Honeywell F115A1064 Скачать руководство пользователя страница 4

MOUNTED MEDIA AIR CLEANERS

68-0201—05

4

Mount and Wire the Air Cleaner

CAUTION

Eye Exposure.
Harmful dust can obstruct or injure unshielded 
eyes.

A CPZ™ module usually releases dust when it is 
handled. 
Always wear safety glasses when installing or 
removing CPZ™ canisters.

IMPORTANT

When installing the air cleaner, be sure to follow all 
local codes and accepted practices.

1.

Decide if the air cleaner wire connections will be 
from the top or the side. Make the necessary wiring 
provisions at the ceiling.

2.

Grasp the air cleaner cover edge near the plenum 
and remove the cover from the support brackets. Set 
it aside.

3.

Loosen and remove the filter securing nuts, holding 
plates and filters. Set them aside.

4.

Insert fastening hardware (lag bolts, eye bolts or 
threaded rod) through the 3/8 in. (10 mm) mounting 
holes in the filter/motor bases. See Fig. 1.

5.

Secure the air cleaner to the ceiling load bearing 
supports or joists. If installing on a T-grid drop ceil-
ing, secure the air cleaner to the true ceiling.

6.

Fasten the plenum assembly snugly against the ceil-
ing.

IMPORTANT

Do not over-tighten the plenum fasteners which 
can collapse or break the plastic base/plenum.

7.

Connect the power. See Fig. 3.

Fig. 3. F115 Media Air Cleaner (120, 60 Hz) typical 

wiring diagram.

IMPORTANT

Make sure the air cleaner is grounded for proper 
operation and safety.

8.

Turn on the power and check that the blowers are 
operating freely.

9.

Position the filter cartridges on the filter base.

10.

Insert the CPZ™ cartridge with the cartridge base 
notches against the motor towers.

11.

Attach the filter cover plates.

12.

Replace the air cleaner cover.

OPERATION

The F115 Ceiling Surface Mounted Media Air Cleaners 
provide their own air circulation. When the air cleaner is 
powered, the blower/motor draws the contaminated air 
into the air cleaner. Particles that are too small to be 
caught in the prefilter are removed by the particle or HEPA 
filter. The cleaned air is then returned to the building 
space. 

In areas with ceilings up to 10 feet high, the F115 models 
can clean a 600 to 1200 sq ft (54 to 108 sq m) area.

SERVICE

The air cleaner removes a variety of particulate 
contaminants from the air. In the process of cleaning the 
air, the air cleaner filters become dirty.

To maintain a high standard of reliability and efficiency, it 
is necessary to periodically service the air cleaner. The 
filter life is determined by the quantity and type of 
contaminants present and the frequency of air cleaner 
use. In relatively clean spaces, the filter life can extend as 
long as 30 months. In areas that are very smoky and dusty, 
filters need to be replaced sooner. The frequency of 
servicing can only be established after a period of use.

NOTE:

Some Full-Service Distributors provide regular 
servicing to commercial establishments.

CAUTION

Electrical Shock Hazard.
Power source can shock.

• Turn off the power to the air cleaner when 

cleaning or servicing.

• Stand on a stable platform when working with 

the air cleaner.

CAUTION

Eye Exposure.
Harmful dust can obstruct or injure unshielded 
eyes.

A CPZ™ module usually releases dust when it is 
handled.
Always wear safety glasses when installing or 
removing CPZ™ canisters.

MOTOR

MOTOR

MOTOR

MOTOR

WHITE (N)

BLACK (L1)

GREEN/YELLOW

JUNCTION BOX

CONDUIT IN PLENUM

M12736A

WHITE (N)

BLACK (L1)

GREEN/YELLOW

WHITE (N)

WHITE (N)

BLACK (L1)

BLACK (L1)

GREEN/YELLOW

GREEN/YELLOW

Содержание F115A1064

Страница 1: ...Hospital grade filter 95 efficient at 0 3 micron MERV 16 F115 single speed models deliver up to 600 cfm 1020 m3 hr Select models include CPZ disposable canisters for odor control Light colored covers complement the ceiling finish Available in 120 Vac 60 Hz SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances There fore this unit may n...

Страница 2: ... being switched on accidentally when servicing or cleaning the media air cleaner Choose Location The air cleaner is mounted horizontally and can be used in almost any air cleaning application For the most efficient operation centrally locate the air cleaner to the area to be cleaned For the best air patterns avoid discharging the air directly at an obstruction such as a ceiling beam decorative cor...

Страница 3: ...o make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock Hazard Power source can shock Do not connect the power source until after the air cleaner is mounted This will prevent electrical shock or equipment damage Be sur...

Страница 4: ...plates 12 Replace the air cleaner cover OPERATION The F115 Ceiling Surface Mounted Media Air Cleaners provide their own air circulation When the air cleaner is powered the blower motor draws the contaminated air into the air cleaner Particles that are too small to be caught in the prefilter are removed by the particle or HEPA filter The cleaned air is then returned to the building space In areas w...

Страница 5: ...e is a noticeable loss of air volume circulation approximately every 10 to 24 months 6 Reassemble the air cleaner and turn the power on PARTS LIST Refer to Table 2 and Fig 4 for a parts list and an exploded view of the parts Table 2 F115 Ceiling Surface Mounted Media Air Cleaner Parts List Fig Reference No Description Pack Qty Order Number 1 Blower Wheel 2 120V 60 Hz Single Speed Motor 3 Mid plate...

Страница 6: ...MOUNTED MEDIA AIR CLEANERS 68 0201 05 6 Fig 4 Exploded view of F115 Ceiling Surface Mounted Media Air Cleaner components ACCESS PLATE INSPECTION PLATE PLENUM M12712B 8 1 2 3 4 5 6 7 ...

Страница 7: ...MOUNTED MEDIA AIR CLEANERS 7 68 0201 05 ...

Страница 8: ...S Honeywell Building Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 68 0201 05 M S Rev 08 20 Printed in United States ...

Отзывы: