7.1 C300 controller module and IOTA replacement
To replace a non-redundant controller module, perform the following steps:
Prerequisites
• These procedures can only be performed while off process.
• We recommend that you proceed with extreme caution whenever replacing any component in a control
system.
• Be sure the system is offline or in a safe operating mode.
• Component replacements may also require corresponding changes in the control strategy configuration
through Control Builder, as well as downloading appropriate data to the replaced component.
• Note that all modules are keyed.
1
Loosen screws at each side of the module cover that secures the controller module to the IOTA board.
2
Carefully remove the Controller module from the IOTA board and connector.
3
Insert the new controller module onto the IOTA board making sure that the controller circuit board mates
properly with the IOTA board connector.
4
Secure the controller module to the IOTA board with two screws located at each side of the plastic cover.
5
The new controller will boot-up to
ALIVE
or
NODB
state.
6
Load firmware. Ensure that the version is the same as was running on the old controller.
7
On
Control Builder
, perform a
Load with Contents
to the controller.
To replace a non-redundant controller IOTA board, perform the following steps.
1
On the defective IOTA, loosen screws at each side of the module cover that secures the controller module to
the IOTA board.
2
Carefully remove the controller module from the IOTA board and connector.
3
Label and disconnect all cables from the IOTA board connectors, (yellow and green FTE cables, gray and
violet I/OLink cables, and Battery cable).
4
Loosen the four mounting screws only half-way that secure the IOTA board to the channel.
5
Remove completely the four mounting screws securing the IOTA board to the channel and remove the
IOTA.
6
Place screws, washers and spacers aside for reassembly.
7
Assemble screws, washers and spacers on the new IOTA board. Mount new controller IOTA board on the
channel at the same position as the old IOTA board.
8
Insert and thread the four mounting screws only half-way to attach the IOTA board to the channel. Do not
tighten.
9
Tighten the four mounting screws securing the IOTA board to the channel.
10
Set the Device Index address to the same address as the old IOTA using the three rotory FTE DEVICE
INDEX switches.
11
Connect
FTE-A
and
FTE-B
Ethernet link cables to the
RJ-45
connectors on C300 IOTA board.
12
The
yellow
Cat5 cable connects to the
FTEA
connector on the IOTA.
13
The green Cat5 cable connects to the
FTEB
connector on the IOTA.
14
Connect I/O Link cables to IOTA board, if present.
a
Connect the gray I/O LINK cable to
IOL1A
and
IOL1B
for
IOLINK 1
interface of the controller.
b
Connect the violet IOLINK cable to
IOL2A
and
IOL2B
for
IOLINK 2
interface of the controller.
15
Install the two-wire twisted pair battery cables onto the
Memory Hold Up
connector on the left side of the
IOTA board.
7 MAINTENANCE
30
www.honeywell.com
Содержание Experion LX 8 series
Страница 1: ...Experion LX Series 8 Cabinet Installation Instruction EXDOC X290 en 500A April 2017 Release 500 ...
Страница 4: ...CONTENTS 4 www honeywell com ...
Страница 6: ...1 ABOUT THIS DOCUMENT 6 www honeywell com ...
Страница 12: ...2 OVERVIEW OF CE COMPLIANCE 12 www honeywell com ...
Страница 15: ...3 MOUNTING AND SEGREGATION OF WIRING 15 ...
Страница 19: ...Figure 2 Typical safety ground connections in cabinet 4 BONDING AND GROUNDING 19 ...
Страница 24: ...5 POWER SUPPLY SELECTION AND DISTRIBUTION 24 www honeywell com ...
Страница 36: ...7 MAINTENANCE 36 www honeywell com ...
Страница 40: ...8 DECLARATION OF CONFORMITY 40 www honeywell com ...
Страница 41: ...9 Conclusions Related topics Conclusions on page 42 41 ...