[9] CLEANING

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms. 

1.  Remove the sensor to be cleaned from the system.

2.  Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place. 

3.  Vacuum the screen carefully without removing it. If further cleaning is re-

quired continue with Step 4, otherwise skip to Step 7. 

4.  Remove the chamber cover/screen assembly by pulling it straight out. 

5.  Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber. 

6.  Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber. Turn until it is firmly in place. 

7.  Replace the cover using the LEDs to align the cover and then gently push ing 

it until it locks into place. 

8.  Reinstall the detector. 

9.  Test the detector as described in TESTING. 

10.  Reconnect disabled circuits. 

11.  Notify the proper authorities that the system is back on line. 

[10] SENSOR REPLACEMENT

The D365PL comes with the sensor head factory installed, part number 
SD365R-IV. Other UL listed compatible sensor heads can also be used.

1.  Remove the sensor head by rotating counterclockwise.

2.  Pull gently to remove it. 

3.  To replace the sensor head, align the mounting features and rotate clock-

wise into place.

[11] OPTIONAL ACCESSORIES 

Optional accessories include RA100Z, RTS151 and RTS151KEY.

NOTE: Ensure blue wire always remains connected to RA+ on the field con-
nector side of the terminal block.

FIGURE 8. WIRING DIAGRAM FOR D365PL TO RA100Z

(+)

(-)

RA100Z

– RA

+ RA

REMOTE ALARM LED 

OPTION 1 PER UNIT 

 

H0570-05

Note: Remove jumper when using RA100Z with the intelligent duct smoke 
detector. 

The RTS151/RTS151KEY Remote Test Station facilitates test of the alarm ca-
pability of the duct smoke detector. These accessories provide the stimulus to 
initiate an alarm condition at the detector. The D365PL duct smoke detector 
must be reset by the system control panel.

[11.1] REMOTE TEST USING SENSOR WITH REMOTE TEST CAPABILITY

If replacing the sensor head shipped with D365PL, refer to the control panel 
technical documentation for compatible UL-listed heads with Remote Test Ca-
pability.

To install the RTS151/RTS151KEY, using the sensor with remote test 
capability connect the device as shown in Figure 9; wire runs must be limited 
to 25 ohms or less per interconnecting wire. 

NOTE: Resistor assembly must be in place between RA+ and OUT+ 

 

inside the D365PL for Remote Test function to operate.

FIGURE 9. RTS151/RTS151KEY USING SENSOR WITH REMOTE TEST 

CAPABILITY

RTS151/RTS151KEY

JUMPER

4

5

3

2

1

NOT USED 

NOT USED 

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

H0633-02

[11.2] ADDITIONAL MODULE OPTION

The D365PL can also accommodate a relay or control module (sold sepa-
rately) within the power board side of the housing. The relay or control mod-
ule must be listed as compatible to the fire alarm control panel.

PHYSICAL MODULE MOUNTING 

1.  Remove the breakaway tabs at the four corners of the module.

2.   Locate the module at right most corner of the power board. The upper left 

corner mounting hole of the module will align with a screw boss in the 
housing.

3.   Install a #8×

3

8

˝ Plastite screw at the screw boss location.

Note: See the corresponding module's Installation Instructions for general  
description, control panel compatibility, wiring and ratings.

  

I56-6626-000 

 

 2/26/2019

Содержание Fire-Lite Alarms D365PL

Страница 1: ...rent 200 µA 24 VDC one communication every 5 seconds with LED blink enabled Max Alarm Current LED on 6 2 mA 24 VDC NOTE The D365PL comes with the sensor head factory installed part number SD365R IV TABLE OF CONTENTS PAGE 1 Limitations of Duct Smoke Detectors 1 2 General Description 1 3 Contents of the Duct Smoke Detector Kit 1 4 Detector Installation 2 5 Sampling Tube Installation 2 6 Measurement ...

Страница 2: ... A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 3 2 FOR SQUARE TOP OVER BOTTOM MOUNTING CONFIGURATION Center punch at four target centers two A for sampling tubes and two C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and...

Страница 3: ...er than necessary to span the duct width Use a 0 193 inch diameter 10 drill and add the appropriate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube CAUTION This procedure should only be used as a temporary fix It is not intended as a permanent substitute for ordering the c...

Страница 4: ...ENANCE PROCEDURES Test and maintain duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under test to prevent unwanted alarms ...

Страница 5: ...ING DIAGRAM FOR D365PL TO RA100Z RA100Z RA RA REMOTE ALARM LED OPTION 1 PER UNIT H0570 05 Note Remove jumper when using RA100Z with the intelligent duct smoke detector The RTS151 RTS151KEY Remote Test Station facilitates test of the alarm ca pability of the duct smoke detector These accessories provide the stimulus to initiate an alarm condition at the detector The D365PL duct smoke detector must ...

Страница 6: ...television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the d...

Отзывы: