Pressure switches with manual 
reset

 

DG..NT locks off if the pressure drops to the 
value set using the hand wheel.

 

DG..HT locks off if the pressure rises to the value 
set using the hand wheel.

 1 

  Reset the pressure switch using the manual reset.

 

Requirement for reset: 

 

DG..NT: the pressure must have risen at least 
to the set switching point plus the pressure dif-
ferential between the switching pressure and 
possible lock-off.

 

 DG..HT: the pressure must have dropped at least 
to the set switching point minus the pressure 
differential between the switching pressure and 

possible lock-off.

 

For details of the pressure differential between 
the switching pressure and possible reset, see 
table on page 3 (Adjustment).

Tightness test

 1 

 Shut off the downstream gas pipeline close to 

the valve.

 2 

 Open the valve and the gas supply.

 

Check all used ports for tightness.

N

2

13 psi

max. 29 psi

< 15 min

3

4

Maintenance

In order to ensure smooth operation, check the tight-
ness and function of the DG..T every year, or every 
six months if operated with biogas.

Accessories

LED set, red/green

3

1

4

2

NC

1

COM

3

NO

2

N

NO

2

1 NC

3 COM

+

24 V DC, I = 16 mA; 24 V AC, I = 8 mA,  
Order No.: 74921089. 

110 to 230 V AC, 

Order No.: 74923275.

Содержание DG T Series

Страница 1: ...th socket IP 65 1 2 1x NPT connection 2x NPT connections K2 T2 N Red green pilot LED for 24 V DC AC Red green pilot LED for 110 to 230 V AC Blue pilot lamp for 120 V AC A External adjustment If none this specification is omitted DG T switches with rising pressure Part designations 1 2 3 5 4 1 Upper housing section with cover 2 Lower housing section 3 Hand wheel 4 NPT conduit coupling 5 Manual rese...

Страница 2: ...rtical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point ps SK ps SK 0 08 WC ps SK 0 08 WC CAUTION If port 4 is at the top IP 65 will not be satisfied 4 IP65 The DG T must not be in contact with...

Страница 3: ...0 0 4 0 4 WC 1 cm 1 mbar 6 Apply pressure In doing so monitor the ohm meter and the pressure gauge Pressure switches without manual reset DG T DG FT DG ST Type Adjusting range WC mbar Mean switching differential at min and max setting WC mbar Max inlet pressure pmax psi mbar No venting line With venting line1 DG 6T 0 2 2 4 0 5 6 0 08 0 12 0 2 0 3 2 4 psi 165 8 5 psi 600 DG 10T 0 4 4 1 10 0 1 0 16 ...

Страница 4: ...tching point minus the pressure differential between the switching pressure and possible lock off For details of the pressure differential between the switching pressure and possible reset see table on page 3 Adjustment Tightness test 1 Shut off the downstream gas pipeline close to the valve 2 Open the valve and the gas supply Check all used ports for tightness N2 13 psi max 29 psi 15 min 3 4 Main...

Страница 5: ... medium and ambient temperatures 40 to 140 F 40 to 60 C Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the service life please contact manufacturer The set switching point may palpably change in me dia and ambient temperatures below 22 F 30 C Storage temperature 4 to 104 F 20 to 40 C Diaphragm pressure switch silicone free Diaphr...

Страница 6: ...omplete see page 1 Part designa tions Report any transport damage immediately Storage Store the product in a dry and clean place Storage temperature see page 5 Technical data Packaging The packaging material is to be disposed of in accordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Directive on the restriction o...

Отзывы: