BALANCING EXCEL 10 VAV II
WITH E-VISION
NOTE: The standard commissioning and Flow table
download steps must be completed before
starting this task. See E-Vision User Guide,
Form 74-2588.
DOUBLE CLICK
E-VISION
SELECT A VAV II CONTROLLER
FROM THE NETWORK DIAGRAM
FROM THE CALIBRATION DIALOG BOX
CLICK THE "MAXIMUM" BUTTON
CLICK MENU ITEM "CONTROLLER"
AND THEN CLICK "CALIBRATE"
MAXIMUM
AIR
BALANCE
ENTER MEASURED FLOW IN CFM
AND THEN CLICK CALIBRATE
STABLE
FLOW
REACHED
?
NO
YES
START
A