UV100E ULTRAVIOLET AIR TREATMENT SYSTEM

3

68-0249-1

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous 
condition.

2.

Check the rating given in the instructions and on the 

product to make sure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Personal Injury Hazard. 
Power supply can cause electrical shock.

Disconnect power supply before beginning installation. 

Do not open base unit or lamp knob; there are no 
user-serviceable components inside.

WARNING

UV Light Hazard. 
Harmful to bare skin and eyes. 

Can cause temporary or permanent loss of vision.

Never look at the lamps while illuminated.
Only view illumination by way of the light indicator on 

the lamp knob.

To prevent exposure to ultraviolet light, disconnect 
power to the ultraviolet air treatment system before 

servicing any part of the heating/air conditioning 

system.
Do not mount device in location that allows ultraviolet 

light to be seen after installation.

Do not attempt to bypass the duct mount switch.

Selecting Mounting Location

CAUTION

Equipment Damage Hazard. 

Ultraviolet light can cause color shift or structural 

degradation of plastic HVAC materials.

Select mounting location that prevents exposure to 

plastic components with 

unknown resistance to 

ultraviolet light. 

Three-feet minimum is recommended 

between ultraviolet lamps and plastic-fabricated 

devices (such as humidifiers and non-fiberglass media 

filters).

IMPORTANT

If mounting options are limited, protect plastic or rub-

ber material listed in CAUTION with ultraviolet-resis-
tant material such as aluminum foil duct tape.

NOTE: When the installer is uncertain about whether the 

drip pan in the installation can tolerate UV exposure, 

consult the UV exposure white paper, form no. 50-

8788, at hbctechlit.com Web site.

1.

The ultraviolet air treatment system can be mounted in 

any orientation.

2.

Choose a location that is readily accessible for regular 

inspection and cleaning.

3.

Allow clearance in front of the device for removing the 
lamp assemblies. See Fig. 2 for lamp assembly lengths.

4.

Select mounting location that prevents exposure to 

plastic components with unknown resistance to 
ultraviolet light. A minimum of three feet is required 

between the ultraviolet lamps and devices fabricated of 

plastic, such as humidifiers.

5.

Mount the ultraviolet air treatment system to non-lined 

metal ductwork. Do not mount in a location that permits 

ultraviolet exposure to plastic flexible duct liner.

CAUTION

Sharp Edges Hazard.

Can cause personal injury.

Be careful when inserting ultraviolet device into the 
sheet metal cutout.

Wear protective gloves when working near sheet 
metal.

Duct Mounting

Use the following instructions to mount the air treatment 

system on the air duct of an HVAC system:

1.

Disconnect power to the HVAC system before installing 
the Ultraviolet Air Treatment System.

2.

Determine the location for installation (see Fig. 1):

a. The single-lamp and dual-lamp units require an 

easily-accessible, flat mounting surface on the 

metal return air duct of the HVAC system. The coil 

irradiation unit requires an easily-accessible, flat 
mounting surface on the metal supply air duct of the 

HVAC system. The coil irradiation unit must be 

located so the lamp surrounds the evaporator coil 
and drip pan with ultraviolet light.

b. The duct mounting location must be a minimum of 

8 in. wide. See Fig. 2.

c. The depth of the duct must accommodate the full 

length of the ultraviolet lamp for your model as 

shown in Fig. 2.

d. The unit should be located as far away as possible 

from any rubber or plastic components, such as 

isolators, in the duct.

e. The space adjacent to the mounting location must 

be large enough to allow for ultraviolet lamp 

installation and removal.

f. A 120 Vac electrical outlet must be within range of 

the unit to plug in the power cord.

Содержание Enviracaire Elite UV100E

Страница 1: ...nd with the ultraviolet rays Safe design prevents lamps from lighting unless the base is correctly mounted on the HVAC duct Light pipe to safely view the lamp operation Power cord that plugs into 120 Vac electrical outlet Quick and easy lamp replacement Easy lamp maintenance AIRWATCH Indicator can be installed to remind customers when to change lamp To capture and minimize micro organism pass thro...

Страница 2: ...ncy performance against airborne bacteria in return air applications UV100E dual lamp unit is mounted in the return air duct of an HVAC system It has high efficiency performance against airborne bacteria in return air applications UV100E coil irradiation unit is mounted downstream from the air conditioner cooling coils or in the return air duct of the HVAC system The single lamp unit reduces mold ...

Страница 3: ...xposure consult the UV exposure white paper form no 50 8788 at hbctechlit com Web site 1 The ultraviolet air treatment system can be mounted in any orientation 2 Choose a location that is readily accessible for regular inspection and cleaning 3 Allow clearance in front of the device for removing the lamp assemblies See Fig 2 for lamp assembly lengths 4 Select mounting location that prevents exposu...

Страница 4: ... Air Treatment Systems CONDITIONED AIR TO ROOM HEAT EXCHANGER RETURN AIR FURNACE CONDENSATE DRAIN CONDENSER COOLING AIR REMOTE CONDENSER SECTION HIGH SIDE REFRIGERANT PIPING SINGLE LAMP AND DUAL LAMP UNIT LOCATION COIL IRRADIATION UNIT LOCATION M13529A ELECTRONIC AIR CLEANER HIGH EFFICIENCY AIR CLEANER ...

Страница 5: ... in in mm 2 1 4 57 3 1 2 89 4 1 2 114 7 178 1 25 7 178 3 1 2 89 4 102 14 7 8 379 M17661A COIL IRRADIATION 2 1 4 57 3 1 2 89 4 1 2 114 7 178 1 25 7 178 3 1 2 89 4 102 7 7 16 188 M17662A SINGLE LAMP 3 1 2 89 5 127 7 178 10 254 2 3 16 56 8 1 2 216 3 1 4 83 4 102 14 7 8 379 M17663A 3 1 2 89 5 127 DUAL LAMP ...

Страница 6: ... Be sure the duct surface is flat after all holes are drilled 8 Position the entire base unit on the duct Be sure the lamp holes in the duct align with those in the unit to allow lamp insertion 9 Install the unit into the duct using the three or two depending on the model no 10 2 in Phillips head sheet metal mounting screws provided There is a spare screw provided for the three screw model 10 Tigh...

Страница 7: ...0249 1 M17665B CENTERS OF 2 IN 51 MM HOLES FOR LAMP 3 32 IN 3 MM PILOT HOLES FOR MOUNTING SCREWS ALIGN EITHER OF THESE LINES AS CLOSE AS POSSIBLE TO DUCT CENTER LINE INSTALLATION TEMPLATE FOR DUAL LAMP 3 32 IN 3 MM PILOT HOLES FOR MOUNTING SCREWS ...

Страница 8: ...e heating air conditioning system 14 Plug the cord into the nearby 120 Vac electrical outlet 15 Reconnect the power to the HVAC system 16 Choose a location on the adjacent HVAC equipment for the HVAC maintenance label included in the air treatment system packing box Choose a location that a future installer can easily see during any future HVAC maintenance or repair 17 Adhere the HVAC maintenance ...

Страница 9: ...et lamp s Fig 4 Ultraviolet lamp cleaning reminder schedule To clean your lamps 1 Disconnect the power to your HVAC system 2 Unplug your ultraviolet air treatment system cord from the electrical outlet and allow the lamps to cool for at least 15 minutes 3 Rotate your lamp knob counterclockwise and gently pull the lamp knob to remove the lamp s 4 Holding only the lamp knob wipe the lamp glass using...

Страница 10: ...urface with your hands 6 Continue lightly pushing in on the lamp while rotating it slowly counterclockwise This should cause the lamp to drop into the bottom of the lamp well 7 Rotate the lamp clockwise until it snaps into place with the lamp light indicator aligned with the raised button on the unit cover WARNING UV Light Hazard Harmful to bare skin and eyes Can cause temporary or permanent loss ...

Страница 11: ...ngle Lamp Return Air Unit UC100E1006 18W UV100E1019 Dual Lamp Return Air Unit UC100E1014 twin pack two lamps provided 36W each lamp UV100E1035 Coil Irradiation Unit UC100E1030 36W UV100E1019 DUAL LAMP RETURN AIR UNIT UV100E1001 SINGLE LAMP RETURN AIR UNIT UV100E1035 COIL IRRADIATION UNIT M19013 UC100E1014 UC100E1030 UC100E1006 ...

Страница 12: ...n and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers UV100E ULTRAVIOLET AIR TREATMENT SYSTEM M18621 ...

Отзывы: