Technical description

Part no.:

Battery (NiMH):
Battery Protection:
Min./Max. Charge Current:

40 / 125mA

Overcharge protection / Deep discharge protection

o

5 to 40  C

Up to 95%

16 hours

Produced in accordance with:

Ambient Temperature Range:

Maximum Power Consumption:

Operation Voltage:

Relative Humidity:

Charging Time:

Technical lifetime (light source):

Lumen output, normal:

> 100000 hours

150lm

180lm

ExiLED M ST LED 25m

ExiLED M ST LED 40m

3.3W / 3.5V

3.5W / 3.7VA

220-240V AC, 50-60 Hz

138126

138087

3.6V / 1.2Ah

IP40

1h / 3h / 8h manually selected (default 1h)

Degress of cover protection:

Emergency Mode Duration:

EN 60598-1, EN 60598-2-22, EN 55015 
EN 61547, EN 61000-3-2, EN 61000-3-3

Charge Voltage Range:

3 - 4.5V

Lumen output, emergency (1h/3h/8h):

180/110/40lm

210/110/40lm

Weight:

Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function

540 gr

690 gr

4 years

Every 15 days the luminaire will perform an emergency operation test. This will light the exit sign for approximately 3 
seconds. The red indicator LED will flash during this test sequence.

It can be configured as maintained or non-maintained.

By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed. The exit sign will be lit for 
approximately 3 seconds, the red indicator LED will flash during this test sequence.

The ExiLED is a self-contained LED exit sign with selftest function.

Selftest functions

Every 6 months the luminaire will perform a battery condition test. The test will last for the stated duration. The exit sign will 
be lit and the yellow indicator LED will flash during this test sequence.

Note:

 When using DALI or Wireless communication, the frequencies and schedules for tests will instead be determined by 

the connected PC software.

Manual test functions

Manual tests can only be performed if both mains and battery are connected.

By pressing the test button for a time space between 5 and 10 seconds, a battery condition test is performed. This test will 
last for the stated duration and can only be performed when the battery is fully charged (steady green indicator LED). The 
exit sign will be lit and the yellow indicator LED will flash during this test sequence.

Push the test button for a time space between 10 and 15 seconds to delete all indicated errors. Then the luminaire enters 
regular operation mode.
 

Dimming

By pressing the test button continuously for 15 seconds, when luminaire is connected to mains, the luminosity will be 
reduced to 10% of its total luminance. In emergency mode the light output will remain unchanged.
To restore the original settings, repeat the above procedure.
The dimming setting remains stored in the luminaire even when both mains and battery voltages are disconnected.

Resetting errors