6.4.10 HART Measurement Transmitter (EEx d) via MFE7 Board
(without barrier, external Power Supply)
Hazardous Area
Safe Area
enCore device
MFE7 board
A1+ or A2+
A1− or A2−
SH
HART pressure
transmitter, EEx d
HART temperature
transmitter, EEx d
HART
communicator
0V
24V
+
−
(sink mode)
Fig. 6-15: HART pressure and temperature transmitter (EEx d) via MFE7 – example
Characteristics MFE7:
•
a galvanically isolated input safe circuit for a transmitter with HART
interface
− load:
approx. 300 Ω
•
protocol converter integrated in input:
max. 4 transmitters:
thereof max. 1 transmitter in burst mode
13,
•
max. cable length:
250 m
13
Up to and including basic system version
03-24
, you could use either up to
4 × transmitters in multidrop mode or 1 × transmitters in burst mode.
14
Burst mode is not supported by all transmitters.