Water bottom measurement
___________________________________________________________________________
Instruction manual VITO
Page 41
5.4
Troubleshooting
5.4.1
Water error request (item EW)
Data item
EW
contains the most recent error code concerning the water probe measurement, encountered by the
optional HCU/ICU_HPI board.
xx00
No error, value at initialisation
xx01
C
test
error
Either defective 762 VITO interface or defective (leaking) water probe
xx02
Linearity error
Should be within 1% of the test capacitance, if too large, change 762 VITO interface
xx03
No water probe available
Measured capacitance is >4000 pF; check water probe wiring (green wire and coax
cable) to 762 VITO interface terminals
xx04
Sub system error
Defective 762 VITO interface
xx05
Capacitance too low
Measured capacitance <50pF; check water probe wiring or change 765/766/768 VITO probe
xx06
Capacitance too high
Measured capacitance >3000pF;check water probe wiring or change 765/766/768 VITO
probe
xx07
Capacitance shortcut
Either water probe error or internal 762 VITO interface error
xx11
No reply on initial HART commands
Communication error. Check connection level gauge – 762 VITO interface, or change
762 VITO interface or HCU/ICU_HPI board
xx79
Not calibrated
Check items VR and VT (set to zero or are equal to each other)
xx98
No water sources found
No water probe connected
xx:
24 for HPU emulation;
28 for HSU emulation;
30 for HCU emulation
5.4.2
Water level (ullage) status bytes
The water level and ullage, items
LW
and
LH
, are constructed as follows: s
0
s
1
IIIIIIIII
For decoding of the status bytes, refer to the ASCII table in appendix A.
IIIIIIIII : water level (or ullage) value; format according the level dimension
LD
.
s
0
s
1
: two status bytes, bit coded; containing the following information:
status byte s0
status byte s1
bit 0: general probe fail
bit 0: water probe (0=present; 1= absent)
1: low water alarm
1: 0 (not used)
2: high water alarm
2: 0 (not used)
3: water below probe warning
3: 0 (not used)
4: water above probe warning
4: 0 (not used)
5: 0
5: 0
6: 1
6: 1
7: 0
7: 0
Note:
Only the bits which are to set to ‘1’ have an active status.