SENSITIVITY CONTROLS

ON Sensitivity   -   Sets sensitivity to movement when lights are switched on

This is the normal sensitivity adjustment expected on any detector.  Choose a setting as low as practical.  (ON Sensitivity set to maximum will result in lights staying on permanently.)

OFF Sensitivity   -   Sets sensitivity to movement when lights have switched off

This additional sensitivity adjustment is useful in storage aisles, open plan areas etc.  It enables a reduced sensitivity to be set for when an area is empty, so that fringe activity will not switch on the lights.
When fully clockwise, a very large movement is needed to switch on the lights whilst a much smaller movement (set by ON Sensitivity) will sustain them.  In enclosed rooms or corridors, this control may be left in the fully anti-clockwise position 
when the sensitivity will remain the same whether the lights are ON or OFF.  The change takes  5 seconds after the lights have switched off to establish fully.

COMMISSIONING 

Ensure that any heating / ventilation plant which may cause interference is switched ON.  Set the PHOTOCELL control fully clockwise, 
sensitivity controls fully anti-clockwise and the four switches to OFF then follow these simple commissioning instructions. We recommend 
that the Off Sensitivity is not adjusted unless absolutely necessary and therefore the commissioning procedure is started from Step 2.

O

N

O

F

F

4.  OFF DELAY AND POWER-UP CONDITION

Sets the time delay following the last observed movement after which the 
lights switch OFF.

With 3 and 4 in the OFF position, the delay time is 5 seconds which must only be 
used for setting up purposes.  In semi-automatic mode the lights are switched ON 
by switching the wall-switch OFF then ON.
NOTE:   In semi-automatic mode, Power-up ON must be selected,   i.e. Switch 1 
must be ON.

3.  PHOTOCELL 

Prevents lights being switched ON when there is adequate daylight.  

Commission  for  movement  before  adjusting  the  photocell.  Anti-clockwise 
adjustment makes the photocell more active so that lights will be held OFF until it is 
darker.   A mid setting is generally suitable.   The photocell may be overridden by 
switching the normal light switch OFF then ON.  The lights will come ON if Power-up 
ON is selected, i.e. Switch 1 is ON.

2.  ON SENSITIVITY
Sets the sensitivity to movement when the lights are ON.  

Rotate the control clockwise so that the LED flashes in response to typical 
movements expected at the extremities of the monitored area.  Wait to ensure 
that the lights switch off and that no interference signals are triggering the 
detector.  
DO NOT TURN TO MAXIMUM.  Always adjust to the lowest setting consistent 
with reliable performance.

1.  OFF SENSITIVITY
Reduces the sensitivity to movement when the lights are switched OFF.

When set fully anti-clockwise, the sensitivity is the same with the lights switched 
ON and OFF. 
Wait outside the area for the lights to switch OFF.  Re-enter the area and check 
the point at which the lighting switches on again.  Increase the setting until the 
lights are switched on JUST AT THE POINT OF ENTRY.

LED

Coarse Sensitivity Adjustment

Normal setting is anti-clockwise. Turn clockwise to reduce 
overall sensitivity (required only in special circumstances).

1 Power-up ON Power-up OFF
2 Semi-auto

Auto

3 5 min delay

Zero delay

Add switches together

4 10 min delay

Zero delay

to select 15 minutes

ON

OFF

INSTALLATION

The Standard Range LightSpot is a sensitive, ultrasonic movement detector; it is essential therefore that it be installed 
on a rigid surface that will not itself be subject to movement or vibration.   

Fix directly to a rigid surface or use the semi-flush fixing kit to recess into a ceiling tile etc.  (For semi-flush fixing, use a 
hole saw to drill a 76mm hole into the ceiling tile.)   Existing light switch can be retained.  Use switch wire from switch as 
LIVE IN.  A spare connection has been provided for earth termination.

WHEN INSTALLING, REMEMBER

LightSpot is not for use outdoors.

Range is 10-15 metres for a walking target in a corridor and 5-8 metres for small hand-movements.

Best performance is achieved at a mounting height of 2-3 metres - in a corner - pointing into the room (max size 6.0m 

x 6.0m) or one end of a corridor.

The detector is more sensitive to movement ALONG the beam than ACROSS it.

The detector can see behind itself, so it should be positioned a metre or more inside the monitored area - particularly 

in the case of racking aisles and corridors.

Ultrasonic detectors are sensitive to all moving objects including air movement.   A mounting location should be 

chosen thoughtfully, particularly where there are fans in the area, e.g. extract fans and computer cooling fans. 

The detector should not be positioned within 25cm of a luminaire.

TECHNICAL/WIRING DETAILS

Switching capacity 10 Amps.  Incandescent lamps: 1500W max.  For use on 230V ac supplies only.

Terminal Capacity
1 x 2.5mm
or  2 x 1.5mm

N

N

L

E

E

MS1500

L

OUT

LOAD

L

IN

Important Additional Notes

1.

A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.

2.    This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of some 

lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life.  
Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect. 

Содержание Ex-Or MS1500P

Страница 1: ...Standard Series LightSpot MS1500P MS1500PF MS1500PF MS1500P Installation and Commissioning Instructions by Honeywell ...

Страница 2: ...use outdoors Range is 10 15 metres for a walking target in a corridor and 5 8 metres for small hand movements Best performance is achieved at a mounting height of 2 3 metres in a corner pointing into the room max size 6 0m x 6 0m or one end of a corridor The detector is more sensitive to movementALONG the beam thanACROSS it The detector can see behind itself so it should be positioned a metre or m...

Страница 3: ...orporated in the fixed wiring in accordance with the current wiring regulations 2 This equipment switches lights no more frequently than would a responsible human occupant However manufacturers of some lighting types e g 2D luminaires may specify a maximum number of switching cycles in order to achieve a predicted lamp life Please check with the manufacturer of the luminaires to ensure that they a...

Страница 4: ...seconds which must only be used for setting up purposes In semi automatic mode the lights are switched ON by switching the wall switch OFF then ON NOTE In semi automatic mode Power up ON must be selected i e Switch 1 must be ON 3 PHOTOCELL Prevents lights being switched ON when there is adequate daylight Commission for movement before adjusting the photocell Anti clockwise adjustment makes the pho...

Страница 5: ...0W max at 230V TERMINAL CAPACITY 2 x 1 5mm or 1 x 2 5mm WEIGHT 148g TIME DELAY 5 10 or 15 mins POWER UP CONDITION select ON or OFF DETECTOR RANGE adjustable see installation notes RANGE REDUCTION adjustable see installation notes ULTRASONIC FREQUENCY 40kHz PHOTOCELL adjustable 50 to 5000 lux SEMI FLUSH FIXING requires 76mm hole to be drilled in ceiling tile Ex Or Novar ED S Limited Haydock Lane Ha...

Отзывы: