Honeywell FCI 2151 Скачать руководство пользователя страница 2

Ordering Information 

Part Number  Description 

2151  

Photoelectronic detector 

B110LP  

Base, Two-wire 

301BL4 
 

Base, four-wire, 24 VDC operation 
Form A & C 

301BL4AC 
 

Base, four-wire, 120 VAC operation 
Form A, C & Supv. 

B401BH 
 

Base, four-wire, with audible 
sounder 

RA-400Z 

Remote alarm indicator 

PAM-1 

End of line relay, 24 VDC 
Form B 
Test Kit 

 

 

 

Mounting 

  On a 4-inch square box with or without plaster ring. 

Minimum depth 1.5 inches. 

  On a 3.5-inch octagonal box. Minimum depth 1.5 

inches. 

 

Installation 

Place the detector into the detector base. Turn the detec-
tor clockwise until the detector locks into place. 

To use the tamper-proof feature, break the smaller tab on 
the scribed line in the tamper proof tab located on the 
detector mounting bracket. Install the detector. To remove 
the detector from the base when using the tamper-proof 
feature, insert the blade of a small screwdriver into the 
hole on the side of the base and push the plastic lever 
away from the detector head. This will allow the detector 
to be rotated counterclockwise for removal. NOTE: The 
decorative ring must be removed in order to remove the 
head when using the tamper-proof feature. 
 
The tamper-proof feature may be defeated permanently 
by breaking the plastic lever off the base. 
 
Note: The number of two-wire smoke detectors which can 
be accommodated per zone varies with different control 
panels. Consult the control panel instruction manual to 
determine the capacity. 
 
Refer to NFPA 72, Chapter 5-3, “Smoke Sensing Fire 
Detectors” for spacing, location of detectors and other 
guidelines. 
 

Testing 

Detectors may be tested in the following ways: 

 

Place a test magnet against the detector as directed in 
the installation instructions. The detector should go into 
alarm within 30 seconds. 

 Field metering of detector sensitivity may be per-

formed with the aid of a voltmeter and Test Kit, 
MOD 400R.

 

For the complete procedure, refer to the Installation and 
Maintenance instructions furnished with each detector. 
 

Cleaning programs should be adapted to the individual 
environment in conformance with NFPA Standard 72. We 
recommend at least an annual cleaning of the unit. The 
detector screen and cover assembly can be removed, 
revealing the sensing chamber. A vacuum cleaner can be 
used to remove dust from the screen, cover and sensing 
chamber. For the complete procedure, refer to the Instal-
lation and Maintenance instructions furnished with each 
detector. 

Maintenance 

 

GAMEWELL-FCI 

12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118 

 www.gamewell-fci.com

 

9020-0583 Rev. B  page 2 of 2

 