Commissioning

The factory default settings will be appropriate for most applications. However, the installer does have the facility to re-

programme a wide range of parameters using an infrared programming tool.  The full range of parameters is accessible via 

the HP2000; the HP18 offers different/limited programming options. Please read carefully the operating instructions that 

accompany the programmer prior to performing a programming operation.
Below is a table showing the pre-set factory settings and a brief explanation of each parameter.  These parameters may be 

re-programmed any number of times and all settings will be retained in the event of a power loss.

Parameter

Options

Pre-set

Notes

Power up

on/off

on

Sets the luminaire state at power up irrespective of occupancy.  Useful in 

reducing start-up load following power cut.  Power-Up off - responds to 
occupancy after 30 seconds.

Response

auto/semi-auto

auto

If set to auto, the presence detector switches the luminaire on and off 

automatically. If set to semi-auto, the luminaire will not turn on automatically 
when a person enters the area.  It can be turned on using the hand-held 

controller or by toggling the power switch.  When the area is vacated, the light 

will turn off automatically.

Off delay 

1 min-96 hrs / disabled 20 mins

The time for which the luminaire will stay on following the last detected 

5,10 or 20 mins (HP18)

movement.  Also 10-second setting for walk-testing.

24hr Cycle

on/off

off

For use in ‘Washroom mode’ only - not applicable to this detector.

Photocell Mode passive/active/

disabled The operation of the built-in photocell is governed by the setting chosen and 

disabled

 by values stored in the Upper and Lower thresholds (see diagram overleaf).

Passive

 - The photocell will inhibit turn-on of the controlled load if sufficient 

natural light is available. It will not turn the load off whilst an area is occupied.

Active

 - The photocell will turn the controlled load on and off as required 

whilst natural light levels fluctuate during a period of occupancy. This mode of 

operation operates in conjunction with a passing cloud timer (PCT). The PCT 

is asymmetrical in operation - the load will be switched on immediately that 
the light level falls below the lower set point, however, the load switches off 
only if the light level exceeds the upper threshold 

continuously 

 for a period 

equal to the Off Delay.

Disabled

 - The photocell has no effect.

Lower Threshold 0-254

254

Point at which photocell allows lights to switch on.

Upper threshold 0-254

254

Point where photocell turns lights off if Photocell is in Active mode.

Important Additional Notes

1. Only suitably qualified personnel should install this equipment. 
3. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
3. This equipment switches lights no more frequently than would a responsible human occupant.  However, manufacturers of 

some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles and/or a minimum on-time in 

order to achieve a predicted lamp life.   Please check with the manufacturer of the luminaires to ensure that they are 

compatible with automatic controls in this respect. 

Lens Mask

A lens mask (MBPIRLM) is available to mask end-of-aisle movement from being detected.

Walk-test Mode

Walk-test mode is used to check that the detector is operating as required.  The short off-delay enables the installer to 

check that lights are switching on when movements are made at the edge of the detection zone.  It is easier to carry out a 

walk-test when the photocell is not holding the lights off.
1.   Change the Off Delay to 10 seconds with the HP2000 by pressing ‘Utilities/Walk Test/OK’ or press ‘TEST’ on HP18.
2.   Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before moving 

and triggering the lights back on. 

W5100A

Содержание Ex-Or MS1200PMBF

Страница 1: ...42 719229 Fax 44 0 1942 508753 Email technicalsales ex or honeywell com www ex or com At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with normal household waste Do not burn Note HP2000 or HP18 required for commissioning Please note that the HP18 offers different limited programming options ...

Страница 2: ...th a minimum clearance of 125mm between the front surface of the tile and the hard ceiling behind The detector should be mounted in the centre of the group of luminaires to be controlled Cut a 50mm diameter 64mm if using an FR64 flush ring or PB64 plasterboard fixing kit circular hole in the tile feed the flying lead and detector through the hole and secure into position with the locking ring Twis...

Страница 3: ...urn the load off whilst an area is occupied Active The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the light level falls below the lower set point howeve...

Страница 4: ...he thresholds may be read back and fine tuned if necessary using the HP2000 Please note that the values are non specific units i e not lux Note The light level perceived by the detector at the moment immediately prior to a Download operation is shown momentarily on the HP2000 screen following the Download this is a useful mechanism for troubleshooting Lights ON Lights OFF Upper Threshold Lower Thr...

Отзывы: