6. Ex-proof thermostats (Ex-de, Ex-t)
6.2 Connection plan
The terminal board can be accessed after
the protective casing has been removed.
After connecting the supply lines, the
protective casing should in all cases be
reattached.
Fig. 13.
Connection layout
With increasing pressure 3–1 will be
interrupted and 3–2 will be closed.
52
MU2B-0375GE51 R0211A
Connection of conductive protection
accessible after removal of cover.
(See also Fig. 14).
6.3 Electrical ratings of
components
Microswitch
Voltage rating
up to 250 VAC
Current rating at 250 VAC
3 A resistive, 3 A inductive
Current rating at 250 VDC
0.25 A resistive, 0 03 A inductive
Current rating at 125 VDC
0.5 A resistive, 0.06 A inductive
Current rating at 75 VDC
1 A resistive, 1 A inductive
Current rating at 30 VDC
3 A resistive, 3 A inductive