Flexputs™ I/O Circuits
Hardware Installation
2.
Smoke power is supplied to each Class A loop as shown in Figure 3.15.
Figure 3.15 Class A 4-Wire Smoke Detector Connections
3.5.6 Auxiliary Power Configuration
Flexput circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are:
•
Door Holder (see Section for description)
•
Constant (see Section for description)
•
Resettable (see Section for description)
•
Sounder Sync Power (see Section for description)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 5A).
To configure a Flexput circuit as auxiliary power:
1.
Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 3.16 for location or Flexput circuits.
2.
Configure the auxiliary power output through programming for Door Holder, Constant or Resettable power.
Figure 3.16 Flexput Circuits Used as Auxiliary Power
Door Holder Power
Door holder is intended for fire door applications. When there are no alarms in the system and the panel has AC power, door holder cir-
cuits have 24-volt power present at their terminals. Any alarm will cause power to discontinue. Power will be re-applied when the sys-
tem is reset. If AC power is off for more than 15 seconds the auxiliary door holder power will be discontinued to conserve the battery
backup power. When AC power is restored, power is immediately restored to the door holder circuits.
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
NOTE:
In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.15 uses I/O circuits 1, 2, 3 together and 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be
referred to as point 4.