DIMMING CHANNELS

MAINS  INPUT

N

L

1

3

L

E

N

Introduction

The  CDH8U5  is  an  intelligent  LCM  providing  connections  for  multiple 
luminaires*, up to 5 presence detectors and up to 10 SELV inputs.  Provision 
is made for 7 switched live outputs plus one volt-free power output. The unit 
features    a  switched  output  for  Maintained  Live  to  allow  initiation  of 
Emergency Lighting Test.   In addition, the unit is provided with a volt-free 
signalling output to provide control of / interface to other equipment.   The 
CDH8U5  is  designed  to  simplify  installation  whilst  providing  an  intelligent 
managed lighting system. 

Please  note  that  during  the  installation  after  the  unit  is  power  up  and  no 
detector has been connected (or commissioning has not been done), lights 
will be on for 20min and will turn themselves off. Please also note that when 
using a MLS2000SSPmk2 with the MLS Network and connecting the lights 
directly to the plate instead of to the LCM the command from the RB2000 will 
be ignored as it does not get through the CD box. 

 

*Note: Refer to the Technical Data section for the maximum allowable number 
of luminaires.   

Fixing 

The CDH8U5 should be mounted in an enclosure with a DIN-rail.

Consideration  should  be  given  to  access  for  installation  and  maintenance 
when selecting the enclosure and location. The external enclosure DIN-rail 
should comply with EN 60715. 

Electrical Connections

The connections to this equipment should be made only by a suitably 
qualified person and in accordance with the current wiring regulations.  
A  means  of  disconnection  must  be  incorporated  in  the  fixed  mains 
wiring to this box in accordance with the current wiring regulations.  

All the connections should be routed ensuring adequate strain relief on the 
cable before termination to the unit’s pluggable connectors.  

CAUTION: DO NOT CONNECT MAINS TO THE MLS BUS OR DIMMING
OUTPUTS.

Connecting the Luminaires

Variants  of  the  CDH8U5  are  provided  to  control  DSI 

(available  on 

configuration only),

 DALI and 1-10V ballasts.  (See Part Numbers section for 

more details.) 

Note: Dimming Ballast types CANNOT BE MIXED on a single CDH8U5.

The  CDH8U5  is  equipped  with  8  two-wire 

pluggable  terminals  for 

(Blue)

 

dimming outputs and 4 two-wire 

pluggable terminals are provided for 

(Black)

 

switched live outputs.  Switched Live Outputs 1 through 6 are grouped in pairs 
on  a  single  plug  to  add  mechanical  strength  for  plugging/unplugging. 
Switched Live Output 7 has two terminals for connecting the load.

Note: Earth and Neutral are connected directly to the luminaire and not 
routed through the CDH8U5.

(Black) 

(Blue) 

Note: + and - relevant for 
analogue versions only.

Ballast

Ballast

N

N

L

L

E

E

D

D

D

D

L

E

E

N

N

Loads on Channel 1

Dimming

Dimming

Note: some connectors omitted for clarity

As shown above, one or more luminaires may be connected to each channel 
of the CDH8U5. 

Note: For the maximum number of allowable ballasts, refer to Technical 
Data section.  

Connecting Switched Live Output

The  CDH8U5  has  7  switched  live  outputs.   As  shown  in  the  diagram,  the 
Neutral and Earth connections should be taken directly to the load.  

Each Switched Live output is rated for a load of up to 6A, with a total maximum 
switched live load not exceeding 16A for the unit.  

Output 8 is provided as a volt-free style for extra flexibility.

Connecting Volt Free and Maintained Live Output

The CDH8U5 provides a 5-way terminal block for connecting mains rated Volt 
Free load and Maintained Live output.     For wiring convenience, the middle 
terminal  of  the  5-way  block  is  internally  linked  to  the  Mains  Live  input  as 
shown. 

L

E

E

N

N

Ballast

N

L

E

Note: some connectors omitted for clarity

Switched Live

Internal Link

Maintained 
Output

External shorting Links

Содержание Ex-Or CDH8U5

Страница 1: ...CDH8U5 8 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions Product option shown here for illustrative purposes only ...

Страница 2: ... cable before termination to the unit s pluggable connectors CAUTION DO NOT CONNECT MAINS TO THE MLS BUS OR DIMMING OUTPUTS Connecting the Luminaires Variants of the CDH8U5 are provided to control DSI available on configuration only DALI and 1 10V ballasts See Part Numbers section for more details Note Dimming Ballast types CANNOT BE MIXED on a single CDH8U5 The CDH8U5 is equipped with 8 two wire ...

Страница 3: ...lso be compromised Connecting Switches The CDH8U5 is equipped with SELV switch inputs which will typically be two way centre off momentary rockers e g the MK K4900 range The logical function of a switch can be configured from a wide range of options and its action can be associated with any combination of channels The switch connection consists of a 3 pole pluggable terminal block comprising a com...

Страница 4: ...trol Module provides a gateway to the wider MLS system but connecting directly to a CDW12U5 CDH4U5 or CDH8U5 LCM also allows use in non MLS applications Easy touch screen control of AV and lighting User interface panels or touch screens from the Ex Or Scene Select II range can also be used Connecting to the MLS Digital Network It is imperative that the MLS Bus be wired in the correct type of cable...

Страница 5: ...rmines different actions when the area is vacant dependent on time of day Background Tmr 10 seconds to 96 hours or none Applies to Alt Exit Scenes and some Background Level scenes i e not XTN and BLD options When Background Timer expires channel s output turns off Fade to Off Yes No Bus Connect Yes No Zones 1 4 None Zone number 1 100 Common 1 2 3 Zones 1 4 TRX Tx Rx Tx Only Rx Only Determines how ...

Страница 6: ...splays the CDH 8 Channels V2 screen 4 Scroll down to Ballast and press OK This displays a sub menu with multiple operations 5 Scroll down to DSI 1 and press OK The selected operation is applied 6 Use the RightArrow Key to navigate across all the channels and repeat steps 4 to 5 to edit the Ballast to DSI 1 operation for each channel 7 Stand directly below the unit and press Upload wait for about 5...

Страница 7: ...mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable Two core multi stranded twisted pair Cross sectional area 1 5mm unscreened 600 1000V rated LSOH insulated see Application Note AN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IP rating 20 Dimensions Enclosure An enclosure K5612S MET is available for this product It provides integra...

Страница 8: ...Module Plasterboard Fixing Kit MLS2001CDR 360 PIR detector Obsolete no longer made Detector Patch Leads BT5E030GY 3m Patch Lead BT5E050GY 5m Patch Lead BT5E100GY 10m Patch Lead Connectors CDHHDIP 10 way Plug green SELV switch input 1 piece CDHDOP 2 way Plug blue dimming outputs 2 pieces CDHSLOP 2 way Plug black switched live outputs 2 pieces CDHIP 3 way Plug green SELV switch inputs and auxiliary ...

Отзывы: