Honeywell F115A1064 Скачать руководство пользователя страница 1

PRODUCT DATA

68-0201-05

F115 Ceiling Surface
Mounted Media Air Cleaners

GENERAL

The F115 Ceiling Surface Mounted Media Air Cleaners use 
direct-drive, forward curve, blower/motors with 95% D.O.P. 
(MERV 16) particle or HEPA filters to remove airborne 
contaminants. The air cleaners are designed for use in 
restaurants, conference rooms, lounges and offices where 
overhead air cleaning is required. They provide their own 
air circulation, so the air cleaners can be used in any 
situation that requires the reduction of contamination 
from an enclosed area.

FEATURES

• High Efficiency Particulate AIR (HEPA) filter models are 

99.97% efficient and the D.O.P. particle filter models 
are 95% efficient at 0.3 micron particles. Both models 
are more efficient on particles smaller and larger.

• Two levels of filtration:

99.97% High Efficiency Particulate Air (HEPA) 

Hospital grade filter 95% efficient at 0.3 micron 
(MERV 16)

• F115 single speed models deliver up to 600 cfm (1020 

m3/hr).

• Select models include CPZ™ disposable canisters for 

odor control.

• Light colored covers complement the ceiling finish.
• Available in 120 Vac, 60 Hz

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not 
include normal manufacturing tolerances. There-
fore, this unit may not exactly match the listed 
specifications. This product is tested and cali-
brated under closely controlled conditions, and 
some minor differences in performance can be 
expected if those conditions are changed.

Models: 

Refer to Table 1 for model descriptions.

Color: 

White cabinet and cover

Blower/Motor:  

Single-speed, direct-drive, forward curve.

Dimensions: 

See Fig. 1 for dimensions.

Table 1. F115 Description

Model

Input Power

Filter Rating

Approximate weight of CPZ

TM 

sorbent filters (pounds)

Air Volume in

CFM (m

3

/hr)

F115A1064

120 Vac, 60Hz, 

1PHS, 7.2A

99.97% HEPA

N/A

600 (1020)

F115A1005

120 Vac, 60Hz, 

1PHS, 7.2A

95% at 0.3 micron 

(MERV 16)

16

600 (1020)

Содержание F115A1064

Страница 1: ...Hospital grade filter 95 efficient at 0 3 micron MERV 16 F115 single speed models deliver up to 600 cfm 1020 m3 hr Select models include CPZ disposable canisters for odor control Light colored covers complement the ceiling finish Available in 120 Vac 60 Hz SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances There fore this unit may n...

Страница 2: ... being switched on accidentally when servicing or cleaning the media air cleaner Choose Location The air cleaner is mounted horizontally and can be used in almost any air cleaning application For the most efficient operation centrally locate the air cleaner to the area to be cleaned For the best air patterns avoid discharging the air directly at an obstruction such as a ceiling beam decorative cor...

Страница 3: ...o make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock Hazard Power source can shock Do not connect the power source until after the air cleaner is mounted This will prevent electrical shock or equipment damage Be sur...

Страница 4: ...plates 12 Replace the air cleaner cover OPERATION The F115 Ceiling Surface Mounted Media Air Cleaners provide their own air circulation When the air cleaner is powered the blower motor draws the contaminated air into the air cleaner Particles that are too small to be caught in the prefilter are removed by the particle or HEPA filter The cleaned air is then returned to the building space In areas w...

Страница 5: ...e is a noticeable loss of air volume circulation approximately every 10 to 24 months 6 Reassemble the air cleaner and turn the power on PARTS LIST Refer to Table 2 and Fig 4 for a parts list and an exploded view of the parts Table 2 F115 Ceiling Surface Mounted Media Air Cleaner Parts List Fig Reference No Description Pack Qty Order Number 1 Blower Wheel 2 120V 60 Hz Single Speed Motor 3 Mid plate...

Страница 6: ...MOUNTED MEDIA AIR CLEANERS 68 0201 05 6 Fig 4 Exploded view of F115 Ceiling Surface Mounted Media Air Cleaner components ACCESS PLATE INSPECTION PLATE PLENUM M12712B 8 1 2 3 4 5 6 7 ...

Страница 7: ...MOUNTED MEDIA AIR CLEANERS 7 68 0201 05 ...

Страница 8: ...S Honeywell Building Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 68 0201 05 M S Rev 08 20 Printed in United States ...

Отзывы: