Document: 151455      Rev: 

E

ECN: 17-0212

Installation and Operation Guide

ECS-Series

Emergency Communication System

Содержание ECS Series

Страница 1: ...Document 151455 Rev E ECN 17 0212 Installation and Operation Guide ECS Series Emergency Communication System ...

Страница 2: ...arning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explo sions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reach...

Страница 3: ...ith a normal room temperature of 15 27º C 60 80º F Verify that wire sizes are adequate for all initiating and indi cating device loops Most devices cannot tolerate more than a 10 I R drop from the specified device voltage Like all solid state electronic devices this system may operate erratically or can be damaged when subjected to light ning induced transients Although no system is completely imm...

Страница 4: ... Silent Knight Technical Support at 800 446 6444 Please give the following information Product name and version number if applicable Printed manual Topic Title Page number for printed manual Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation To order parts contact Honeywell Silent Knight Sales at 800 328 0103 ...

Страница 5: ...ironmental Specifications 3 1 3 2 Wiring Specifications 3 1 3 3 Electrical Specifications 3 5 3 4 Installing ECS Series Cabinets 3 5 3 4 1 Preventing Water Damage 3 5 3 4 2 Surface Mounting the IFP 100ECS IFP 1000ECS IFP 300ECS IFP 2100ECS or ECS LOC Cabinet 3 5 3 4 3 Surface Mounting the IFP 2000ECS or ECS LOC Cabinet 3 6 3 4 4 Surface Mounting the IFP 300ECS Cabinet 3 8 3 4 5 Surface Mounting th...

Страница 6: ... 1 Mounting the ECS INT50W 4 25 4 5 2 Wiring to a FACP 4 27 4 5 3 VBUS Wiring 4 27 4 5 4 Setting the Device Address 4 29 4 6 Speaker Wiring 4 29 4 6 1 Calculating Current Draw and Standby Battery 4 29 4 7 Installing the ECS 125W 4 30 4 7 1 ECS 125W Board Layout 4 30 4 7 2 Mounting the ECS 125W 4 31 4 7 3 Mounting the ECS 125WBD Board Only 4 31 4 7 4 Wiring Specifications 4 33 4 7 5 Speaker Wiring ...

Страница 7: ...nstalling the ECS 50WBU 4 57 4 9 1 ECS DUAL50W Board Layout 4 57 4 9 2 Installing the ECS 50WBU 4 58 4 10 Installing the ECS CE4 4 59 4 11 Installing the ECS RVM 4 60 4 11 1 ECS RVM Board Layout 4 60 4 11 2 Wiring the ECS RVM 4 61 4 11 3 Installing the Microphone 4 62 4 11 4 To Remove the ECS RVM 4 63 4 12 Addressing SBUS Devices 4 66 Panel Security Honeywell Fire Product Warranty and Return Polic...

Страница 8: ... Module IFP 300ECS IFP 300 ECS NVCM Network Voice Control Module IFP 2100ECS IFP 2100 ECS NVCM Network Voice Control Module ECS LOC ECS RVM Remote Voice Module RA 2000 Remote Annunciator ECS LOC2100 ECS RVM Remote Voice Module RA 2000 Remote Annunciator Model Number Description Compatible With ECS SW24 Adds 24 additional switches to the ECS VCM ECS NVCM or ECS RVM to manually select various voice ...

Страница 9: ...le LOC IFP 100ECS IFP 300ECS IFP 1000ECS or IFP 2000ECS Systems can support up to seven ECS LOC s IFP 2100ECS Systems can support up to 15 ECS LOC s Mappable Speaker Circuits IFP 100ECS IFP 300ECS or IFP 1000ECS Systems can support up to 64 mappable speaker circuits using a combination of ECS 50W s ECS 125W s ECS DUAL50W s and ECS CE4 s IFP 2000ECS and IFP 2100ECS Systems can support up to 128 map...

Страница 10: ...hat is programmed to trigger an ECS event on the IFP 2000ECS or IFP 2100ECS ECS LOC Priority The priority level which is programmed for every ECS LOC In order from lowest to highest Low Normal High ECS Super User A user profile provided option that allows the user to override all ECS Control rules and gain ECS Control VBUS The VBUS is an analog voice bus that carries the recorded voice messages fr...

Страница 11: ...l notify the user as soon as possible Users have the right to file complaints if necessary with the Federal Communications Commission 5 The telephone company may make changes in its facilities equipment operations or procedures that could affect the operation of the equipment If this happens the telephone company will pro vide advance notice to allow you to make the necessary modifications to main...

Страница 12: ...plications whereby a general alarm is sounded It is intended for elevator recall door holding applications and hotel motel room applications The system allows the Alarm Verification time to be set from 60 to 255 seconds For UL certified installations the setting must be a minimum of 60 seconds The system allows the Auto resound time to be set to 24 or 4 hours For UL certified installations that ar...

Страница 13: ...ce and either a 5220 Keltron 3158 or the built in Digital Alarm Communicator Transmitter DACT 1 Do not exceed the current load restrictions shown in Section 3 7 5 2 The AC Loss Hours option must be set from 1 3 hours 2 2 5 Requirements for the Installation of Carbon Monoxide CO Detection and Warning Equipment NFPA 720 When using carbon monoxide detection the system must be monitored by a Supervisi...

Страница 14: ...ondensing 3 2 Wiring Specifications Induced noise transfer of electrical energy from one wire to another can interfere with telephone communication or cause false alarms To avoid induced noise follow these guidelines Isolate input wiring from high current output and power wiring Do not pull one multi conductor cable for the entire panel Instead separate the wiring as follows Do not pull wires from...

Страница 15: ...ld beads or by wrapping it around a ferrite toroid Figure 3 1 Wire Routing Example Note All circuits are power limited except the battery and AC cabling Maintain 1 4 inch spacing between high Telco Wiring NACs SBUS Devices SLC Devices Relays IFP 100ECS SBUS Devices Flexputs NACs VBUS VBUS AC AC Relays SLC Devices IFP 1000ECS ...

Страница 16: ...nd between power limited and non power limited circuits Figure 3 2 IFP 2000ECS Wire Routing Example Figure 3 3 Wire Routing IFP 300ECS Relays AC Power Input SLC SBUS Devices VBUS Flexputs NACS Device SLC devices Phone Lines AC Power Input SBUS devices ...

Страница 17: ...ECS Series Emergency Communication System Installation Manual 151455 3 4 Figure 3 4 Wire Routing IFP 2100ECS Relay outputs AC Power Input lines SLC devices devices To Phone SBUS ...

Страница 18: ...n the wall surface by using the mounting holes in the back of the cabinet see Figure 3 5 The ECS LOC Local Operating Console is a combination ECS RVM Remote Voice Module and its associated annunciator The ECS LOC is compatible with the Honeywell Farenhyt Series panels IFP 1000ECS IFP 100ECS IFP 300ECS and IFP 2100ECS Table 3 1 ECS 50W AC Current Draw Module Voltage Standby Current Alarm Current EC...

Страница 19: ...he wall surface by using the mounting holes in the back of the cabinet see Figure 3 6 The ECS LOC is a combination ECS RVM Remote Voice Module and its associated RA 2000 annunciator The ECS LOC is compatible with the IFP 2000ECS For more information refer to Installation manuals for the FACP Cabinet dimensions are 20 362 W x 27 H x 5 054 D Model Number FACP Installation Manual PN IFP 2000ECS 15143...

Страница 20: ...Installation 151455 3 7 Figure 3 6 IFP 2000ECS and ECS LOC Cabinet Mounting Holes 27 20 362 Bottom Mounting Holes Key Shaped Holes ...

Страница 21: ...can be mounted on the wall surface by using the mounting holes in the back of the cabinet see Figure 3 6 For more information refer to Installation manuals for IFP 300ECS PN LS10145 001SK E Cabinet backbox dimensions are 26 5 H x 20 W x 4 1 D Figure 3 7 IFP 300ECS Cabinet Mounting Holes 26 5 Bottom Mounting Holes Key Shaped Holes 20 ...

Страница 22: ...ions are 26 5 H x 20 W x 4 1 D Figure 3 8 IFP 2100ECS or ECS LOC2100 Cabinet Mounting Holes 3 4 6 Surface Mounting Instructions The ECS Series cabinets can be mounted on the wall surface by using the mounting holes in the back of the cabinet see Figure 3 8 1 Insert two screws level with each other 16 apart for the top cabinet key shaped holes See Figure 3 8 2 Hang the cabinet onto the two screws T...

Страница 23: ... be 1 5 to 1 75 of cabinet extruding from the wall this should be measured from either the top edge or bottom edge to the exterior side of the sheet rock See Fig ure 3 9 3 Mount the cabinet to wall studs by inserting a screw through the cabinets side mounting holes into the wall stud Figure 3 9 Detail of Flush Mounting with Trim Ring Important Do not insert the cabinet deeper than recommend above ...

Страница 24: ...ront panel This section provides instructions on how to remove the door and dead front panel 1 Disconnect the SBUS connection between the ECS VCM and the FACP 2 For the IFP 100ECS control disconnect the cable harness that connects the display to the main control board 3 Disconnect VBUS wiring from ECS VCM 4 Using a Phillips head screw driver remove the six screws that hold the dead front panel in ...

Страница 25: ...how to remove the door and dead front panel for the IFP 300ECS or the IFP 2100ECS 1 Disconnect the connection between the ECS NVCM and the ECS EMG keypad 2 Disconnect VBUS wiring from ECS NVCM 3 Slide the door or dead front over two pins in the hinge bracket of the base The outer hinge pins are for the door the inner hinge pins are for the dead front See Figure 3 12 Figure 3 12 Cabinet Door and De...

Страница 26: ...y Communication System This section provides information on how to install or remove the ECS VCM to the control cabinet and how to make the proper wiring connections 4 2 1 ECS VCM Board Layout The following is description of the ECS VCM voice control module components Figure 4 1 Back View of ECS VCM ECS Series Model Number FACP Installation Manual IFP 2000ECS 151430 L8 IFP 1000ECS 151460 IFP 100EC...

Страница 27: ...l 151455 4 2 Figure 4 2 Front View of ECS VCM 4 2 2 Connecting the ECS VCM to the SBUS Refer to Figure 4 3 to properly connect the ECS VCM to the FACPs SBUS Figure 4 3 SBUS Connections See Section 4 12 to set SBUS addressing FACP ECS VCM Supervised Power Limited ...

Страница 28: ... dead front panel See Figure 4 6 for IFP 100ECS and IFP 1000ECS or Figure 4 7 for IFP 2000ECS 5 For the IFP 100ECs or IFP 1000ECS Connect one end of the wiring harness P N 130398 sup plied to the ECS VCM and the other end to the ECS SW24 as shown in Figure 4 4 6 For IFP 2000ECS connect one end of the wiring harness PN 130398 supplied to the ECS VCM and the other end to the ECS SW24 If two ECS SW24...

Страница 29: ...gency Communication System Installation Manual 151455 4 4 Figure 4 5 Wiring Harness Connection for VCM to Two ECS SW24 Figure 4 6 Back View of IFP 100ECS or IFP 1000ECS Dead Front Panel VCM Mounting Studs ECS SW24 VCM ...

Страница 30: ... Installing the Microphone To install the microphone follow these steps 1 Clip the microphone into the micro phone clip See Figure 4 18 Figure 4 8 Sliding Microphone into Microphone Clip 2 Insert Microphone cord through hole at the bottom of the dead front panel See Mounting Studs ECS SW24 VCM ...

Страница 31: ...4 20 4 Push the strain relief into the hole in the dead front panel 5 Connect microphone to appropriate connector on ECS NVCM Keypad Figure 4 10 Installing Strain Relief Clip 4 3 Installing the ECS NVCM This section provides information on the ECS NVCM Network Voice Control Module The ECS NVCM is compatible with the IFP 2100ECS and IFP 300ECS FACPs For more information on how to install or remove ...

Страница 32: ...ayout Figure 4 11 Front View of ECS NVCM Figure 4 12 Back View of ECS EMG Keypad Network Connector P4 Keypad connector P3 VBUS1 VBUS2 Port 1 Port 2 AUX AUDIO CMD1 COMMON CMD2 Fiber Module Connectors ECS NVCM Connector Microphone Connection ECS SW24 Connector ...

Страница 33: ...tteries 4 Install the ECS SW24 on the six mounting studs located on the inside of the dead front panel See Figure 4 15 for IFP 300ECS or Figure 4 17 for IFP 2100ECS 5 For the IFP 300ECS connect one end of the wiring harness P N 130398 supplied to the ECS EMG and the other end to the ECS SW24 as shown in Figure 4 15 6 For IFP 2100ECS connect one end of the wiring harness PN 130398 supplied to the E...

Страница 34: ...ECS Device Installation 151455 4 9 9 Reconnect backup batteries Figure 4 14 Wiring Harness Connection for NVCM to IFP 300ECS Figure 4 15 Connection between ECS EMG and One ECS SW24 FACP NVCM ...

Страница 35: ...ECS Series Emergency Communication System Installation Manual 151455 4 10 Figure 4 16 Wiring Harness Connection for NVCM to IFP 2100ECS Figure 4 17 Connection between ECS EMG and Two ECS SW24s ...

Страница 36: ...ion sheet PN LS10178 001SK E SK FML Fiber Optic Multi Mode Receiver SK FSL Fiber Optic Single Mode Transmitter 4 3 4 Installing the Microphone To install the microphone follow these steps 1 Clip the microphone into the micro phone clip See Figure 4 18 Figure 4 18 Hang Microphone on to Microphone Clip 2 Insert Microphone cord through hole at the bottom of the dead front panel See ...

Страница 37: ...ough Dead Front Panel Hole 3 Attach strain relief clip to microphone cord The strain relief clip should have about 2 of micro phone cord through it See Figure 4 20 4 Push the strain relief into the hole in the dead front panel 5 Connect microphone to appropriate connector on ECS EMG Figure 4 20 Installing Strain Relief Clip 2 ...

Страница 38: ...able in a black cabinet as P N ECS 50WB 4 4 1 ECS 50W Board Layout Figure 4 21 shows the location of terminals DIPs and Expander connection used in the installation of the ECS 50W Figure 4 21 Components Layout of ECS 50W All references to ECS 50W within this manual are applicable to the ECS 50WB VBUS In Out SBUS SBUS ID DIPs Audio Circuits Audio Expander AC Transformer Connector Battery Connector ...

Страница 39: ... attach a piece of plywood to the concrete surface and then attach the cabinet to the plywood Also mount any other modules to the plywood The cabinet can be surface or flush mounted If you will be flush mounting the cabinet the hole for the enclosure should be 14 5 W x 24 H x 3 7 16 D 36 8cm W x 62 9cm H x 8 73cm D Do not flush mount in a wall designated as a fire break The Outside dimensions of t...

Страница 40: ...inst EMI and AFI emission and susceptibility If using shielded cable attach the shield to earth ground on the control panel For the same reasons wiring within the cabinet should be routed around the perimeter of the cabinet It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits High fre...

Страница 41: ...igure 4 23 Wire Routing Example for ECS 50W 4 4 4 Speaker Wiring Each ECS 50W supplies four NAC Notification Appliance Circuit for speaker connection The speaker circuit can be supervised and wired Class B Style Y or Class A Style Z The speaker circuit is capable of 50 watts of power at 25 Vrms or 70 7 Vrms ...

Страница 42: ...rs Total Load Wire Distance in Feet 1 2 W 1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 70Vrms 25000 39700 63200 100520 20 10 25Vrms 10W 2125 3380 5375 8540 70Vrms 15200 24150 38400 61100 30 15 25Vrms 15W 1460 2320 3690 5870 70Vrms 11000 17500 27800 44200 40 20 25Vrms 20W 1100 1750 2780 4420 70Vrms 8500 13510 21500 34175 52 26 25Vrms 26W 760 1200 1920 3050 70Vrms 6...

Страница 43: ...ries the recorded voice messages from the ECS VCM or ECS NVCM to the ECS 50W s or the voice messages generated from a system microphone to the ECS 50W s The maximum resistance on the VBUS is 20Ω Connect the VBUS from the ECS VCM to the ECS 50W s as shown in Figure 4 26 or ECS NVCM as shown in Figure 4 27 Figure 4 26 VBUS Wiring with ECS VCM Supervised Power Limited To Next ECS 50W 15kΩ EOL ECS VCM...

Страница 44: ...ECS Device Installation 151455 4 19 Figure 4 27 VBUS Wiring with ECS NVCM ECS NVCM ECS 50W ECS 50W 15kΩ EOL at last panel on the VBUS Supervised Power Limited VBUS Connections 3 Vrms 5mA max ...

Страница 45: ...CS or up to 16 for IFP 2000ECS or IFP 2100ECS onto the main control SBUS Refer to Section 4 1 for SBUS specifications Wire the SBUS as shown in Figure 4 28 or Figure 4 29 Figure 4 28 SBUS Connections of the ECS 50W Figure 4 29 Connecting Multiple ECS 50Ws to the SBUS See Section 4 12 for information on setting SBUS addresses Control Panel Supervised Power Limited To Next ECS 50W Max 8 Control Pane...

Страница 46: ... ECS 50W cabinet follow these steps 1 Open the cabinet door 2 To access cabinet interior open dead front panel by removing the upper screw and the mid door retaining screw 3 Mount the transformer onto the threaded cabinet transformer mounting studs using the supplied locking hex nuts as shown in Figure 4 30 Figure 4 30 Transformer Mounting Threaded Mounting Studs ...

Страница 47: ...unication System Installation Manual 151455 4 22 4 Connect AC to the Transformer as Shown in Figure 4 31 Figure 4 31 AC Connections 5 Plug the transformer output to the AC connector on the control panel as shown in Figure 4 31 ...

Страница 48: ...fer to Figure 4 32 1 Connect the black wire of the battery harness to the side of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 3 Connect the red wire from the battery harness to the positive side of battery 1 Figure 4 32 Battery Connections to the ECS 50W ...

Страница 49: ...s used to amplify the audio message for distribution throughout the facility for the Emergency Communication System 4 5 1 Board Layout Mounting Figure 4 33 Front View of ECS INT50W Table 4 3 Current Draw ECS 50W and ECS CE4 Device No of Devices Current Per Device Standby Current Alarm Current ECS 50W 25V 1 Standby 85 mA 85 mA Alarm 525 mA 525 mA ECS 50W 70 7V 1 Standby 100 mA 100 mA Alarm 580 mA 5...

Страница 50: ...unting the ECS INT50W in the ECS cabinet that contains a EVS NVCM it is necessary to mount the ECS INT50W on the right side of the control board To do this you will need the ECS AMPMT mounting kit ordered separately 4 Mount the ECS AMPMT plate into the cabinet using the six supplied screws Orientate with Top side up see Figure 4 35 Secure the ECS INT50W onto the six standoffs making sure the two c...

Страница 51: ...es Emergency Communication System Installation Manual 151455 4 26 Figure 4 36 ECS INT50W Installed using the ECS AMPMT Figure 4 37 ECS INT50W installed in IFP 2100ECS Cabinet Install with coils to the top right ...

Страница 52: ...med as Constant Auxiliary Power Refer to the FACP installation manual Figure 4 38 Wiring the ECS INT50W to the FACP 4 5 3 VBUS Wiring The VBUS is an analog voice bus that carries the recorded voice messages from the ECS VCM to the ECS INT50Ws or the voice messages generated from a system microphone to the ECS INT50W The maximum resistance on the VBUS is 20Ω ECS INT50W FACP ...

Страница 53: ... Installation Manual 151455 4 28 Connect the VBUS from the ECS VCM to the ECS INT50Ws as shown in Figure 4 39 Figure 4 39 VBUS Wiring for ECS VCM Figure 4 40 VBUS Wiring for ECS NVCM ECS VCM ECS INT50W ECS INT50W ECS NVCM ECS INT50W ECS INT50W ...

Страница 54: ... battery needs for your installation Complete the remaining instructions in Table 4 4 Batteries larger than 18 AH will not fit in the main control cabinet and must be housed in the RBB Accessory Battery Cabinet Maximum of 33 Amp Hours per system Table 4 4 Current Draw Calculations Device No of Devices Current Per Device Standby Current Alarm Current ECS INT50W 25V 1 Standby 52 mA 52 mA Alarm 275 m...

Страница 55: ...on on how to install the ECS 125W for use with ECS series products 4 7 1 ECS 125W Board Layout Figure 4 41 shows the location of terminals DIPs and Expander connections used in the installation of the ECS 125W Figure 4 41 Components Layout of ECS 125W AC Connector VBUS Out VBUS IN SBUS Audio Expander Audio Circuits Battery Connector ...

Страница 56: ...et the hole for the enclosure should be 14 5 W x 24 75 H x 3 7 16 D 36 8cm W x 62 9cm H x 8 73cm D Do not flush mount in a wall designated as a fire break The Outside dimensions of the cabinet are 16 W x 26 1 4 H x 4 1 8 D 40 64cm W x 66 68cm H x 10 48cm D Follow these steps to properly mount the cabinet 1 On the mounting surface install two screws level with each other 11 apart Figure 4 42 Cabine...

Страница 57: ...ting bracket on the ECS 125WBD with the two mount ing screws See Figure 4 43 Figure 4 43 ECS 125WBD Mounting Bracket 4 Align the mounting holes on the bracket with the enclosure 5 Secure the board to the enclosure 6 Restore AC power and reconnect the backup batteries Figure 4 44 ECS 125WBD In Enclosure Mounting Bracket ...

Страница 58: ... against EMI and AFI emission and susceptibility If using shielded cable attach the shield to earth ground on the control panel For the same reasons wiring within the cabinet should be routed around the perimeter of the cabinet It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits High...

Страница 59: ...ommunication System Installation Manual 151455 4 34 Figure 4 45 provides an example Figure 4 45 Wire Routing Example for ECS 125W To AC VBUS In Out SBUS Audio Circuits Audio Circuits Audio Circuits Battery Connection ECS CE4 ...

Страница 60: ...is allowed 4 7 5 2 Class B Figure 4 46 illustrates how to wire speakers to the control panel using Class B supervision Figure 4 46 Class B Speaker Configuration Table 4 5 Wire Lengths Number Of Speakers Total Load Wire Distance in Feet 1 2 W 1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 20 10 25Vrms 10W 2125 3380 5375 8540 30 15 25Vrms 15W 1460 2320 3690 5870 40 20...

Страница 61: ...hat carries the recorded voice messages from the ECS VCM or ECS NVCM to the ECS 125Ws or the voice messages generated from a system microphone to the ECS 125Ws The maximum resistance on the VBUS is 20Ω Connect the VBUS from the ECS VCM to the ECS 125Ws as shown in Figure 4 48 or for ECS NVCM see Figure 4 49 Figure 4 48 VBUS Wiring for ECS VCM Supervised Power Limited 15kΩ EOL at Last panel Supervi...

Страница 62: ...ECS Device Installation 151455 4 37 Figure 4 49 VBUS Wiring for ECS NVCM ECS 125W ECS 125W Supervised Power Limited 15kΩ EOL at Last panel on the VBUS ECS NVCM ...

Страница 63: ...25Ws up to 8 for IFP 100ECS IFP 300ECS or IFP 1000ECS Up to 16 for IFP 2000ECS or IFP 2100ECS onto the main control SBUS Refer to Section 4 of the FACP s Installation manual for SBUS specifications Wire the SBUS as shown in Figure 4 50 or Figure 4 51 for the ECS VCM Figure 4 50 SBUS Connections of the ECS 125W using ECS VCM Supervised Power Limited ...

Страница 64: ...lation 151455 4 39 Figure 4 51 Connecting Multiple ECS 125Ws to the SBUS using ECS VCM Figure 4 52 Connecting ECS 125W to the SBUS using ECS NVCM Supervised ECS 125W ECS VCM ECS 125W To next ECS 125W Max 8 Power Limited ...

Страница 65: ...addresses 4 7 8 Connecting AC Power At installation connect the AC terminals to the power source as shown in Figure 4 54 It may be necessary for a professional electrician to make this connection The AC terminals are rated as 120 VAC 60 Hz or 240 VAC 50 Hz Figure 4 54 AC Connection 4 7 9 Backup Battery for ECS 125W The following steps explain how to connect the batteries refer to Figure 4 55 ...

Страница 66: ...ttery harness to the side of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 3 Connect the red wire from the battery harness to the positive side of battery 1 Figure 4 55 Battery Connection to ECS 125W ...

Страница 67: ...f Devices Current Per Device Standby Current Alarm Current ECS 125W 120V 1 Standby 375 mA 375 mA Alarm 700 mA 700 mA ECS 125W 240V 1 Standby mA mA Alarm mA mA ECS CE4 0 or 1 Standby 20 mA 20 mA Alarm All Channels 180 mA 180 mA A Current Subtotals mA mA Notification Devices Refer to device manual for number of devices and current ratings B Current Subtotals mA mA C Total current rating of all devic...

Страница 68: ...anual are applicable to the ECS DUAL50WB 4 8 2 Mounting the ECS DUAL50W The ECS DUAL50W is equipped with a separate enclosure It is also available in a black cabinet ECS DUAL50WB Refer to Section 3 1 when selecting a mounting location for the ECS DUAL50W The panel should be accessible to main drop wiring runs It should be mounted as close to the center of the building as possible and located withi...

Страница 69: ...el with each other 11 apart Figure 4 57 Cabinet Flush Mount Dimensions and Mounting Hole Locations 2 Install the cabinet onto the two mounting screws and tighten the screws 3 Insert two screws into the two bottom mounting holes 4 8 3 Mounting the ECS DUAL50WBD Board Only Note Installation and wiring of this device must be done in accordance with NFPA 72 and local ordinances 1 Make certain that AC ...

Страница 70: ...ries Figure 4 59 ECS DUAL50WBD In Enclosure 4 8 4 Wiring Specifications All wiring and devices installed in the system must meet the standards described in National Electrical Code NFPA 70 NFPA Standard 72 and Life Safety Code NFPA 101 To avoid induced noise transfer of electrical energy from one wire to another keep input wiring isolated from high current output and power wiring Avoid pulling one...

Страница 71: ...ot cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits Note Ground Fault Impedance to any Terminal is 0 Ω High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toro...

Страница 72: ...speakers to the control panel using Class B supervision Figure 4 61 Class B Speaker Configuration Table 4 7 Wire Lengths for ECS DUAL50W Number Of Speakers Total Load Wire Distance in Feet 1 2 W 1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 70Vrms 25000 39700 63200 100520 20 10 25Vrms 10W 2125 3380 5375 8540 70Vrms 15200 24150 38400 61100 30 15 25Vrms 15W 1460 2320...

Страница 73: ...is an analog voice bus that carries the recorded voice messages from the ECS VCM or ECS NVCM to the ECS DUAL50Ws or the voice messages generated from a system microphone to the ECS DUAL50Ws The maximum resistance on the VBUS is 20Ω The ECS DUAL50W supports two VBUS channels The wiring method is the same for both channels VBUS1 and VBUS2 should never be wired together Connect the VBUS from the ECS ...

Страница 74: ...9 64 for ECS VCM or Figure 4 65 and Figure 4 66 for ECS NVCM Figure 4 63 VBUS Wiring for Single Channel for ECS VCM UL Listed 15kΩ EOLat Last panel Supervised Power Limited ECS VCM ECS DUAL50W To next ECS DUAL50W on the VBUS ECS DUAL50W ...

Страница 75: ...on Manual 151455 4 50 Figure 4 64 VBUS2 Wiring for Dual Channel for ECS VCM Figure 4 65 VBUS Wiring for Single Channel for ECS NVCM ECS VCM To next ECS DUAL50W UL Listed 15kΩ EOL at Last panel on the VBUS ECS DUAL50W ECS DUAL50W Supervised Power Limited ...

Страница 76: ...1000ECS or up to 16 for IFP 2000ECS or IFP 2100ECS onto the main control SBUS Refer to Section 4 of the FACPs Installation manual for SBUS specifications Wire the SBUS as shown in Figure 4 67 or Figure 4 68 for the VCM and wire the SBUS as shown in Figure 4 69 or Figure 4 70 using the NVCM Figure 4 67 SBUS Connections to the ECS DUAL50W ECS DUAL50W ECS DUAL50W ECS NVCM Supervised Power Limited FAC...

Страница 77: ...ergency Communication System Installation Manual 151455 4 52 Figure 4 68 Connecting Multiple ECS DUAL50Ws to the SBUS using ECS VCM Supervised ECS DUAL50W ECS DUAL50W ECS VCM To next ECS DUAL50W Power Limited Max 8 ...

Страница 78: ...Installation 151455 4 53 Figure 4 69 SBUS Connections to the ECS DUAL50W Figure 4 70 SBUS Connections to Multi ECS DUAL50Ws See Section 4 12 for information on setting SBUS addresses FACP To next ECS DUAL50W FACP ...

Страница 79: ...ackup DIP setting at 1 100 Watt with Backup requires ECS 50WBU Amp A powers Audio Circuits 1 4 Amp B powers Audio Circuits 5 8 The ECS 50WBU will backup Amp A or Amp B but never both DIP setting at 3 If the ECS DUAL50W is connected to an IFP 2000ECS or IFP 2100ECS system and configured to operate in a dual channel setup Amp A and or Amp B is not restricted to which Audio Circuits it can power Howe...

Страница 80: ...g steps explain how to connect the batteries refer to Figure 4 78 1 Connect the black wire of the battery harness to the side of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 3 Connect the red wire from the battery harness to the positive side of battery 1 Figure 4 73 Battery Connection to ECS DUAL50W ...

Страница 81: ...f Devices Current Per Device Standby Current Alarm Current ECS DUAL50W 25V 1 Standby 110 mA 110 mA Alarm 1 2 A 1 2 A ECS DUAL50W 70 7V 1 Standby 110 mA 110 mA Alarm 1 4 A 1 4 A ECS 50WBU 1 Standby 40 mA 40 mA Alarm 110 mA 110 MA A Current Subtotals mA mA Notification Devices Refer to device manual for number of devices and current ratings B Current Subtotals mA mA C Total current rating of all dev...

Страница 82: ...rating the ECS DUAL50W in the 100 watt with backup mode for both single and dual channel setups The ECS 50WBU mounts above the ECS DUAL50W board on the standoffs provided 4 9 1 ECS DUAL50W Board Layout Figure 4 74 shows the location of the ECS 50WBU on the ECS DUAL50W board Figure 4 74 Layout of ECS 50WBU ECS 50WBU ...

Страница 83: ...hat all power supplied to the ECS DUAL50W is removed 2 Connect the backup amplifier cable harness P N 50116775 001 from the connector labeled Backup Amplifier on the ECS DUAL50W to the connector on the ECS 50WBU as shown in Fig ure 4 75 3 Using the 4 supplied screws mount the ECS 50WBU to the standoff s as shown in Figure 4 75 Figure 4 75 Mounting the ECS 50WBU ...

Страница 84: ...Using the four supplied screws mount the ECS CE4 in the cabinet as shown in Figure 4 76 Figure 4 76 Mounting the ECS CE4 2 Connect the audio expander cable harness P N 130426 from the connector labeled Audio Expander on the ECS 50W or ECS 125W to the connector on the ECS CE4 as shown in Figure 4 77 Figure 4 77 Audio Expander Wire Harness Connections Mounting Screws Mounting Screws ECS CE4 ECS CE4 ...

Страница 85: ...the Emergency Communication System 4 11 1 ECS RVM Board Layout The following is description of the ECS RVM remote voice module components Note The ECS VCM and ECS RVM circuit boards look similar but they are not interchangeable The ECS VCM is mounted in the IFP 1000ECS IFP 300ECS IFP 2000ECS or IFP 2100ECS and the ECS RVM is mounted in the ECS LOC cabinet Figure 4 78 Back View of ECS RVM VBUS Micr...

Страница 86: ...Figure 4 79 SBUS Connections 2 See Section 4 12 to set SBUS addressing 3 Connect the SBUS to the annunciator and ECS RVM See Figure 4 80 Figure 4 80 SBUS Wiring for ECS RVM 4 Set the SBUS address on the annunciator and the ECS RVM board See Section 4 12 FACP Supervised Power Limited ECS RVM From Previous SBUS Device Annunciator ECS RVM ...

Страница 87: ...re 4 81 VBUS and ECS 125W Wiring for ECS RVM using the ECS NVCM 4 11 3 Installing the Microphone To install the microphone follow these steps 1 Clip the microphone into the micro phone clip See Figure 4 82 Figure 4 82 Hang Microphone on to Microphone Clip 2 Insert Microphone cord through hole at the bottom of the dead front panel See ECS RVM ECS 125W ...

Страница 88: ... through it See Figure 4 84 Figure 4 84 Installing Strain Relief Clip 4 Push the strain into the hole in the dead front panel 4 11 4 To Remove the ECS RVM To install the ECS RVM follow these steps 1 Remove AC power and disconnect batteries from the main control panel 2 Disconnect the SBUS connections from the SBUS terminals on the ECS RVM See Figure 4 79 3 Disconnect any devices connected to the V...

Страница 89: ...em Installation Manual 151455 4 64 4 Unplug the Microphone from the microphone connector See Figure 4 85 or Figure 4 86 Figure 4 85 Back View of IFP 100ECS or IFP 1000ECS Dead Front Panel Figure 4 86 Back View of IFP 2000ECS Dead Front Panel ...

Страница 90: ... Device Installation 151455 4 65 Figure 4 87 Back View of IFP 300ECS or IFP 2100ECS Dead Front Panel 5 Remove the six hex nuts that hold the ECS RVM in place 6 Lift the ECS RVM off of the dead front panel ...

Страница 91: ...the module to assign an ID to the module Figure 4 88 shows all possible DIP switch positions and their correlation to a numerical ID For example to select ID 2 place DIP switch 2 in the up position Figure 4 88 Possible Module Addresses More information regarding ECS and ECS operations Please refer to the ECS section of FACP s installation manual ECS Series Model Number FACP Installation Manual IFP...

Страница 92: ...igure networks and firewalls Assess security risks Develop a Disaster and Recovery Plan Develop a Backup and Recovery Strategy Install configure and keep anti virus software updated on all computers which access the panel Keep operating system updated on all computers which access the panel Deliver all required system information upon delivery to the system owner Train end users on security mainte...

Страница 93: ...LS1014 001SK E 2 ...

Страница 94: ... ground Return the Honeywell Silent Knight product circuit board only Products that are returned in cabinets will be charged an additional 50 to cover the extra shipping and handling costs over board only returns Do not return batteries Honeywell has the authority to determine if a product is repairable Products that are deemed un repairable will be returned to the customer Product that is returne...

Страница 95: ...ANUFACTURER MAKES NO FURTHER WARRANTIES AND DISCLAIMS ANY AND ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF O...

Страница 96: ......

Страница 97: ......

Страница 98: ...12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www farenhyt com ...

Отзывы: