Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2014/35/EU
RoHS directive 2011/65/EU
Standard
EN 61010-2-032:2012
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10 °C .. +55 °C
-20 °C .. +70 °C
5% .. 85%, non condensing
2
IP20
The TQ is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current (Ith)
Rated dynamic current (Idyn)
Rated continuous thermal current (Icth)
Rated insulation level
Rated frequency
Class of insulation
Material (housing)
IEC 61869-2:2012
60 x Ipr / 1s
2.5 x Ith
100%
0.72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL94: V2
Specifications per type
EEM-CT-
150-5
200-5
250-5
EEM-CT-
300-5
400-5
500-5
EEM-CT-
600-5
750-5
1000-5
EEM-CT-
1000-5-L
Suitable for
cable
ø 18mm
ø 28mm
ø 42mm
2x ø
42mm
../1A
Secondary
leads length
for 0.5mm
2
3m
3m
5m
5m
Approximate
weight
360g
310g
525g
725g
../5A
Secondary
leads format
0,5 meter
ø1.5mm
0,5 meter
ø1.5mm
3 meter
ø1.5mm
3 meter
ø1.5mm
Approximate
weight
300g
250g
650g
850g
Please be aware, product liability, fulfilment to requirements and
warranty are all expired when modifications on the product are made.
Printing and typographical reserved.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instructions
All activities for the installation, commissioning, and main-
tenance of this current transformer must be performed by
qualified personnel with a knowledge of applicable safety
precautions. It is assumed that the reader of this document
has sufficient electro-technical knowledge to understand the
contents of this document.
General
The TQ split-core is a current transformer (CT) and can be
used only to measure electrical alternating currents. It is
suitable only for mounting on insulated primary conductors in
a weather-protected and dry location.
Explanation of symbols
This product is designed according to the EN
61010-2-032:2012 standards and therefore meets
the requirements of the Low Voltage Directive
2014/35/EU.
Do not apply around or remove from
UNINSULATED HAZARDOUS LIVE conductors,
which may render electric shock, electric burn, or
arc flash.
Read this Installation Guide before mounting the
product. Unprofessional work activities on
electrical installations may endanger the life and
health of human beings and livestock!
Under no circumstances may the secondary
circuit of the CT be opened while the CT is closed
and current is flowing in the primary circuit. High
voltages may appear on the secondary leads if
this circuit is left open.
RoHS Directive 2011/65/EU
ELEQ states that they use only qualified com-
ponents in their products from manufacturers
whose specifications meet or exceed the require-
ments of the European Directive for the
Restriction of use of certain Hazardous
Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates
that the equipment should not be disposed of as
unsorted municipal waste. Contact a qualified
recycler for disposal
Manufactured for and on behalf of the Connected Building Division of Honeywell
Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland
by its Authorized
Representative:
Home and Building Technologies
Honeywell GmbH
Phone +49 (0) 7031 637 01
Böblinger Strasse 17
Fax +49 (0) 7031 637 740
71101 Schönaich, Germany
http://ecc.emea.honeywell.com
EN1B-0647GE51 R1019A
/
83743 / EN1801
EEM-CT
Split-Core Current Transformer
Installation Guide
EEM-CT-150-5
EEM-CT-200-5
EEM-CT-250-5
EEM-CT-300-5
EEM-CT-400-5
EEM-CT-500-5
EEM-CT-600-5
EEM-CT-750-5
EEM-CT-1000-5
EEM-CT-1000-5-L
Read this Installation Guide before installing the product!
® U.S. Registered Trademark
Copyright © 2019 Honeywell
EN1B-0647GE51 R1019A