DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
133
April 2017
5.8 Single Setpoint Ramp
Configuring the setpoint ramp
You can configure a single setpoint ramp to occur between the current local setpoint and a final local
setpoint over a time interval of from 1 to 255 minutes. You can RUN or HOLD the ramp at any time.
Procedure
Table 5-17 lists the procedure for configuring the Setpoint Ramp 1 or 2 parameters. The procedure for
Setpoint Program
is in
Section 6 – Setpoint Ramp/Soak Programming Option.
Table 5-17 Procedure for configuring a single setpoint ramp
Step
Operation
Press
Action/Result
1
Select SP RAMP 1 or
SP RAMP 2 Set Up
group
SET
UP
Until you see:
Upper Display:
SET UP
Lower Display:
SP RAMP X
X
= 1 or 2
2
Select the Setpoint Ramp
function
FUNC
Until you see:
Upper Display:
DISABL
Lower Display:
SP RAMP X
3
Enable Setpoint Ramp
▲
Until you see:
Upper Display:
ENABLE
Lower Display:
SP RAMP X
NOTE: You cannot change the current local setpoint if
the setpoint ramp function is enabled. Make sure SP
PROG is disabled.
4
Set the Ramp Time
FUNC
Until you see:
Upper Display:
The ramp time in minutes
Lower Display:
TIME MIN
▲
or
▼
Change the upper display value to the number of
minutes in which you want the final setpoint to be
reached.
Setting Range = 1 to 255 minutes
NOTE: Entering “0” implies an immediate step change
to the final SP.
5
Set the Final Setpoint
value
FUNC
Upper Display:
The final setpoint value
Lower Display:
FINAL SP
6
▲
or
▼
Change the upper display value to the desired final
setpoint value.
Setting Range = within the setpoint limits