GENERAL

DTC  100/4TD  is  a  microprocessor  aided  double  differential  thermostat,  designed  for 

heating of domestic water from two heating sources (collectors, boilers, heat pumps,...), 

using its logic of additional energy source switching on (boiler of central heating system). 

The thermostat controls two pumps or two motors actuated ball valves (EMV 800...) and 

one burner or electric heating element.

The thermostat enables regulation of four parameters, i.e.:

1. Regulation of maximum temperature in hot water tank from 10 to 90°C.

2. Regulation of difference for higher exchanger from 2 to 15K (after-heating circuit)

3. Regulation of difference for lower exchanger from 2 to 15K (collector circuit)

4. Setting two working regimes - C.n.b (normal) and C.d.t. (switching off the limitation of 

boiler temperature for collector circuit).

With first two regulation options you define how much the value of the source temperature

(collector, boiler,...) should exceed the temperature of water around the exchanger in hot 

water tank, that the regulator activates the pump or opens the valve. 

The difference is set in relation to the volume of heat losses of the system which depend 

on lenghts of pipelines from source to hot water tank and on pipeline insulation.

Built-in digital display enables prompt reading of the temperatures of individual sensors 

and of all set values as well.

OPERATION:

DTC 100/4TD double differential thermostat measures the temperature of two heating 

sources (collectors, boiler, ...) and of two spots in user (hot water tank). Heating effect is 

provided, when heating unit (heating element in hot water tank) exceeds the temperature 

of the user  (water in hot water tank) for at least 3 - 5K. Consequently minimum adjustable 

difference is 2K (factory set to 5K). 

When the temperature of the source exceeds the temperature around the exchanger for 

at least 5K, the thermostat opens the valve (EMV...) or activates the pump; it closes the 

valve or stops the pump, when temperature difference is one degree lower than pre-set value.

The thermostat also switches off a pump if pre-set temperature is reached in hot water 

tank (adjustable from 10 to 90°C).

If gas flow boiler, oil boiler or electric heating element (which is switched off during summer

seasons), is connected to after-heating circuit, the regulator can switch on the boiler by 

means of the third output, if domestic water is to be additionally heated by means of after-

heating circuit.  In summer seasons a few days of cloudy weather can appear or use of 

domestic water increases. In such cases domestic water is to be after-heated from additional 

source  (central  heating  system  boiler  or  electric  heating  element).  Classic  differential 

thermostat would require hot boiler throughout the year, which is not recommended from 

ecological and economic point of view. DTC 100/4TD, with its third additional output, enables 

activation of after-heating source. When after-heating of water is required, regulator first

switches on the burner of the boiler and when the condition of difference for after-heating 

circuit is also assured (pre-set difference of boiler has higher temperature than hot water 

tank), pump is switched on.

Содержание DTC 100/4 TD

Страница 1: ... of two heating circuits in combination of solar and classic heating with temperature display and regulation of burner or electric heating element DTC 100 4 TD User s manual Installation and maintenance instructions ID 2106 13 DTC100 4TD Honeywell 170039 ...

Страница 2: ...erential thermostat DTC 100 4TD 2 T1 collector sensor with silicone conductor 3 T2 hot water tank sensor with PVC conductor 4 T3 sensor for installation in boiler or to upstream conduit in front of mixing valve PVC 5 T4 hot water tank sensor with PVC conductor 6 Fixing screws with wall inserts 2 pcs 7 Clip for T4 sensor fastening with fixing springs 8 Instructions for use 9 Warranty certificate In c...

Страница 3: ...boiler and of two spots in user hot water tank Heating effect is provided when heating unit heating element in hot water tank exceeds the temperature of the user water in hot water tank for at least 3 5K Consequently minimum adjustable difference is 2K factory set to 5K When the temperature of the source exceeds the temperature around the exchanger for at least 5K the thermostat opens the valve EM...

Страница 4: ...s a sensor in lower part of hot water tank T3 and T4 are designed for additional i e after heating circuit which additionally heats water in hot water tank upper exchanger T3 is a sensor of heating source generally boiler and T4 is a sensor in upper part of hot water tank TEHNICAL DATA Supply voltage 230V 50Hz 10 Power consumption 4 VA Pump relay rating 3A 230VAC cos 0 6 Type of thermostat P Max m...

Страница 5: ...d sleeve For cables longer than 15m we recommend over voltage protection with VDR resistor flow direction T piece 1 2 pipe 1 2 extension conductor sensor conductor Connection to terminal pins BOILER TERMINAL CONNECTION 1 2 T1 sensor heating source sensor collectors boiler 3 4 T2 sensor hot water tank sensor 5 6 T3 sensor heating source sensor for higher heating circuit boiler 7 8 T4 sensor hot wate...

Страница 6: ...part of exchanger When sensor is mounted as contact one we recommend to coat it with heat conducting paste or liquid metal In special purpose vertical or horizontal tube sensor should be protected against accidental extraction On hot water tank with clip wire and spring strip use paste for better heat transmission In special purpose side tube protect against extraction CONTROL PANEL 1 Key for coll...

Страница 7: ...the water temperature to 55 C max and connect output from terminal 12 and 14 through temperature safety fuse in hot water tank or through additional safety thermostat When you set the required temperature press key T1 to pass over the next setting 2 Setting of difference of collector circuit 0 15 On the display appear C and current difference of collector circuit factory set to 5K With keys T2 in ...

Страница 8: ...the possibility to disconnect the collector circuit and after heating circuit For such step we decide in following cases Disconnection of Collector Circuit Operation It is used in cases of mechanical faults of collector system which requires draining of liquid water from collector system but after heating circuit should operate in automatic mode Disconnection is useful also in systems where water ...

Страница 9: ...e display Display of Sensor Errors Errors of sensors short circuit interrupted sensor are listed on the display If the sensor is short circuited the display shows Er2 and if it is interrupted Er1 For T4 sensor this is permanently shown and for other sensors you must press T1 T2 or T3 keys If T1 or T2 sensor is faulty collector heating circuit is inoperative and after heating circuit operates norma...

Страница 10: ... the valve is opened pump switches on Electric connection DTC Differential thermostat DTC 100 4TD T1 T2 T3 T4 Sensors T1 collector sensor T2 hot water tank sensor T3 boiler sensor T4 hot water tank sensor P1 P2 Circuit pump P2 primary circuit pump P1 after heating circuit pump EMV1 EMV2 Electric motor actuated ball valve EMV 110 4230 series EMV110 3230seriescompact BOILER ...

Страница 11: ...conditions for heating a heating circuit are achieved pump switches on Electric connection DTC Differential thermostat DTC 100 4TD T1 T2 T3 T4 Sensors T1 collector sensor T2 hot water tank sensor T3 boiler sensor T4 hot water tank sensor P1 P2 Circuit pump P2 primary circuit pump P1 after heating circuit pump RV1 RV2 Nonreturn valve BOILER ...

Страница 12: ...d be installed above electric heating element Electric connection DTC Differential thermostat DTC 100 4TD T1 T2 T3 T4 Sensors T1 collector sensor T2 hot water tank sensor T3 boiler sensor T4 hot water tank sensor P1 P2 Circuit pump P2 primary circuit pump P1 after heating circuit pump EMV1 EMV2 Electric motor actuated ball valve EMV 110 4230 series EMV110 3230seriescompact safety thermostat power ...

Страница 13: ...CONNECTION OF ELECTRIC HEATING ELEMENT SAFETY THERMOSTAT OF HEATING ELEMENT POWER RELAY 230V 50Hz EL HEATER BURNER CONTROL WARNING Before opening unplug from power supply Only qualified person can maintain the apparatus ...

Страница 14: ...DTC 100 4 TD 14 HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL ...

Страница 15: ...UTO position Irrespective of the temp after heating pump is continously switched on and collector pump is inoperative Selector switch in ON2 position Set selector switch to AUTO position Collector pump operates normally and after heating pump not After heating circuit discon nected Connect after heating circuit See Settings After heating pump operates normally and collector pump not Collector circ...

Страница 16: ... not appear When closed 100 sealing is guaranteed They have an output for pump up to 100 W in open position therefore they do not present a hydraulic load for pump in closed position They enable pump switching on only in completely open position Due to installed RELAY module they enable control with make contact only If during closing or opening process impurities enter in valve which could block ...

Отзывы: