ADT-HRSI INTELLIGENT HEAT DETECTOR

Home

 

and

 

Building

 

Control

Home & Building Control

European Centre of Excellence

Honeywell Inc.

Honeywell GmbH

Fire Solutions

Honeywell Plaza

Honeywellstrasse

Lovelace Road, Southern Industrial Area

P.O. Box 524

63477 Maintal 1

Bracknell, Berkshire,  RG12 8WD

Minneapolis MN 55408-0524

Germany

United Kingdom

EN0C-0746E 0599R0-OB Printed in U.S.A.

SPECIFICATIONS

Heat Sensor:

Combination fixed temperature and rate of rise, alarms at

57°C (135°F) ambient or temp. increases greater than
9°C (15°F) per min.

Detector Spacing:

70ft (21.3m) center to center

Environmental Limits:

Temperature: 32° to 100°F (0° to 38°C)
Humidity: 0 to 93% rh, non-condensing

Voltage:

15.2  to 19.95 Vdc (19 Vdc nominal)

Operating Current:

Stand-by: 45

µ

A at 19V

Alarm: 45

µ

A at 19V

Emergency stand-alone alarm mode: 18mA
Pulse current: 100

µ

A (100 msec)

During communication: 9 mA max.

Construction:

High impact engineering polymer

Finish:

White

Compatible Mounting Bases:

SIGA-SB standard base
ADT-RB relay base
ADT-IB and ADT-IBS isolator base

LED Operation:

On-board green LED: Flashes when polled
On-board red LED: Flashes when in alarm
Both LEDs: On steady when in alarm (stand-alone)

Compatible remote red LED:

Flashes when in alarm

Compatibility:

Signature loop controller

Address Requirements:

1 device address

Accessories:

SIGA-SB:  Detector mounting base
ADT-RB: 

Detector mounting base with relay

ADT-IB: 

Detector mounting base with fault isolator

ADT-IBS: 

Same as above, with loop continuity switch

SIGA-LED:  Remote alarm LED
SIGA-TS: 

Trim skirt (supplied with 4in bases)

74-3346    J.S.    12-99

Содержание EXCEL ADT-HRSI

Страница 1: ...C 15 F per minute rate of rise and 57 C 135 F fixed temperature alarm threshold Intelligent detector with integral microprocessor Non volatile memory Automatic device mapping Electronic addressing Identification of defective detectors Twin status LEDs Standard relay and fault isolator mounting bases Designed and manufactured to ISO 9001 standards Original detector sensitivity values upon manufactu...

Страница 2: ...ance technician Quality and Reliability Honeywell detectors are manufactured to strict international ISO 9001 standards All electronics utilize surface mount technology SMT for smaller size and greater immunity to RF noise A conformal coating is used for humidity and corrosion resistance All critical contacts are gold plated Electronic Addressing The loop controller electronically addresses each d...

Страница 3: ...relay is controlled by the detector or the loop controller A maximum of 96 isolator bases can be installed on one circuit The isolator base does not support the SIGA LED Remote LED The isolator operates as follows a short on the line causes all isolators to open within 23 msec at 10 msec intervals beginning nearest the loop controller the isolators close to provide the next isolator down the line ...

Страница 4: ...to 19 95 Vdc 19 Vdc nominal Operating Current Stand by 45µA at 19V Alarm 45µA at 19V Emergency stand alone alarm mode 18mA Pulse current 100µA 100 msec During communication 9 mA max Construction High impact engineering polymer Finish White Compatible Mounting Bases SIGA SB standard base ADT RB relay base ADT IB and ADT IBS isolator base LED Operation On board green LED Flashes when polled On board...

Отзывы: