MLSUC500 / 1250 Installation Guide 32340084-001 Rev A, 24-Aug-2018. MU1B-0638GE51 R0718A 1

Installation Guide

MLSUC500 / 1250

 

Important: Retain these instructions

by Honeywell

These instructions shall be used by trained service 

personnel only. 

If the equipment is used in a manner not 

specified by these instructions, the protection provided by the 

equipment may be impaired.

1

Dimensions & Clearances 

(including optional expansion modules)

3 INSTALLATION

BOX CONTENTS

2 STORING

CONTENTS

Box Contents .................................................................1

2 Storing ...........................................................................1

3 Installation .....................................................................1

MLSUC500 / 1250 

Installation 

Instructions - Mounting 

(32340084-001)

and enclosure 

mounting instructions.

Field Maintenance .........................................................4

5 Disposal .........................................................................4

H O

2

+85°C

-40°C

95%RH

185 mm (7.25”)

30

0 m

m (

11

.7

5”

)

Allow

Cover clearance

Unit with door open

It is recommended that the installation should comply 

with the local electrical safety installation practices (e.g. 

HSE Memorandum of Guidance on Electricity at Work 

Regulations 1989, USA National Electric Code).

ATTENTION: 

Observe precautions for handling 

electrostatic sensitive devices.

!

WARNING: 

Contains no serviceable parts. Do not 

attempt to open the unit. Failure to comply may 

cause damage to the unit.

335 mm (13.25”)

300 mm (11.75”)

Enclosure

MLS spine terminals

MLSJ8

MLS PSU

MLS circuit breaker

MLS power terminals

Содержание Ex-Or MLSUC500

Страница 1: ...500 1250 Installation Instructions Mounting 32340084 001 and enclosure mounting instructions 4 Field Maintenance 4 5 Disposal 4 H O 2 85 C 5 40 C 95 RH 185 mm 7 25 300 mm 11 75 Allow Cover clearance Unit with door open It is recommended that the installation should comply with the local electrical safety installation practices e g HSE Memorandum of Guidance on Electricity at Work Regulations 1989 ...

Страница 2: ...ocation subject to electrical noise H O 2 60 C 5 20 C 95 RH The entry for the power wiring can be made by drilling a conduit of around 20mm at the bottom or either side of the enclosure The power wiring must be terminated at the MLS power terminals and circuit breaker and terminal blocks The MCB and the terminal blocks are prewired to the MLSJ8 PSU in the factory Note the MLS circuit breaker and M...

Страница 3: ...In that event disconnect it from the network segment and power cycle the MLSUC500 1250 32 devices RS 485 The MLSUC500 1250 assumes the role of Bus Master on the MLS Spine This means that all the RB2000s should be given consecutive unique non zero addresses refer to RB2000 documents The last unit at each end of the MLS spine should be configured to terminate the two RS485 signal pairs A B and Y Z I...

Страница 4: ...ycling centre Do not dispose of with normal household waste Do not burn 5 FIELD MAINTENANCE MLSUC500 1250 requires no routine maintenance WARNING Contains no serviceable parts Do not attempt to open the unit Failure to comply may cause damage to the unit 3 INSTALLATION continued MLSUC500 1250 Configuration Manual W6003 The following information will be useful RB2000 locations Zones and their respe...

Отзывы: