The DT70 digital thermostats are designed for ON/OFF
control of the valve, or the valve and fan in 2-pipe fan-
coil applications and also one-stage compressors in
DX-type equipment.

The thermostat operates an on/off valve to provide
control at the desired setpoint temperature.

Fan-coil thermostat models are available with constant
or cycled fan operation, and have a three-speed fan
selector switch with low, medium and high settings.

The fan can also be controlled from the thermostat.  In
some cases it is wired to run continuously, and can be
switched off with the system ON/OFF switch.

Heat/cool changeover operation is also possible on all
versions.  This function can be accomplished by
changing the Heat/Cool parameter in SETUP mode.

.'/",('&

 

Elegant styling with digital display makes

thermostat well harmonised with any interior

decoration of office or hotel

 

Digital display of room ambient temperature, with

display of user selected setpoint on demand

 

Push button adjustment of setpoint

 

Push button setting of Heat/Cool changeover

 

Switches allow manual control of system operation

and fan speed

 

Thermostat mounts directly onto a wall, a standard

65

3

65mm junction box (hole pitch 60mm) or a

85

3

85mm junction box

 

Ability to set minimum relay off-times (heating or

cooling) for applications requiring compressor short-

cycle protection (0~10min.)

 

Ability to set control-off-times for applications

requiring starting-time reservation (0~24hr.)

 

Ability to display temperature sensor failure for

easier troubleshooting

 

EEPROM permanently retains user settings in the

event of power loss

 

Suitable for use with Honeywell VC4000/VC6000

series and V4043/V4044 valves and compressor

starters/relays up to 2A full load rating

                                                                                  Contents

Application …………………………………………………   1
Features ……………………………………………………   1
Specifications ……………………………………………...   2
Installation ………………………………………………….   3
Wiring diagram …………………………………………….   4~5
Operation …………………………………………………..    6

Содержание DT70 Series

Страница 1: ...hermostat well harmonised with any interior decoration of office or hotel Digital display of room ambient temperature with display of user selected setpoint on demand Push button adjustment of setpoint Push button setting of Heat Cool changeover Switches allow manual control of system operation and fan speed Thermostat mounts directly onto a wall a standard 65365mm junction box hole pitch 60mm or ...

Страница 2: ...V 12A inrush Typical loads are fans zone valves and relays Operational life Greater than 100 000 cycles all loads for thermostat contacts at 220 V Greater than 10 000 operations for all manually operated switches Mounting Mounts directly onto wall or wall box a standard 65x65mm junction box hole pitch 60mm or a 85385mm junction box Mounting screws supplied Wiring 7 or 9 screw in terminals per unit...

Страница 3: ...d the thermostat concealed pipes or chimneys 0 22 0 93 8678 6 6 3 656 The DT70 Series thermostat can be directly mounted on the wall or on either a 65x65mm standard junction box or a 85x85mm junction box Mounting screws are supplied for both alternatives IMPORTANT The installer must be a trained service engineer Disconnect the power supply before beginning installation Separate the base from the m...

Страница 4: ...g Diagram DT70 F002ET F012ET 7 6 5 4 3 2 1 CONTROL ELECTRONICS RELAY FAN Switch H M L ON OFF Switch FAN CLOSE Overload Protection Device COOL HEAT N L 3 6 2 VC6013 OFF ON Fig 3 DT70 F002ET DT70 F012ET Cool Heat Off wiring diagram with 3 speed cycled fan ...

Страница 5: ... FAN Switch H M L FAN EXTERNAL UNIT CHILLER Over Load Protection Device 8 9 VALVE M HI LO PRESSURE SWITCH COMPRESSOR MOTOR OFF ON AUTO MANUAL ON OFF Switch OFF ON L N INTERNAL UNIT Fan Coil COOL HEAT Fig 4 DT70 F003ET Cool Heat Off wiring diagram with 3 speed fan and CHILLER DT70 F003ET ...

Страница 6: ...rn to showing the room temperature Cooling Heating changeover 1 To change cooling heating mode press the SET key for 3 seconds and C Cooling is displayed 2 Press the or key These keys change the mode into H Heating or C Cooling Minimum relay off time setting This is the function that prevents the relay from energizing the load for the setting time The default setting is zero minutes no minimum rel...

Отзывы: