4
Commissioning
The units are supplied with the factory default settings shown below which render commissioning
unnecessary in many applications. To make use of the programmable settings, an infrared commissioning
tool is required (QuickSet Pro). A ten-second time delay is selectable to aid commissioning.
Sensitivity to Movement
While the factory settings will be correct for many applications, the sensitivity can be adjusted if required.
ON Sensitivity:
This sets the detector’s range when the lights are ON. Choose setting from 1-100 where 1 is
lowest and 100 is maximum. (Note: Choose the lowest level possible to give adequate detection.)
OFF Sensitivity:
This sets the detector’s range when the lights are OFF. Choose % setting from 10% to
100% where 10% = 10% of ON Sensitivity and 100% = same as ON Sensitivity. This is an approximation and
should be tested on site during commissioning.
Like all programmable parameters, the sensitivity settings will be retained in the event of a power failure and
can be re-programmed any number of times.
Factory Default Settings
These are the settings to which the units have been programmed before they leave the factory.
Parameter
Power Up
Response
Off Delay
On Sensitivity
Off Sensitivity
Pcell Rly
Set-Point Low
Set-Point High
Default
Setting
ON
AUTO
20 mins
20
100%
Disabled
409
512
Options
On/Off
Auto, Semi Auto
1min-96hrs, 10 secs (walk test), Disabled
0-100
100-10% in 10% increments
Disabled/Passive/Active
0-1023
0-1023
Options
Each of these settings
can be re-programmed,
if desired, by use of the
QuickSet Pro infrared
programming tool.