Emergency Command Center Manual —
P/N LS10001-000FL-E:G 5/3/2016
Operating Instructions
Operation
4.4.9 Alarm/Alert Response, System Configured for Combo
Fire/Mass Notification with Fire Priority
If a fire alarm
only
occurs under this configuration, then the system will respond as in Section 4.4.3
above.
If a mass notification alarm/alert
only
occurs under this configuration, then the system will respond
as in Section 4.4.7 above and additionally will:
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can
annunciate the alarm/alert and notify a central station (if programmed to do so).
If a fire alarm is active in the system and a subsequent mass notification alarm/alert occurs, then the
system will not respond until the fire alarm has been restored.
4.4.10 Alarm/Alert Restoral, System Configured for Combo
Fire/Mass Notification with Fire Priority
If the restoral is for a fire alarm
only
under this configuration then the system will respond as in
Section 4.4.4 above.
If the restoral is for a mass notification alarm/alert
only
under this configuration then the system
will respond as in Section 4.4.8 above and additionally will:
• Signal the FACP of the restoral using the FACP Data Bus such that the FACP can stop
annunciation of the alarm/alert and notify a central station (if programmed).
If the restoral is for a fire alarm that overrode an earlier active mass notification alarm/event then
the system will:
• Stop playing the fire alarm message
• Turn the “Fire System Active” LED off
• Return the system to the active state of the earlier mass notification alarm/event
4.4.11 Alarm/Alert Response, System Configured for Combo
Fire/Mass Notification with Mass Notification Priority
If a fire alarm
only
occurs under this configuration then the system will respond as in Section 4.4.3
above.
If a mass notification alarm/alert
only
occurs under this configuration then the system will respond
as in Section 4.4.7 above. and additionally will:
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can
annunciate the alarm/alert and notify a central station (if programmed to do so).
If a fire alarm is active in the system and a subsequent mass notification alarm/alert occurs, then the
system will:
• Stop playing the current fire message
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can
annunciate the alarm/alert, notify a central station (if programmed), and turn off audible
NACs (if programmed).
• Respond as in Section 4.4.7 above
If a mass notification alarm/alert is active in the system and a subsequent fire alarm occurs, then the
system will not respond until the mass notification alarm/alert is restored.
Содержание ECC-50/100
Страница 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Страница 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Страница 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Страница 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Страница 114: ...Cut along dotted line ...
Страница 116: ...World Headquarters 1 Firelite Place Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www firelite com ...