Intelligent Heat Detector

SPECIFICATION DATA

DESCRIPTION

Honeywell's Signature Series Model ADT-HRSI Intelligent
Heat Detectors gather analog information from their fixed
temperature and/or rate-of-rise heat sensing elements and
converts it into digital signals. The detector's on-board
microprocessor measures and analyzes these signals. It
compares the information to historical readings and time
patterns to make an alarm decision. Digital filters remove
signal patterns that are not typical of fires. Unwanted alarms
are nearly eliminated.

The microprocessor in each detector provides four additional
benefits; self-diagnostics and history log, automatic device
mapping, stand-alone operation and fast, stable
communication.

Self-diagnostics and History Log:

Each Signature Series detector constantly runs self-checks
to provide important maintenance information. The results
of the self-check are automatically updated and permanently
stored in the detector's non-volatile memory. This information
is accessible for review any time at the control panel, PC, or
by using the SIGA-PRO Signature Program/Service Tool.
The information stored in the detector's memory includes:

- Detector serial number, address, and type
- Date of manufacture, hours of operation, and last

maintenance date

- Current detector sensitivity values and the extent of

environmental compensation

FEATURES

 

70ft (21.3 meter) spacing

 

 

9°C (15°F) per minute rate-of-rise and 57°C (135°F)
fixed temperature alarm threshold

 

 

Intelligent detector with integral microprocessor

 

 

Non-volatile memory

 

 

Automatic device mapping

 

 

Electronic addressing

 

 

Identification of defective detectors

 

 

Twin status LEDs

 

 

Standard, relay, and fault isolator mounting bases

 

 

Designed and manufactured to ISO 9001 standards

- Original detector sensitivity values upon manufacturing
- Number of recorded alarms and troubles
- Time and date of last alarm
- Analog signal patterns just before the last alarm
- Up to 32 possible trouble codes which may be used to

diagnose faults.

In the unlikely event that an unwanted alarm does take place,
the history file can be called up to help isolate the problem
and prevent it from happening again.

Automatic Device Mapping:

The loop controller learns where each device's serial number
address is installed relative to other devices on the circuit.
This "mapping" feature provides supervision of each device's
installed location to prevent a detector from being reinstalled
(after cleaning etc.) in a different location from where it was
originally. The history log for the detector at its original
location remains relevant and intact.

The Signature Series Data Entry Program also uses the
mapping feature. With interactive menus and graphic
support, the wired circuits between each device can be
examined. Layout or "as-built" drawing information showing
wire branches (T-taps), device types and their address are
stored on disk for printing hard copy. This takes the "mystery"
out of the installation. The preparation of "as-built" drawings
is fast and efficient.

S      Y      S      T      E      M

74- 3346

Содержание EXCEL ADT-HRSI

Страница 1: ...C 15 F per minute rate of rise and 57 C 135 F fixed temperature alarm threshold Intelligent detector with integral microprocessor Non volatile memory Automatic device mapping Electronic addressing Identification of defective detectors Twin status LEDs Standard relay and fault isolator mounting bases Designed and manufactured to ISO 9001 standards Original detector sensitivity values upon manufactu...

Страница 2: ...ance technician Quality and Reliability Honeywell detectors are manufactured to strict international ISO 9001 standards All electronics utilize surface mount technology SMT for smaller size and greater immunity to RF noise A conformal coating is used for humidity and corrosion resistance All critical contacts are gold plated Electronic Addressing The loop controller electronically addresses each d...

Страница 3: ...relay is controlled by the detector or the loop controller A maximum of 96 isolator bases can be installed on one circuit The isolator base does not support the SIGA LED Remote LED The isolator operates as follows a short on the line causes all isolators to open within 23 msec at 10 msec intervals beginning nearest the loop controller the isolators close to provide the next isolator down the line ...

Страница 4: ...to 19 95 Vdc 19 Vdc nominal Operating Current Stand by 45µA at 19V Alarm 45µA at 19V Emergency stand alone alarm mode 18mA Pulse current 100µA 100 msec During communication 9 mA max Construction High impact engineering polymer Finish White Compatible Mounting Bases SIGA SB standard base ADT RB relay base ADT IB and ADT IBS isolator base LED Operation On board green LED Flashes when polled On board...

Отзывы: