Assembly Instructions
6
Page 60 of 120
Operating Instructions
enCore FC
Hints on parameterization
Branch
<device> – Basic System – I/O boards –
Board <x>: ExMFE5
Set the following value:
•
channel
P1+ P1−
: type
Current input
6.4.5 Analog Measurement Transmitter (EEx d) via MFE7 Board
(without barrier)
Hazardous Area
Safe Area
enCore device
MFE7 board
A1+ or A2+
A1− or A2−
SH
Analog pressure
transmitter
4...20 mA, EEx d
(source mode)
Fig. 6-10: Analog pressure transmitter (EEx d) via MFE7 – example
Characteristics MFE7:
•
a galvanically isolated input safe circuit with 4 ... 20 mA interface:
− open-circuit voltage:
approx. 21 V
− voltage at 20 mA:
approx. 12.6 V
− max. load:
600 Ω
•
max. measurement error:
±0.05 % of the measurement
(in the measuring range 4 ... 20 mA and between −10 to +55 °C
ambient temperature)