Technical description
Part no.:
Battery (NiMH):
Battery Protection:
Min./Max. Charge Current:
40 / 125mA
Overcharge protection / Deep discharge protection
o
5 to 40 C
Up to 95%
16 hours
Produced in accordance with:
Ambient Temperature Range:
Maximum Power Consumption:
Operation Voltage:
Relative Humidity:
Charging Time:
Technical lifetime (light source):
Lumen output, normal:
> 100000 hours
150lm
180lm
ExiLED M ST LED 25m
ExiLED M ST LED 40m
3.3W / 3.5V
3.5W / 3.7VA
220-240V AC, 50-60 Hz
138126
138087
3.6V / 1.2Ah
IP40
1h / 3h / 8h manually selected (default 1h)
Degress of cover protection:
Emergency Mode Duration:
EN 60598-1, EN 60598-2-22, EN 55015
EN 61547, EN 61000-3-2, EN 61000-3-3
Charge Voltage Range:
3 - 4.5V
Lumen output, emergency (1h/3h/8h):
180/110/40lm
210/110/40lm
Weight:
Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function
540 gr
690 gr
4 years
Every 15 days the luminaire will perform an emergency operation test. This will light the exit sign for approximately 3
seconds. The red indicator LED will flash during this test sequence.
It can be configured as maintained or non-maintained.
By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed. The exit sign will be lit for
approximately 3 seconds, the red indicator LED will flash during this test sequence.
The ExiLED is a self-contained LED exit sign with selftest function.
Selftest functions
Every 6 months the luminaire will perform a battery condition test. The test will last for the stated duration. The exit sign will
be lit and the yellow indicator LED will flash during this test sequence.
Note:
When using DALI or Wireless communication, the frequencies and schedules for tests will instead be determined by
the connected PC software.
Manual test functions
Manual tests can only be performed if both mains and battery are connected.
By pressing the test button for a time space between 5 and 10 seconds, a battery condition test is performed. This test will
last for the stated duration and can only be performed when the battery is fully charged (steady green indicator LED). The
exit sign will be lit and the yellow indicator LED will flash during this test sequence.
Push the test button for a time space between 10 and 15 seconds to delete all indicated errors. Then the luminaire enters
regular operation mode.
Dimming
By pressing the test button continuously for 15 seconds, when luminaire is connected to mains, the luminosity will be
reduced to 10% of its total luminance. In emergency mode the light output will remain unchanged.
To restore the original settings, repeat the above procedure.
The dimming setting remains stored in the luminaire even when both mains and battery voltages are disconnected.