Section 3: Programming
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, Equipment for Fire Signal Receiving Centers and Systems: ULC-S559, and Standard for Control Units for
Fire Alarm Systems: ULC-S527, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature or
option
Permitted in
UL864/
ULC-S527
/ULC-S559?
(Y/N)
Possible settings
Settings permitted in
UL864 / ULC-S527/ULC-S559
Trouble Call Limit
N
Refer to “Trouble Report Limit (Dialer Runaway Prevention)”
on page 84.
• Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
• Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Trouble Call Limit = 0 for unlimited Central
Station trouble calls
AC Fail Delay Timer
Y
Refer to “AC Loss Delay” on page 72.
• 0-23 hours
1-3 hours
Remote Download
Y
Refer to “FS-Tools Upload/Download” on page 120.
• Remote Download - Proprietary No
• Remote Download - Proprietary Yes
Remote Download
Proprietary Yes
for
Proprietary system intended to protect only
contiguous properties
Control Module Delay
N
Refer to “Control Module Delay” on page 72.
• Control Module Delay = 0 (factory default): no delay in
Control Module activation
• Control Module Delay = 1-180: delays control module
activation from 1-180 seconds
Control Module Delay = 0 for no delay in
control module activation
Cellular/Ethernet
Supervision Options
Y
Refer to “Supervision Settings” on page 83 and page 84.
• NFPA 2010 Dual Path: Supervision Interval: 24 Hours
• NFPA 2010 Sole Path: Supervision Interval: 5 min
• NFPA 2013 Dual Path: Supervision Interval: 6 Hours
• NFPA 2013 Sole Path: Supervision Interval: 1 Hour
Any NFPA setting is permitted for UL864.
For ULC applications, the supervision interval
for panels communicating in Sole Path
(Cellular-only or Ethernet-only method) is
fixed at 3 minutes and cannot be changed,
regardless of setting option, when the
Canadian Option is enabled.
Trouble Reminder
(when used with
SWIFT wireless
devices)
Y
Refer to “Trouble Reminder” on page 78
• 4 hours
• 24 hours
4 hours
4XTMF Supervision
Y
Refer to “4XTMF Supervision” on page 78.
• Enabled Yes
• Enabled No
Enabled Yes when the 4XTMF module is
installed.
Supervised Phone
Line
Y
Refer to “Supervised Phone Line” on page 80.
• Supervised Yes
• Supervised No
Supervised Yes if transmission method is
POTS.
Test Time Interval
Y
Refer to “Test Time Interval” on page 82.
• 24 hours
• 12 hours
• 8 hours
• 6 hours
• 4 hours
• 3 hours
• 2 hours
• 1 hour
• 6 hours
• 4 hours
• 3 hours
• 2 hours
• 1 hour
Annunciator Lock
Enable
Y
Refer to “Lock Enable Option” on page 95.
• Enabled Yes
• Enabled No
Enabled Yes
Canadian Option
N (UL864)
Y (ULC-S527)
Y (ULC-S559)
Refer to “Canadian Option” on page 77.
• On
• Off
Off (UL864)
On (ULC-S527)
On (ULC-S559)
NOTE:
Two-stage operation cannot be used at the same time as in-suite silence feature.