Connecting Presence Detectors

The following SELV detectors are designed to interface to the CDH4U5:

MLS2500CDR

Corner-mount Microwave presence detector with photocell, semi-flush mounted.  Available with surface mount (SM suffix).

MLS2401CDR

360° Microwave presence detector with photocell, flush mounted.  Available in surface mount version (SM suffix).

MLS2001CDR

360° PIR presence detector with photocell, flush mounted.  Available in surface mount version (SM suffix). 

MLSM2002CDR Controller for a 360° PIR detector with photocell.  Used with the DHS OR DHW mini-head to form an integral luminaire-mounted unit.  
Each connects to the CDH4U5 by means of an Ethernet-style RJ45 connector terminated patch lead which are available ready-made in 3m, 5m and 10m 

lengths.  Up to five detectors may be connected to a CDH4U5. 

Positioning Presence Detectors

For information on installing and positioning detectors, please refer to the installation instructions provided with the particular detector. 

Connecting Switches 

The CDH4U5 is equipped with  SELV switch inputs which will typically be two way, centre off, momentary rockers, (e.g. the MK K4900 range). The logical 

function of a switch can be configured from a wide range of options and its action can be associated with any combination of channels.  The switch connection 

consists of a 3-pole pluggable terminal block comprising a common and two returns from normally open contacts. Four plugs are provided with each CDH4U5, 

additional plugs can be ordered using the code CDHIP (5 pieces per pack).

.

 Note that if the SELV status of any one of the switches 

is compromised by reason of inadequate insulation or 

segregation of the cabling, then the SELV status of all 

other switches AND OF THE DETECTORS will also be 

compromised. 

B Com A

The recommended cable for use with the SELV switches is 3-core 300/500v 0.75mm

 cable to CMA Reference 3183Y or for LS0H, to CMA Reference 3183B.  

The maximum allowable cable length between the switch mechanism and the CDH4U5 terminal block is 100m. 

Three separate single wires should not be used.

Connecting the Communications Bus (MLS) 

2

It is imperative that the MLS Bus be wired in the correct type of cable.  Normally it should be 1.5mm  unscreened twisted pair.  See Application Note AN4001. 

Do not connect Mains to the MLS Bus.

For connection of Bus Power Supply variants, see also Supplementary Installation Instructions W5071.

-5-

VOLT FREE CHANNELS

1  -  1       2  -  2

COMMS BUS

+   4   -

+   3   -

+   2   -

+   1   -

DIMMING CHANNELS

N

L

MAINS INPUT

VOLT FREE CHANNELS

N2   L2

N1   L1

CH2

ML

CH3

CH1

CH4

D

D

The recommended cable for use with the SELV switches is 3-core 300/500v 0.75mm

cable to CMA Reference 3183Y or for LS0H, to CMA Reference 3183B.

The maximum allowable cable length between the switch mechanism and the CDH4U5 terminal block is 100m.

Three separate single wires should not be used.

Connecting the Communications Bus (MLS)

2

It is imperative that the MLS Bus be wired in the correct type of cable. Normally it should be 1.5mm unscreened twisted pair. See Application Note AN4001.

Do not connect Mains to the MLS Bus.

For connection of Bus Power Supply variants, see also Supplementary Installation Instructions W5071.

In

In

Out

Out

MLS Bus 1

MLS Bus 2

Содержание Ex-Or CDH4U5

Страница 1: ...CDH4U5 4 Channel Programmable Intelligent Lighting Control Module Installation and Commissioning Instructions ...

Страница 2: ...uct simplifies installation whilst providing an intelligent lighting control system Provision is made for 4 volt free power outputs rated for 415V isolation Additionally the unit features a switched output for Maintained Live to allow initiation of Emergency Lighting Test The CDH4U5 has the ability to operate from dual supplies with the capability to modify its operating behaviour when failure is ...

Страница 3: ...wn in the diagram one or more channels may be powered from either of the supplies Ballast N L E D D Ballast N L E D D Ballast Ballast Ballast N N N L L L E E E D D D D D D 1 DETECTOR PORTS 2 3 4 5 B COM A B COM A B COM A B COM A B COM A 1 2 3 4 5 SELV SWITCH INPUTS VOLT FREE CHANNELS 1 1 2 2 COMMS BUS 4 3 2 1 DIMMING CHANNELS N L MAINS INPUT VOLT FREE CHANNELS N2 L2 N1 L1 CH2 ML CH3 CH1 CH4 D D CH...

Страница 4: ... the unit an external change over contactor is required Line terminals from each of the supplies N1 L1 and N2 L2 are connected via the change over contactor The Live and Neutral outputs from the contactor are connected to the mains input of the unit In the case of failure of one of the supplies the change over contactor switches to the alternative supply to ensure continuous supply to the unit As ...

Страница 5: ...k comprising a common and two returns from normally open contacts Four plugs are provided with each CDH4U5 additional plugs can be ordered using the code CDHIP 5 pieces per pack Note that if the SELV status of any one of the switches is compromised by reason of inadequate insulation or segregation of the cabling then the SELV status of all other switchesAND OF THE DETECTORS will also be compromise...

Страница 6: ...ns 6 PARAMETERS OPTIONS Per Box Parameters Switch A 1 5 Switch B 1 5 Switch 6A 6B 7A 7B User may choose any option for Switch A or Switch B from following Sustain Brighten Dim Off Scene 01 06 On Partition OneSwitch On Dim Off Brighten On Brighten Off Dim Emergency Test Emergency End See separate table for detailed description of Switch Input options Detector 1 5 Range Max 100 Max 75 Max 50 High 10...

Страница 7: ...r example 20 Ballasts Maintained live output 6A Mains supply terminal capacity 2x2 5mm or 1x4mm Override switch input connector 2 5mm MLS bus connector 2 5mm MLS bus cable 1 5mm unscreened twisted pair seeApplication NoteAN4001 Case material Self extinguishing blend PC ABS Case finish Gray RAL7035 IPrating 20 Dimensions 9 m 1m 62mm 3m 21 m Volt free Channels Volt free Channels Dimming Channels Com...

Страница 8: ... Power Supply Unit Wireless switch enabled DSI Dimming CDH4U5 RBDALIWL 4 Channel LCM with MLS Bus Power Supply Unit Wireless switch enabled DALI Dimming Plug in Cards CDHDC Plug in Digital Dimming Card CDHAC Plug in Analogue Dimming Card CDHBC Plug in MLS Bus Interface CDHRB Plug in MLS Bus Power Supply Unit CDHWL Plug in Wireless EnOcean Card Presence Detectors with photocell MLS2500CDR Corner mo...

Отзывы: