Honeywell DIAL-SET DS05C Скачать руководство пользователя страница 5

DS05C,D,G

5

62-3041—4

Cleaning the Cartridge Screen

To clean the cartridge screen:

1.

Shut off the supply valve and open a downstream faucet 

to relieve the system pressure.

CAUTION

To prevent injury and/or equipment damage, 

loosen locking screw and turn adjusting knob 

counter-clockwise 

to remove spring tension. 

Do not remove screw.

2.

Loosen locking screw and turn adjusting knob counter-

clockwise 

to remove spring tension.

3.

Remove the bonnet and washer using an MT06A service 

tool. 

4.

Remove the cartridge using two screwdrivers as levers 

as shown in Figure 3. 

5.

Remove and clean the cartridge screen.

6.

Replace the cartridge screen and make sure the O-rings 

are installed properly.

7.

Carefully clean the cartridge seat area.

8.

Insert the cartridge. Do not scratch the sides.

9.

Place the washer on top of the cartridge.

NOTE: The inner lip must be pointing up to avoid damaging 

the diaphragm.

10.

Replace the spring and bonnet.

11.

Readjust the outlet pressure to the desired setting by 

using the procedure described in Changing the Outlet 

Pressure section.

Recalibration

If the dial knob assembly has been dismantled, recalibration is 

necessary. Recalibrate as follows:

1.

Install a good quality pressure gauge at the gauge tap 

connection.

2.

Open supply pressure and adjust spindle until the gauge 

shows 60 psi.

3.

Reassemble dial ring and adjustment knob so dial reads 

60 psi.

Fig. 3. Replacing the DS05 cartridge.

3

O-RINGS

WASHER

(LIP UP)

M7313A 

1

4

5

6

2

60

60

 LOOSEN THE SETPOINT DIAL LOCKING SCREW.

UNSTRESS THE 

PRESSURE SPRING 

BY TURNING COUNTER-

CLOCKWISE         .

UNSCREW THE BONNET WITH MT06A SERVICE TOOL.

REMOVE CARTRIDGE USING TWO SCREWDRIVERS AS LEVERS.

WHEN REASSEMBLING,

ENSURE O-RINGS AND

WASHER ARE PROPERLY

INSTALLED           

REASSEMBLE BONNET IN REVERSE ORDER.

MT06A SERVICE TOOL

(ORDER SEPARATELY)

Содержание DIAL-SET DS05C

Страница 1: ...d thermal bypass Balanced seat construction provides superior pressure regulation Inlet and outlet are internally threaded female NPT and externally threaded for use with union assemblies Stand In Pipe available for temporary installation during construction or system flushing SPECIFICATIONS Model DS05 Dial Set Pressure Regulating Valves Construction Materials Body Bronze Internal Parts Stainless ...

Страница 2: ...inlet to outlet Reduced Ratio 10 1 maximum Temperature Maximum Air 158 F 70 C Water 180 F 82 C Ambient Temperature Range 33 F to 140 F 1 C to 60 C Pipe Sizes Available 1 2 in 3 4 in 1 in and 1 1 4 in available Connections Can be configured as female thread by thread single union or double union NPT threaded or sweat Strainer Screen Size 0 032 in 0 8 mm Gauge Tap 1 1 4 in model only Approvals ASSE ...

Страница 3: ...Capacity US gpm Velocity ft sec a a Velocity in feet per second is based on schedule 40 pipe size Recommended pressure falloff for general use is approximately 104 kPa 15 psi Recommended velocities for the flow of water residential and general use 5 to 10 ft sec industrial use 7 to 15 ft sec boiler feed 7 to 15 ft sec Flow Capacity US gpm Velocity ft sec a Flow Capacity US gpm Velocity ft sec a Fl...

Страница 4: ... by turning the locking screw clockwise 4 Replace the dust cap over the dial MAINTENANCE Replacing the Cartridge See Fig 3 The working parts of the DS05 including diaphragm valve seat strainer and disk are all contained in a replaceable cartridge To replace the cartridge 1 Shut off the supply valve and open a downstream faucet to relieve the system pressure 2 Loosen the setpoint screw by turning i...

Страница 5: ...er on top of the cartridge NOTE The inner lip must be pointing up to avoid damaging the diaphragm 10 Replace the spring and bonnet 11 Readjust the outlet pressure to the desired setting by using the procedure described in Changing the Outlet Pressure section Recalibration If the dial knob assembly has been dismantled recalibration is necessary Recalibrate as follows 1 Install a good quality pressu...

Страница 6: ...in Figure 3 Freezes up Replace bonnet or cartridge if damaged To avoid further freeze up Temporarily slightly open a downstream faucet if the DS05 will be exposed to temperatures below 32 F 0 C The slight water flow will eliminate freeze up Move the DS05 to a location with an ambient temperature above 32 F 0 C if it is currently exposed to prolonged temperature below 32 F 0 C Pressure gauge measur...

Страница 7: ...pring force and require a higher downstream pressure to close the valve Similarly reducing the spring force lowers the outlet set pressure A factory calibrated dial is built into the adjustment mechanism to allow outlet pressure no flow to be set without a gauge A locking screw maintains the setting A black plastic cover is provided to conceal the setting and protect the Dial Set from moisture and...

Страница 8: ...ns Gaskets and Nuts K06U1192 1 DN25 Female NPT 1 in PRV Jumper Kit 2 Threaded Unions Gaskets and Nuts K06U1200 1 1 4 DN32 Sweat 1 1 4 in Jumper Kit 2 Sweat Unions Gaskets and Stand in Pipe K06U1218 1 1 4 DN32 Female NPT 1 1 4 in Jumper Kit 2 Threaded Unions Gaskets and Stand in Pipe PRV202 039 3 4 DN20 Male NPT 3 4 in Stand in Pipe PRV202 040 1 DN25 Male NPT 1 in PRV Stand in Pipe PRV203 034 1 1 4...

Отзывы: