EXCEL 10 FCU CONTROLLER LNS PLUG-INS USER GUIDE
63 EN2B-0285GE51
R0909
Table C4. Output Variables for Excel 10 FCU Controllers.
NV name
field name
engineering units:
English (metric) or states plus
range
digital
state
or
value
default comments
nvoUnitStatus heat_output_primary
SNVT_lev_percent
0 to 100%
163.835% = INVALID
This output variable reports the actual heating output value. Any
change forces nvoUnitStatus to be transmitted immediately.
nvoUnitStatus heat_output_
secondary
SNVT_lev_percent
0 to 100%
163.835% = INVALID
This output variable reports the reheat output value.
nvoUnitStatus cool_output
SNVT_lev_percent
0 to 100%
163.835% = INVALID
This output variable reports the actual cooling output value. A
change of more than 1% forces nvoUnitStatus to be transmitted
immediately.
nvoUnitStatus fan_output
SNVT_lev_percent
0 to 100%
This output variable reports the actual fan speed level.
nvoUnitStatus in_alarm
UBYTE
NO_ALARM
ALARM
ALARM_NOTIFY_DISABLED
0
1
255
This output variable reports the actual alarm status of the controller
and is set to ALARM_NOTIFY_DISABLE when nviManualMode =
SUPPRESS_ALARMS.
nvoWindow value
SNVT_switch.value
0 to 100%
0
(at application restart)
This output variable reports the status of the window sensor. It
allows the locally-wired window sensor to be used by other nodes
on the network.
nvoWindow state
SNVT_switch.state
CLOSED
OPEN
NO_WINDOW
0
1
255
NO_WINDOW
(at application restart)
See above.
nroPgmVer
id[0]
UBYTE, 70 = F
This output variable identifies the Excel 10 node type by an eight
byte constant describing the node type, major and minor functional
release number and bug fix. First character.
nroPgmVer
id[1]
UBYTE, 67 = C
Second character.
nroPgmVer
id[2]
UBYTE, 85 = U
Third character.
nroPgmVer
id[3]
UBYTE, 50 = 2
Fourth character.
nroPgmVer
major_ver
UBYTE, 0 to 255
Major Functional Release Number:
1. Add or delete a network variable (NV), nv field.
2. Change the name of a nv or nv field.
3. Range or type (short / long) of data in a nv field is changed.
4. Enumerated value list of a nv field is changed.
NOTE:
Algorithm changes or bug fixes may also be included.
nroPgmVer
minor_ver
UBYTE, 0 to 255
Minor Functional Release Number: