Honeywell D05T Скачать руководство пользователя страница 4

D05T COMPACT DESIGN PRESSURE REGULATING VALVES

62-3021—03

4

6.

Turn the adjusting bolt clockwise 

 to gradually 

increase the pressure until the gauge indicates the 

desired outlet pressure (under no flow condition).

7.

Reopen a downstream valve. During flow, there will nor-

mally be a pressure falloff of 3 to 15 psi depending on 

the amount of water flow.

8.

Tighten the locknut by turning clockwise 

 until tight. 

Do not overtighten.

Fig. 2. Changing outlet pressure.

Replacing the Cartridge (See Fig. 3)

The working parts of the D05T, including diaphragm, valve 

seat, and disk are all contained in a replaceable cartridge. To 

replace the cartridge:

1.

Shut off the supply valve and open a downstream faucet 

to relieve the system pressure.

CAUTION

To prevent injury and/or equipment damage, 

loosen locknut and turn adjusting screw 

counterclockwise 

 to remove spring tension.

2.

Loosen locknut and turn adjusting screw counterclock-

wise 

 to remove spring tension.

3.

Remove the bonnet and washer using an adjustable 

wrench, socket, or box-end wrench.

4.

Remove the cartridge using two screwdrivers as levers.

5.

Attach new O-rings and screen onto the new cartridge. 

Make sure O-rings are properly installed above and 

below the screen.

6.

Insert the new cartridge. Do not scratch the sides.

7.

Place the washer on top of the cartridge.

NOTE: The inner lip must be pointing up to avoid dam-

aging the diaphragm.

8.

Replace the spring, spring cup, and bonnet.

9.

Readjust the outlet pressure to the desired setting by 

using the procedure described in Changing the Outlet 

Pressure section.

100

75

50

25

0

125

150

175

200

0

200

400

600

800

1000

1200

1400

PSI

kPa

HONEYWELL

BRAUKMANN

3

TIGHTEN LOCKNUT BY

TURNING CLOCKWISE

1

LOOSEN LOCKNUT 

BY TURNING 

COUNTERCLOCKWISE

THE CLOCKWISE AND COUNTERCLOCKWISE

DIRECTIONS ARE DETERMINED BY LOOKING

DIRECTLY AT THE ADJUSTING BOLT

1

1

1

M32170

150200

250

300

100

50

PSI

water test

2

TURN ADJUSTING BOLT

COUNTERCLOCKWISE

TO DECREASE OR 

CLOCKWISE         TO 

INCREASE OUTLET PRESSURE

Содержание D05T

Страница 1: ...t is not suitable for steam FEATURES Non corroding unitized cartridge contains all working parts and is easily replaceable Includes built in strainer and thermal bypass Balanced seat construction provides superior pressure regulation Inlet and outlet are internally threaded female NPT and externally threaded for use with union assemblies One year warranty SPECIFICATIONS Model D05T Pressure Regulat...

Страница 2: ...ct Number Pipe Size Dimensions Approximate Union Fittings inch DN inch mm D05T1011 3 4 in DN20 6 5 8 in high x 3 1 2 in wide 168 mm high x 89 mm long Union body no tailpieces D05T1029 3 4 in DN20 6 5 8 in high x 5 3 16 in long 168 mm high x 132 mm long Double union sweat D05T1045 1 in DN25 4 1 2 in high x 4 in long 114 mm high x 142 mm wide Union body no tailpieces D05T1052 1 in DN25 8 5 8 in high...

Страница 3: ...ownstream isolating valve if used 3 Install the D05T with the arrow on the body pointing in the direction of water flow The D05T can be mounted in any position The D05T can be installed directly onto the pipe by using the female NPT threads on each end If space limitations restrict turning the D05T install single or double unions NOTE Heat from soldering can damage internal parts of the D05T Alway...

Страница 4: ...sting screw counterclock wise to remove spring tension 3 Remove the bonnet and washer using an adjustable wrench socket or box end wrench 4 Remove the cartridge using two screwdrivers as levers 5 Attach new O rings and screen onto the new cartridge Make sure O rings are properly installed above and below the screen 6 Insert the new cartridge Do not scratch the sides 7 Place the washer on top of th...

Страница 5: ...hown in Fig 3 5 Remove and clean the cartridge screen 6 Replace the cartridge screen and make sure the O rings are installed properly 7 Carefully clean the cartridge seat area 8 Insert the cartridge Do not scratch the sides 9 Place the washer on top of the cartridge NOTE The inner lip must be pointing up to avoid dam aging the diaphragm 10 Replace the spring spring cup and bonnet see Fig 4 11 Read...

Страница 6: ...ESIGN PRESSURE REGULATING VALVES 62 3021 03 6 Fig 4 D05T exploded view ADJUSTING SCREW LOCKING NUT BONNET SPRING CUP SPRING WASHER CARTRIDGE O RING SCREEN O RING NUT TAILPIECE GASKET NUT TAILPIECE GASKET M32171 BODY ...

Страница 7: ...ket for 1 in D05T DS05 quantity 24 K05A1009 Replacement Cartridge Screen and O ring for 3 4 in Valves K05A1017 Replacement Cartridge Screen and O ring for 1 in Valves K05B1007 Replacement Screen and O ring for 3 4 in Valves K05B1015 Replacement Screen and O ring for 1 in Valves Union Kits K06U1077 Union Kit 3 4 in includes nut female NPT threaded tailpiece and gasket K06U1085 Union Kit 1 in includ...

Страница 8: ...ns Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 62 3021 03 T D Rev 07 10 Printed in U S A ...

Отзывы: