Honeywell DT92 Скачать руководство пользователя страница 14

DT92 WIRELESS DIGITAL ROOM THERMOSTAT

14

 

INSTALLER MODE – APPLICATIONS SETTINGS 

The DT92 has a special Installer Mode where some features can be adjusted to suit the application and the needs or 
lifestyle of the user. Each adjustable feature is called a Parameter. These are described below. 

Parameter 

Description and typical use 

Minimum ON/OFF time 

DT92 is able to set a minimum limit for the on and off times of the controlled device or 
appliance, to prevent damage or excessive wear. This minimum time can be set to 1, 
2, 3, 4, or 5 minutes, and is particularly important for heating applications with oil 
boilers, or air conditioning applications with compressors. Recommended settings are 
shown in the next table. 

Cycle rate 

Within the control proportional band, the output will be cycled several times per hour, 
to give precise temperature control. This can be set to 3, 6, 9, or 12 cycles, 
depending on the application. Recommended settings are shown in the next table. 

Proportional band width 

The proportional band is the temperature band, adjacent to the set temperature point, 
within which the thermostat will cycle the controlled output (to control the boiler, for 
example). Above or below this band the output will either be fully on or fully off. 
The band can be adjusted up to 3°C (default 1.5°C) to provide improved temperature 
control. This is useful for (a) well-insulated homes with over-sized heating systems or 
(b) air systems with a fast response

Temperature 
measurement offset 

If the thermostat is located in a particularly hot/cold location and cannot be moved, 
then the measured/displayed temperature can be adjusted by +/- 3°C. This is useful if 
the homeowner wants the reading to match the temperature display on another 
appliance. 

Upper / Lower 
temperature limits 

The normal upper temperature limit of 35°C can be reduced as low as 21°C to save 
energy. The normal lower limit of 5°C can be raised as high as 21°C to protect 
inhabitants from the cold.  

Energy saving ECO 
temperature 

On the DT92E ECO model, pressing the ECO button immediately puts the thermostat 
into energy saving mode, where it will control at this predefined temperature for as 
long as the user wishes. This temperature can be set from 5°C to 35°C. 

Heating or Cooling 
operation 

DT92 can be used for heating or cooling applications. If heating/cooling changeover is 
selected, the thermostat can be manually switched from heating to cooling (and back 
again) by pressing and holding the 

 and 

 buttons together for 3 seconds, in 

normal operating mode. 

Off/standby setpoint 

When the off/standby button is activated, the DT92 will control to a special off/standby 
setpoint. By default this is set to 5°C to provide frost protection, but it can be set up to 
16°C if required. It can also be set off, by setting the parameter value to  --  to provide 
a positive off function. In cooling mode the default setting is off. 

Room temperature 
sensor use 

In normal operation the DT92 uses it own temperature sensor. If it is operating in a 
wireless system with HR80 programmable radiator valves the DT92 needs to know 
that it is controlling HR80s. In addition, there is a choice of whether the HR80s can 
use their own in-built temperature sensors, or whether they will use the temperature 
sensed by DT92. The 3 choices then become: 
a) DT92 operating without HR80
b) DT92 operating with HR80, HR80 using their own temperature sensor
c) DT92 operating with HR80, HR80 using the temperature sensed by DT92

Failsafe operation mode 

Should RF communications be interrupted for a significant period of time, for 
whatever reason, it is possible to specify the desired mode of operation under these 
circumstances. The choices are for the Relay box to switch off, or for it to operate at 
20% on. 

HR80 window open 
function enabling 

In a system where DT92 is operating with HR80 programmable radiator valves, the 
HR80 is capable of detecting whether a window has been opened. This parameter 
enables the HR80 response to this condition – it can either shutdown (enabled) or 
operate as before (disabled) 

HR80 local override 
function enabling 

In a system where DT92 is operating with HR80 programmable radiator valves, the 
user can override the room temperature setpoint using the HR80. This parameter can 
allow (enable) this operation, or prevent it (disable). 

Reset parameters 

This provides a means of resetting all the parameters to the factory supplied values. 

Содержание DT92

Страница 1: ...isplay and easy to read characters Display shows room temperature with option to inquire about setpoint 5 C to 35 C setpoint range with 0 5 C increments using and buttons Off standby button allowing manual switch off with frost protection active Adjustable off standby setpoint 5 C to 16 C or DT92 can be set to off completely Room thermostat is battery powered by 2 x AA LR6 alkaline cells giving up...

Страница 2: ...02 EN55014 1 2006 EN55014 2 1997 ETSI EN300 220 3 ETSI EN301 489 3 WEEE RoHS compliant TEMPERATURE CONTROL Sensing element 10K 25 C NTC thermistor Temperature setting range 5 C to 35 C setpoint range in 0 5 C increments Control form Self learning TPI Fuzzy Logic algorithm Proportional band 1 5 C adjustable up to 3 C in 0 1 C increments Minimum on off time 1 minute adjustable up to 5 min in 1 min i...

Страница 3: ...ry This means they will recognize and communicate with each other as soon as they are powered up The complete device is therefore ready for immediate installation CONTROLS DISPLAY LAYOUT battery low warning fault indicator setpoint indicator off standby indicator off standby button temperature display frost protect indicator heating demand indicator ECO mode countdown timer ECO button ECO countdow...

Страница 4: ...l between parameters and to make changes to their values MAIN FEATURES 2 Way RF Communications RF communications between the room thermostat and the relay box is 2 way making it more efficient and reliable and allowing the room thermostat to display information from the relay box such as actual relay status or communications loss Signal Strength Test Mode Another benefit of 2 way RF is to allow th...

Страница 5: ...ork the 2 units must be reset and bound to each other by following the procedure for Binding Re binding 4 Take the DT92 thermostat to the proposed mounting location and initiate the Signal Strength Test This will indicate if the thermostat is suitably positioned to provide a reliable signal for the relay box If the signal strength is too low the thermostat must be repositioned 5 When a suitable po...

Страница 6: ...ROOM THERMOSTAT 6 a Boiler b Boiler potential free connection c Zone valve d Air conditioner WIRING CONNECTIONS a b c d Note BDR91 Relay Box requires a permanent mains power supply Completing the BDR91 Relay Box Installation ...

Страница 7: ...nication Test to confirm the BDR91 relay box is wired correctly and that both devices are bound linked to each other 2 3 m RF COMMUNICATION TEST Initiate RF Communication Test by the following sequence of actions applied to the DT92 thermostat If green LED does not flash units are not linked and must be bound together again If green LED flashes every 6 seconds units are correctly bound and a suita...

Страница 8: ...ion SIGNAL STRENGTH TEST The Signal Strength Test is used to find a suitable position for the DT92 thermostat such that the signal received by the BDR91 relay box is high strength This will optimize system performance The BDR91 relay box measures the strength of the signal received from the room thermostat and upon request sends this measurement back to the room thermostat using the 2 way RF commu...

Страница 9: ...DT92 WIRELESS DIGITAL ROOM THERMOSTAT 9 TEST AND BINDING FLOWCHART Mounting the DT92 Room Thermostat Wall mounting Optional table stand Completing the installation Press for 5 seconds to exit any mode ...

Страница 10: ... around 1m 2 Reset stored data in relay box 3 Put relay box into binding mode 4 Reset stored data in room thermostat 5 Put room thermostat into binding mode 6 Bind room thermostat to relay box Reset Stored Data in Relay Box Press and hold the push button for 15s to reset the stored data in the BDR91 relay box The red LED will give a brief flash every second to verify reset has happened Put Relay B...

Страница 11: ...t Put Room Thermostat into Binding Mode Bind Room Thermostat to Relay Box With both units in binding mode pressing the off standby button on the room thermostat will bind them together To verify it is now bound the red light on the relay box will immediately stop flashing After about 5 seconds the room thermostat will come out of binding mode and go back to off mode ...

Страница 12: ...building the two products should communicate reliably within a 30m range It is important to take into consideration that walls and ceilings will reduce the RF signal The strength of the RF signal reaching the Relay Box depends on the number of walls and ceilings separating it from the room thermostat as well as the building construction the diagram below illustrates an example of typical signal st...

Страница 13: ...rent relay operation The green LED will indicate the relay position Loss of RF Communications If RF communications is lost for whatever reason the BDR91 relay box will operate in failsafe mode as set in the Installer Mode and the red LED will illuminate The DT92 room thermostat will flash the RF symbol until communications are restored 92 90 27 90 30 5 ...

Страница 14: ...e where it will control at this predefined temperature for as long as the user wishes This temperature can be set from 5 C to 35 C Heating or Cooling operation DT92 can be used for heating or cooling applications If heating cooling changeover is selected the thermostat can be manually switched from heating to cooling and back again by pressing and holding the and buttons together for 3 seconds in ...

Страница 15: ...nications LC 0 switch OFF 1 operate at 20 ON 0 Enable HR80 window open function H0 0 disable 1 enable 0 Enable HR80 local override HL 0 disable 1 enable 1 Reset parameters FS 0 1 1 factory settings In cooling mode the off standby setpoint defaults to OFF Only required if system contains HR80 programmable radiator valves Specific Applications Setting What requires to be changed Cycle s hour Minimum...

Страница 16: ...r value To select and change a parameter d Use the and buttons to move from one parameter to another e Press the off standby button to select the parameter value ready to change f Use the and buttons to adjust the parameter value When the correct value is flashing confirm the selection by pressing the off standby button again returning to the parameter menu To exit Installer Mode g Press and hold ...

Страница 17: ...have this switched on all the time even when the house is occupied 5 Do not programme excessive heatup times for the central heating If the occupier is out of the house or still in bed much of this heating would be unnecessary 6 In the evening when the house is up to temperature it is often possible to switch the heating off up to an hour before going to bed without any noticeable reduction in com...

Отзывы: