Commissioning Detectors using the HP2000

It is important that the HP2000 be held perpendicular and at a distance of between 0.5m and 2m from the detector.   
1. Switch on HP2000 by pressing the red power button.
2.   Point HP2000 at detector and press the DOWNLOAD button.  The HP2000 will confirm the product’s identity, 

and call up the correct menu of parameters and their current settings. It will also show the ballast type and the  

duration (shown in hours) remaining on the 100-hour burn-in.

3. Use a combination of UP, DOWN, FORWARD and BACK buttons to navigate the parameter menu, selecting 

options for each shown. (See Tips below.) 

4. When options for all parameters have been selected, point the HP2000 at the detector and press the UPLOAD 

button.  The luminaire(s) will switch off briefly during the programming process and the HP2000 shows DATA 

OK to confirm operation.

5. After a short period of inactivity (default 5 minutes), the HP2000 hibernates retaining the most recent settings.

Tips

i)  Where there are only two options such as ON/OFF, a double click of the OK button toggles between them. 
ii)   Where there are multiple options, a double click of the OK button recalls a list of all options for that parameter.  

Use the UP, DOWN and OK buttons to select.

iii)  Use the OK button to go forward (through the menus) without displaying help pages.
iv)   Press UPLOAD at any time to transfer all current settings from the handset to the product.

Please refer to HP2000 instructions for comprehensive commissioning details.

Factory Default Settings

These are the settings to which the units have been programmed before they leave the factory:

W4087G

Parameter

Options

Default

Power Up

On / Off

On

Response

Auto, Manual/Bus, Manual

Auto 

Off Delay

1 min - 96 hrs, 10-sec (walk-test), Disabled

20 mins

On Sensitivity

0-100

100

Bus Connect

Yes / No

Yes

Zones 1-4

Address 1-100

-- (no zone)

Corridor 1-2: Begin

1-100 Building Address Span

-- (no zone)

Corridor 1-2: End

1-100 Building Address Span

-- (no zone)

Global 1-2 Rx

Yes / No

No

Start Lamps

Max / Min

Max

Entry Scene

1-6

1

Bright Out

Yes / No

No

Dimming

Reg 50%-Reg100%

Reg 100%

Lamp Max

10%-100%

100%

Fade to Off

Yes / No

No

When Vacant

10 Exit Scenes

Off

Set-Point High

0-1023

1023

Set-Point Low

0-1023

1023

100 Hour Burn-In

See Application Note: AN4028

0 hr

Additional feature accessible under Utilities:

Содержание Ex-Or MLS

Страница 1: ...d Commissioning Instructions Note HP2000 required for commissioning HC5 or HC6 required for testing MLS Digital Luminaire Controllers MLS2000DIS MLS2000DIW for DSI ballasts MLS2000DALIS MLS2000DALIW for DALI ballasts ...

Страница 2: ...mps please ensure that the detector is at the cold end of the lamps In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires that ...

Страница 3: ...the OK button toggles between them ii Where there are multiple options a double click of the OK button recalls a list of all options for that parameter Use the UP DOWN and OK buttons to select iii Use the OK button to go forward through the menus without displaying help pages iv Press UPLOAD at any time to transfer all current settings from the handset to the product Please refer to HP2000 instruc...

Страница 4: ...rs 4 This equipment should be used to control only those ballasts powered from the same phase as the detector 5 Do not connect mains to the MLS bus 2 6 It is imperative that the MLS bus is wired with the correct type of cable normally it should be 1 5mm unscreened twisted pair Please readApplication NoteAN4001 for more details 7 Due to the fact that the photocell is on the ceiling looking down it ...

Отзывы: