F58G,H AND F58GUV SERIES COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER

31-00442—01

12

1.

Install 202614 Carbon Filters (sold separately).
a. Turn the air cleaner power switch to the OFF posi-

tion.

b. Remove the pre-filter and two electronic cells.
c. Install carbon filters in the rear of the air cleaner 

cabinet. First insert the bottom of the carbon filter 
into the rear channel; then rotate the top of the 
carbon filter back to snap it into place under the 
upper clip.

d. Replace electronic cells and pre-filter.

WARNING

Electric Shock Hazard.
Can cause personal injury.

Only a trained service technician should perform 
the following procedure.

2.

Ozone production may be reduced by about 20 to 
25 percent by moving the EFFY Jumper on the power 
supply. Particle collection efficiency can also be 
reduced by about seven to ten percent.
a. Disconnect power to the air cleaner.
b. Remove the pre-filter and two electronic cells.
c. Remove three screws from the power supply tray 

along the top of the air cleaner.

d. Lower the front edge of the power supply tray to 

expose the power supply.

e. Locate the EFFY shorting bar on the power sup-

ply. See Fig. 14. Remove the shorting bar and 
reinstall on only one pin. Ozone will be reduced 
and the shorting bar will be available for reinstal-
lation, if needed.

f.

Raise the front edge of the power supply tray and 
reinstall the three screws.

g. Replace electronic cells and pre-filter.
h. Turn on the power and repeat the Check Air 

Cleaner Operation procedure in the Checkout 
section.

i.

This function does not apply to F58G1016E, 
F58G1016EUV, F58G1024E and F58G1024EUV.

Fig. 14. Moving EFFY shorting bar to reduce ozone 

production about 20 to 25 percent.

ELECTRICAL 
TROUBLESHOOTING

WARNING

Electric Shock Hazard.
Can cause personal injury or equipment damage.

The following procedures expose hazardous live 
parts and are for use only by qualified personnel.
Disconnect power between checks and proceed 
carefully.

Tools and Equipment

Troubleshooting the electronic air cleaner requires:
• Needlenose pliers for stringing ionizer wires and 

inserting edge connectors.

• Ohmmeter.

Test Button

When pushed, the Test button shorts from collector voltage 
to ground. The resulting arcing sound indicates that high 
voltage is being supplied to the collector. The solid state 
power supply controls current flow to the collector. The 
CHECK indicator activates when the Test button is held 
down.

CHECK Indicator

The CHECK indicator activates to indicate the following 
problems:
• Excessive  dirt  loading.
• Partial shorting of collector.
• Continuous ionizer or collector arcing.
• Power supply failure.
• Excessive ionizer current.
• Any condition causing a major reduction in high voltage.

Power Supply

WARNING

Electric Shock Hazard.
Can cause personal injury.

Turn off power before accessing the power supply.

The solid state power supply can be replaced when 
troubleshooting indicates a problem.

Troubleshooting Procedure

The electronic air cleaner troubleshooting diagram shows 
how to quickly isolate a problem in the air cleaner. 
Although an ohmmeter is needed in some steps, the 
primary diagnostic tools are the status indicators and the 
Test button. See Fig. 15.

P3

P4

P1

P2

M10609A

J3

J4

J1

EFFY

Содержание F58G

Страница 1: ...ir cleaners Solid state power supply is self regulating and maintains peak efficiency during a wide range of cell dirt loading conditions Indicator lights signal proper operation and fault conditions May be connected to a building management system Relay closure occurs when fault occurs or when cells need cleaning Galvanized cabinet protects against rust Test button checks system operation Pre fil...

Страница 2: ...tronic Cell each 9 3 16 lb 4 2 kg Shipping Weight F58G 42 lb 19 1 kg F58H 26 7 lb 12 1 kg F58G UV 46 lb 20 9 kg Installed Weight Cells Included F58G 37 lb 16 8 kg F58H 24 lb 10 9 kg F58G UV 41 lb 18 6 kg Dimensions See Fig 3 and Fig 4 Accessories 202614 Carbon Filter 13643AA Ionizer Wires quantity 5 32350736 001 UV tube Repair Parts See Parts List section Regulatory Approvals Ozone free UV tube me...

Страница 3: ...at various airflow rates FRACTIONAL EFFICIENCY PARTICAL DIAMETER Pm EFFICIENCY RATINGS BASED ON AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR CONDITIONING ENGINEERS STANDARDS 52 2 2012 10 1 0 1 100 80 60 40 20 0 0 0 AIR FLOW RATE IN CFM cum hr PRESSURE DROP IN in wc Pa 0 1 24 9 0 2 49 8 0 3 74 7 0 4 99 5 0 5 124 4 2000 3400 500 850 1000 1700 1500 2500 2500 4250 ...

Страница 4: ...NTED ELECTRONIC AIR CLEANER 31 00442 01 4 Fig 3 F58G Installation dimensions of electronic air cleaner in in mm Shown with UV lamp optional Fig 4 F58H Installation dimensions of electronic air cleaner in in mm 6 3 4 171 13 25 32 350 24 610 3 8 10 ...

Страница 5: ...team coils with a freeze up control Choosing Mounting Position WARNING Heavy Equipment Hazard Can cause injury or equipment damage Mount the air cleaner with the power supply on top Do not mount the air cleaner with the pre filter facing down the latches may not hold and the cell and pre filter can fall unexpectedly WARNING Be careful of damage to equipment Ultraviolet light can cause color fading...

Страница 6: ...ring normal operation of HVAC equipment Fig 6 Changing duct size gradually to minimize turbulence INSTALLATION When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a...

Страница 7: ...ion When properly installed the actuator on the pre filter is inserted into the wiring tray of the air cleaner Rotate the latch to secure the pre filter in place WIRING WARNING Electric Shock Hazard Can cause personal injury Be sure line voltage power source is the same as the voltage and frequency listed on the air cleaner label Power supply wiring system shall provide a disconnect switch for all...

Страница 8: ...W VOLTAGE CONNECTION TO BUILDING MANAGEMENT SYSTEM OR PLUG INTO ADJACENT UNIT 24V A C OR 24V D C 2A MAXIMUM STATUS INDICATION LED TWO OR THREE 5 4 3 2 1 INSTALL JUNCTION BOX ON THE END OF EACH ROW 6 JUNCTION BOX 6 ON OFF SWITCH INTERLOCK SWITCH SWITCH OFF WHEN REMOVING PRE FILTER AND SWITCH ON WHEN PRE FILTER INSTALLED CONNECT TO MAIN POWER OR PLUG INTO ADJACENT UNIT LOW VOLTAGE CONNECTION TO BUIL...

Страница 9: ...supply mains SERVICE CAUTION Sharp Edges Can cause personal injury Wear protective gloves to prevent cuts from sharp metal edges Cleaning Cells and Pre filters To assure optimum performance from the air cleaner the cells and pre filters must be cleaned regularly every one to six months WASH indicator on some models lights to indicate it is time to wash the pre filters and cells IMPORTANT Do not wa...

Страница 10: ...cells and pre filters in a final clear water rinse for ten minutes 7 Wipe the ionizer wires and contact board on the end of the cell using your thumb and forefinger with a small damp cloth 8 Make sure to dry the cells before inserting back into the air cleaner Reinstalling Cells and Pre filters Insert the electronic cell with the contact board up and the air flow arrow pointing downstream Tilt the...

Страница 11: ...Electric Shock Hazard Can cause personal injury Disconnect power before opening power supply cover The electronic air cleaner generates a small amount of ozone in normal operation During the first week or two of operation the amount may be higher because of sharp edges on some of the new high voltage metal parts Normal use quickly dulls these edges The average person can detect the odor of ozone i...

Страница 12: ...Checkout section i This function does not apply to F58G1016E F58G1016EUV F58G1024E and F58G1024EUV Fig 14 Moving EFFY shorting bar to reduce ozone production about 20 to 25 percent ELECTRICAL TROUBLESHOOTING WARNING Electric Shock Hazard Can cause personal injury or equipment damage The following procedures expose hazardous live parts and are for use only by qualified personnel Disconnect power be...

Страница 13: ...ECTION CELL FRAME AND COLLECTOR SECTION CELL SHORTED INFINITE RESISTANCE REPLACE CELL CELL OK REPLACE POWER SUPPLY M13460 FOLLOW THE STEPS IN ORDER DO NOT SKIP AROUND EACH TIME YOU ISOLATE AND FIX A PROBLEM GO BACK TO START REPEAT ALL THE STEPS UNTIL THE AIR CLEANER CHECKS OUT OK 1 2 3 THIS STEP EXPOSES DANGEROUSLY HIGH VOLTAGE ONLY A QUALIFIED SERVICE TECHNICIAN SHOULD ATTEMPT THIS STEP WARNING C...

Страница 14: ... V a c 50 Hz CE version 42009287APE 5 Interlock Switch 196277 6 Power Switch 203321 7 Contact Board Assembly 32003893 001 8 Building Management Interface Circuit Board with ON CHECK and with WASH functions with BMS F58G1016 50043779 001U Building Management Interface Circuit Board with ON CHECK functions without WASH without BMS F58G1024 32003942 001U 9 UV Tube 32350736 001 U 10 Ballast 32350743 0...

Страница 15: ... F58H Replacement Parts Reference No Description Part Number 1 Prefilter 50081476 002 2 Electronic Cell FC37B1030 U 3 Contact Board Assembly 32003893 001 4 Interlock Switch 196227 Optional Accessories not shown in diagram Ionizer Wires Quantity 5 136434AA Carbon Filter Only applicable for NON UV version 202614 3 4 2 1 ...

Страница 16: ...mber 9439 92 1 may be contained in these products above the threshold level of 0 1 by weight of the listed article Honeywell Part Number 32000392 585 32000392 601 32000388 401 32000388 709 32000392 451 32000392 689 32000388 422 32000392 251 32000392 385 32002633 004 32000388 481 32000392 373 32000388 447 32000384 211 32000388 709 32000392 389 32000392 466 32000384 301 32000392 251 32000392 401 320...

Отзывы: