Refer to the table on page 47 for permissible settings.
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
ANN-S/PG OPTIONS
1=PORT SER
2=PRINTER SUPV N/A
3=OFFLINE TIMER N/A
ANN-S/PG Options Screen #1
ANN-S/PG OPTIONS
1=BAUD RATE 9600
2=DATA BITS 7
3=PARITY EVEN
ANN-S/PG Options Screen #2
ANN-S/PG OPTIONS
1=STOP BITS 1.0
ANN-S/PG Options Screen #3
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
ANN-LED OPTIONS
1=PIEZO ENABLE NO
2=LMP TST ENABLE NO
3=SIL BTN ENABLE NO
ANN-LED Options Screen
XXX ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-LED OPTIONS
3=ANN-80/100 OPTIONS
ANN-BUS Options Screen
ANN-80/100 OPTIONS
1=PIEZO ENABLE YES
2=LOCK ENABLE YES
3=ACK BTN ENABLE YES
ANN-80/100 Options Screen #1
ANN-80/100 OPTIONS
1=SIL BTN ENABLE YES
2=RST BTN ENABLE YES
3=DRL BTN ENABLE YES
ANN-80/100 Options Screen #2