NOTES
1. Not operative if Proportional Band = 0.
2. Switching differential for ON/OFF control output.
3. Optional; only one legend will appear for each alarm.
4. Only applicable if a DC linear input is fitted.
5. Only applicable if Output 2 is fitted as a secondary control (COOL)
output.
6. Applicable only if the Communications Option is fitted.
7. When a program is running, respective to program setpoint.
4.1
PARAMETER DETAILS
4-3
Parameter
Function
Adjustment Range
Default value
Input Filter Time
Constant
Filter removes extraneous impulses from
the process variable input
OFF, 0.5 to 100.0
seconds in 0.5 second
increments
2.0 seconds
Process Variable
Offset
Modifies actual process variable (PV)
value:
Offset PV + actual PV
= PV value used
±
input span of
Controller
0
Output Power 1
Current Output 1 power level
0 to 100%
Read only
Output Power 2
Current Output 2 power level
0 to 100%
Read only
Proportional
Band 1 (PB1)
Portion of input span in which Output 1
power level is proportional to the
(offset) process variable value (see
Figure 4-1).
0.0 to 999.9% of input
span
10.0%
Proportional
Band 2 (PB2)
Portion of input span in which Output 2
power level is proportional to the
(offset) process variable value (see
Figure 4-1).
0.0 to 999.9% of input
span
10.0%
Reset (Integral
Time Constant)
Integral time constant
1sec. to 99min. 59
secs. and OFF
5 mins. 00
secs.
Rate (Derivative
Time Constant)
Derivative time constant
00 secs. to 99 mins. 59
secs.
1 min. 15
secs.
Overlap/
Deadband
Portion of proportional band (PB1 +
PB2) in which both outputs are active
(overlap) or neither output is active
(deadband) - see Figure 4-1).
−
20% to +20% of
(Proportional Band 1 +
Proportional Band 2)
0%
Manual Reset
(Bias)
Bias applied to output power,
expressed as a percentage of output
power.
0% to 100% (Output 1
only);
−
100% to +100%
(Output 1 & Output 2)
25%
Содержание DCP 50
Страница 1: ...Sensing and Control DCP 50 Digital Controller Programmer Product Manual 57 77 25 17 3 00 ...
Страница 4: ......
Страница 8: ...1 BASE MODE 1 1 DISPLAY SEQUENCE NO PROGRAM RUNNING 1 1 ...
Страница 17: ...2 3 Figure 2 4 Rear Terminal Connections ...
Страница 23: ...3 2 2 Defining Segments Rate Mode 3 3 ...
Страница 24: ...3 2 3 Defining Segments Time Mode 3 4 ...
Страница 25: ...3 2 4 Program Options 3 5 ...
Страница 35: ...4 6 Figure 4 1 Proportional Band and Overlap Deadband ...
Страница 36: ...4 7 Figure 4 2 Alarm Operation ...
Страница 37: ...4 8 Figure 4 3 Alarm Hysteresis Operation ...
Страница 38: ...4 2 EXIT FROM CONTROLLER SET UP MODE A return will then be made to the normal Base Mode display 4 9 ...
Страница 51: ...6 2 Figure 6 2 Hardware Definition Code Access and Adjustment ...
Страница 60: ...7 2 Figure 7 2 Removing the Output 2 Output 3 Option PCBs ...
Страница 87: ......
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......