Honeywell DS05 Скачать руководство пользователя страница 6

DS05 DIAL SET PRESSURE REGULATING VALVE

62-3041—2

6

TROUBLESHOOTING

Table 2 provides a troubleshooting guide for the DS05 Dial Set Pressure Regulating Valve.

Table 2. Troubleshooting the DS05 Dial Set Pressure Regulating Valve.

Problem

Solution

Whistling noise.

Slightly increase or decrease the outlet pressure until the noise disappears.

Will not hold pressure.

Clean the filter cartridge as described in the Installation section.

Chatters.

Replace the screen and O-rings.

Replace the cartridge as shown in Fig. 3.

Freezes up.

Replace bonnet or cartridge if damaged.

To avoid future freeze-up:

— Temporarily (slightly) open a downstream faucet if the DS05 will be exposed

to temperatures below 32°F (0°C). The slight water flow will eliminate
freeze-up.  

— Move the DS05 to a location with an ambient temperature above 32°F (0°C)

If it is currently exposed to prolonged temperatures below 32°F (0°C).

Pressure gauge measures a lower
pressure under flow conditions than
was originally set during static
conditions.

DS05 is functioning properly. No action is necessary. The pressure decrease is
characteristic of all direct acting pressure regulating valves and is referred to as
falloff.

Содержание DS05

Страница 1: ...tatic pressure only FEATURES Built in factory calibrated outlet pressure adjustment dial Noncorroding unitized cartridge contains all working parts and is easily replaceable Includes built in strainer and thermal bypass Balanced seat construction provides superior pressure regulation Inlet and outlet are internally threaded female NPT and externally threaded for use with union assemblies Gauge tap...

Страница 2: ...s ASSE Std 1003 Certified IAPMO CSA and City of L A Listed Dimensions See Fig 1 4 5 16 4 5 16 5 9 16 5 9 16 2 1 16 2 1 16 2 5 8 2 5 8 52 52 66 66 3 3 16 3 1 2 3 15 16 4 11 16 81 89 100 119 1 2 3 4 1 1 1 4 SIZE INCHES H h l 110 110 141 141 3 7 8 4 5 16 5 1 4 6 3 16 4 5 8 5 3 16 6 1 2 7 11 16 1 NON UNION MODEL CONFIGURATION 2 SINGLE UNION MODEL CONFIGURATION 3 DOUBLE UNION MODEL CONFIGURATION 4 DIME...

Страница 3: ...psi pressure differential If 12 gpm capacity is required with only 10 psi falloff allowable a 1 2 in DS05 is required Table 1 Water Capacities Pressure Differential Between Inlet and Outlet Pressure Reduced 25 psi 50 psi 75 psi 100 psi or more Regulator Valve Size Pressure Falloff psi Flow Capacity US gpm Velocity ft sec a Flow Capacity US gpm Velocity ft sec a Flow Capacity US gpm Velocity ft sec...

Страница 4: ... can be mounted in any position The DS05 can be installed directly onto the pipe by using the female NPT threads on each end If space limitations restrict turning the DS05 install single or double unions NOTE Heat from soldering can damage internal parts of the DS05 Always solder the tailpieces separately from the DS05 Open the supply valve slowly and check for leakage and proper operation of the ...

Страница 5: ... the washer on top of the cartridge NOTE The inner lip must be pointing up to avoid damaging the diaphragm 쐅 Replace the spring and bonnet 쐈 Readjust the outlet pressure to the desired setting by using the procedure described in Changing the Outlet Pressure section Recalibration If the dial knob assembly has been disassembled recalibration is necessary Recalibrate as follows Install a good quality...

Страница 6: ...e cartridge as shown in Fig 3 Freezes up Replace bonnet or cartridge if damaged To avoid future freeze up Temporarily slightly open a downstream faucet if the DS05 will be exposed to temperatures below 32 F 0 C The slight water flow will eliminate freeze up Move the DS05 to a location with an ambient temperature above 32 F 0 C If it is currently exposed to prolonged temperatures below 32 F 0 C Pre...

Страница 7: ...e to increase the spring force and require a higher downstream pressure to close the valve Similarly reducing the spring force lowers the outlet set pressure A factory calibrated dial is built into the adjustment mechanism to allow outlet pressure no flow to be set without a gauge A locking screw maintains the setting A black plastic cover is provided to conceal the setting and protect the DialSet...

Страница 8: ...Nut Female NPT Threaded Tailpiece and Gasket K06U1077 Union Kit 3 4 in includes Nut Female NPT Threaded Tailpiece and Gasket K06U1085 Union Kit 1 in includes Nut Female NPT Threaded Tailpiece and Gasket K06U1135 Union Kit 1 1 4 in for D05 D505 includes Nut Female NPT Threaded Tailpiece and Gasket K06U1093 Union Kit 1 2 in includes Nut Sweat Tailpiece and Gasket K06U1101 Union Kit 3 4 in includes N...