W4388E

level press and hold ‘OK’ to store. The luminaire(s) will blink to acknowledge a successful store 

operation.
Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements 

made with a lux meter on the working plane to remain constant when daylight illuminates the ceiling 

and the working plane to a differing extent. Therefore, products of this type should be regarded as 

capable of maintaining an APPROXIMATE light level only.

Setting the Switching Photocell

 

Now the desired switching light level must be arrived at either by waiting for an appropriate time of 

day or by a combination of manually switching off lights and perhaps masking windows. Using the 

HP2000 Programmer, enter the Utilities menu and select  'User Remote'. Scroll down to 'Scene 1' 

and press and hold the 'OK' button to store. The luminaire(s) will blink to acknowledge a successful 

store operation

Testing

Detectors can be put into a temporary 10 second Off-delay mode to check their sensitivity and 

range settings using the HP2000 Utilities menu WalkTest option This mode expires automatically 

after a few minutes.

Part Numbers

MLS2500CDR       Corner-Mount Microwave Presence Detector with Photocell, Semi-Flush Mount

MLS2500CDRSM   Corner-Mount Microwave Presence Detector with Photocell, Surface Mount

WMK

Wall Mounting Kit

BT5E030GY

3m Detector Patch Lead

BT5E050GY

5m Detector Patch Lead

BT5E100GY

10m Detector Patch Lead

Technical Data

 

MAX RECOMMENDED MOUNTING HEIGHT: 3.5m.

RANGE: Adjustable up to 20m.

OPERATING VOLTAGE: 12V DC, SELV if installed correctly.

PHOTOCELL  Regulating.

DEPTH REQUIRED BEHIND CEILING (SEMI-FLUSH VERSION)

 40mm plus an allowance for the minimum bend radius of the patch lead.

WEIGHT:  130g approx. 

COLOUR: White.

MATERIAL: Flame retardant PC/ABS

IP RATING: 4X

Содержание Ex-Or MLS2500CDR

Страница 1: ... MLS2500CDRSM MLS2500CDR MLS2500CDR and MLS2500CDRSM Mid range Directional Microwave Detectors with Photocell for use with CDW12U5 CDH4U5 CDH8U5 Programmable Intelligent Lighting Control Modules HC5 or HP2000 required for Photocell Commissioning ...

Страница 2: ...ng half of the flush ring by loosening the locking screw so that about 3mm of thread is visible and twisting the detector anticlockwise Align the mounting screw holes of the above ceiling half of the flush ring with those of the backbox and position both above the hole in the ceiling tile Now offer the below ceiling half of the flush ring to the underside of the ceiling tile and align the mounting...

Страница 3: ...arts Inside DO NOT OPEN Power consumption 10W I I I I I ta 0 40 C To CD Box Do Not Connect Socket for patch lead to LCM View on Back of MLS2500CDR Detector Bayonet Tab Receptacles Arrow Symbol Locking Screw Commissioning In the CDW12U5 and CDH4U5 CDH8U5 systems all configuration information is held within the LCMs themselves not in individual detectors Most of the configuration items are set up wi...

Страница 4: ...bination of manually switching off lights and perhaps masking windows Using the HP2000 Programmer enter the Utilities menu and select User Remote Scroll down to Scene 1 and press and hold the OK button to store The luminaire s will blink to acknowledge a successful store operation Testing Detectors can be put into a temporary 10 second Off delay mode to check their sensitivity and range settings u...

Отзывы: