background image

 Standard Series LightSpot

MS1500P & MS1500PF

MS1500PF 

MS1500P 

Installation and Commissioning

Instructions

W4006K

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Technical Data

 

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 5 metres
SWITCH CAPACITY: 10 Amps

Incandescent lamps: 1500W max (at 230V) 

TERMINAL CAPACITY: 2 x 1.5mm or 1 x 2.5mm 
WEIGHT: 148g
TIME DELAY: 5, 10 or 15 mins
POWER-UP CONDITION: select ON or OFF
DETECTOR RANGE: adjustable - see installation notes
RANGE REDUCTION: adjustable - see installation notes
ULTRASONIC FREQUENCY: 40kHz
PHOTOCELL: adjustable 50 to 5000 lux
SEMI-FLUSH FIXING: requires 76mm hole to be drilled in ceiling tile

Ex-Or 

Novar ED&S Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ

Tel: +44 (0)1942 719229 
Fax: +44 (0)1942 508753  
Email: [email protected]
www.ex-or.com

by Honeywell

Содержание Ex-Or MS1500P

Страница 1: ...Standard Series LightSpot MS1500P MS1500PF MS1500PF MS1500P Installation and Commissioning Instructions by Honeywell ...

Страница 2: ...use outdoors Range is 10 15 metres for a walking target in a corridor and 5 8 metres for small hand movements Best performance is achieved at a mounting height of 2 3 metres in a corner pointing into the room max size 6 0m x 6 0m or one end of a corridor The detector is more sensitive to movementALONG the beam thanACROSS it The detector can see behind itself so it should be positioned a metre or m...

Страница 3: ...orporated in the fixed wiring in accordance with the current wiring regulations 2 This equipment switches lights no more frequently than would a responsible human occupant However manufacturers of some lighting types e g 2D luminaires may specify a maximum number of switching cycles in order to achieve a predicted lamp life Please check with the manufacturer of the luminaires to ensure that they a...

Страница 4: ...seconds which must only be used for setting up purposes In semi automatic mode the lights are switched ON by switching the wall switch OFF then ON NOTE In semi automatic mode Power up ON must be selected i e Switch 1 must be ON 3 PHOTOCELL Prevents lights being switched ON when there is adequate daylight Commission for movement before adjusting the photocell Anti clockwise adjustment makes the pho...

Страница 5: ...0W max at 230V TERMINAL CAPACITY 2 x 1 5mm or 1 x 2 5mm WEIGHT 148g TIME DELAY 5 10 or 15 mins POWER UP CONDITION select ON or OFF DETECTOR RANGE adjustable see installation notes RANGE REDUCTION adjustable see installation notes ULTRASONIC FREQUENCY 40kHz PHOTOCELL adjustable 50 to 5000 lux SEMI FLUSH FIXING requires 76mm hole to be drilled in ceiling tile Ex Or Novar ED S Limited Haydock Lane Ha...

Отзывы: