EXCEL 12 MODULES 

EN1B-0201GE51 R0905C 

 

4

Rel5

NO

Rel5

NC

Rel5

COM

Rel4

NO

Rel4

NC

Rel4

COM

QL

 

QN

Rel3

NO

Rel2

NO

Rel1

NO

Rel123

COM

QL

QN

58

57

56

55

sunblind

54

53

52

51

50

49

48

47

46

45

0

LOW

4 A

MED

HI

N

L

FAN

Rel5

NO

Rel5

NC

Rel5

COM

Rel4

NO

Rel4

NC

Rel4

COM

QL

 

QN

Rel3

NO

Rel2

NO

Rel1

NO

Rel123

COM

QL

QN

58

57

56

55

sunblind

54

53

52

51

50

49

48

47

46

45

0

LOW

4 A

MED

HI

N

L

FAN

230 Vac
120 Vac

24 Vac

+/-20%

24 V

0

24 V

0

24 V

~

24 V

~

2

2

1

1

24 V

0

24 V

0

24 V

~

24 V

~

23

23

22

22

M

M

fu

ses d

e

p

endent

upon y

our t

ran

s

form

e

r

 

Fig. 6. Connection to 24 Vac power supply 

 

NOTE:

  The max. current at the field device supply terminals 

and all triac outputs together must not exceed 
500 mA continuous. Disregarding these limits can 
result in the destruction of the built-in transformer. 

 
The 24 V models have a power consumption of under 6.5 VA. 
 

Wall Modules 

Table 1. Supported wall module functions 

 

T7560 

button 

bypass 

unit 

ON/OFF 

fan speed

T7460C 

 

 

 

 

T7460D 

 

 

 

 

T7460E 

 

 

 

 

T7460F 

 

 

 

 

left    

 

middle  

 

 

T7560A 

right 

 

 

 

left    

 

middle  

 

 

T7560B 

right 

 

 

 

 
The T7460 and T7560 Wall Modules can be used in con-
junction with the Excel 12 to perform room temperature 
sensing, set-point adjustment, fan speed manual override, 
and occupancy bypass. When hardwired to the Excel 12, the 
wall module's LED/LCD can be configured to provide 
information about the effective occupancy mode, etc. (see 
section "Configuration of the Wall Module's LED / LCD"). 
 

NOTE:

  The intended use of the wall module's buttons must 

be configured using Honeywell's LNS plug-in. 

 

Example: 

The T7560A has a left button which can be configured to act 
as a “fan speed” button, a middle button which can be 
configured to act as a “unit ON/OFF” button, and a right 
button for “bypass.” 
 

Wall Module Connection 

 

AI7

0

AI7

Y

AI6

0

AI6

Y

AI5

Y

AI5

0

LED

Out

AI4

Y

AI3

Y

AI2

Y

AI1

Y

24V~
Out 0

21

20

19

18

17

16

15

14

13

12

11

10

24V~
Out ~

9

Excel 12

com-

mon

temp.

sensor

set-

point

bypass

fan

LED

in

not

used

not

used

24V~

1

2

3

4

5

6

7

8

T7560

BI2

Y

8

 

Fig. 7. Wall module connection 

 

Configuration of the Wall Module's LED / LCD 

When either a T7460 and T7560 Wall Module has been 
hardwired to the Excel 12, its LED can be configured (using 
Honeywell's LNS plug-in) to provide information about e.g. 
overrides or effective occupancy modes. Further, in the case 
of a T7560 Wall Module, its LCD can likewise be configured 
to display such information. 
 

Configuration of the LED to Display Info on Overrides 

The wall module's LED can indicate if an override has been 
activated by either the wall module's bypass button being 
pushed or because the Excel 12 has received a network 
command. Specifically: 

  If the wall module's LED is OFF, then no override (from 

the wall module or the L

ON

W

ORKS

 network) is currently in 

effect. 

  If the wall module's LED is ON continuously, the bypass 

button or a network command has placed the Excel 12 
into the "occupied" or "bypass" mode (however, if the by-
pass button is again pushed or if a cancellation network 
command is received or if the bypass time expires, the 
Excel 12 will return to its scheduled occupancy mode). 

  If the wall module's LED flashes once per second, the 

bypass button or a network command has placed the 
Excel 12 into the "unoccupied" mode (however, if the by-
pass button is again pushed or if a cancellation network 
command is received, the Excel 12 will return to its 
scheduled occupancy mode). 

  If the wall module's LED flashes twice per second, a net-

work command has placed the Excel 12 into either the 
"standby" or the "occupied" mode. 

  If the wall module's LED flashes four times per second, 

the Excel 12 is responding to a network management 
"wink" command. 

 

Configuration of the LED to Display Info on Occupancy Mode 

The wall module's LED can also indicate the Excel 12's 
effective occupancy mode. Specifically: 

  If the wall module's LED is OFF, the Excel 12 is in the 

"unoccupied" mode. 

  If the wall module's LED is ON, the Excel 12 is in the 

"occupied" mode. 

  If the wall module's LED flashes once per second, the 

Excel 12 is in the "standby" mode. 

  If the wall module's LED flashes four times per second, 

the Excel 12 is responding to a network management 
"wink" command. 

 

Configuration of the T7560 Wall Module's LCD 

The T7560 Wall Module's LCD can be configured to display 
various symbols providing the following information: 

Содержание EXCEL 12 W7704B1002

Страница 1: ...nly 100 Vac power supply length 180 mm five relays incl three normally open relays and two changeover relays and six triac outputs four binary inputs six analog inputs plus AI6 which is suitable for reading input from LESST wall modules only two analog outputs 0 10 V one LED output W7704E1005 for Japan only 24 Vac power supply length 126 mm two relays both normally open and three triac outputs fou...

Страница 2: ...out tabs and snap by hand the covers available in packs of 8 into place onto the housing To remove a cover place a screwdriver in the leverage slot see Fig 9 on page 7 and pry it loose Terminal Assignment The terminal blocks are arranged on two sides of the controller the relay side and the low voltage side The relay side consists of a single row of terminal blocks for the connection of cables to ...

Страница 3: ...th Line Power Supply Models with line i e 100 Vac or 230 Vac power supply are equipped with a built in 24 Vac transformer the secondary side of which can be used to power external devices The max current at the field device supply terminals and all triac outputs together must not exceed 300 mA continuous NOTE Do not connect external 24 Vac on models with line power supply These models have a long ...

Страница 4: ...D When either a T7460 and T7560 Wall Module has been hardwired to the Excel 12 its LED can be configured using Honeywell s LNS plug in to provide information about e g overrides or effective occupancy modes Further in the case of a T7560 Wall Module its LCD can likewise be configured to display such information Configuration of the LED to Display Info on Overrides The wall module s LED can indicat...

Страница 5: ... The unit is connected to the LONWORKS network as shown in Fig 8 via terminal pins 3 and 4 black screw type T terminal plug underneath the terminal protection cover if present located on the low voltage side Terminal 24 and 25 are used to connect further devices to the LONWORKS network Excel 12 Excel 12 24V 22 24V 0 23 24V 1 24V 0 2 LON 1 3 LON 2 4 LON 1 24 LON 2 25 24V 22 24V 0 23 24V 1 24V 0 2 L...

Страница 6: ...mable electronic ballast s power supply the Excel 12 system ground must be earthed Triac Outputs The Excel 12 is equipped with up to six triac outputs Hardware Limits for Excel 12 with Line Power Supply Low signal 0 V high signal 24 Vac Maximum 250 mA continuous current in sum for all triac outputs together 550 mA for max 10 sec cos ϕ 0 5 Hardware Limits for Excel 12 with 24 Vac Power Supply Low s...

Страница 7: ...leverage slot LonWorks service button LonWorks service LED ventilation slits Fig 9 Housing top view Accessories Swivel Label Holders For short or long housings required for modules equipped with manual override switches Packs of eight 24 Vac models short order no XAL_LAB_S line power supply models long order no XAL_LAB_L Terminal Protection Covers For short or long housings required for wall ceili...

Страница 8: ...d custom node Application less firmware state exported 6c OFF duration is 1 15 sec depending on the application size and the system clock Afterwards the service LED begins flashing ON and OFF at 0 5 Hz First power up with a new PROM on a Neuron 3150 Chip based custom node Unconfigured firmware state exported 6d OFF duration is indefinite 1 15 sec to load internal EEPROM remains OFF First power up ...

Отзывы: