CR7075 TWO-STAGE LIGHTING CONTROLLER

63-2180—1

4

Wiring

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment 

circuitry.

Disconnect power supply before installation.

IMPORTANT

• All wiring must agree with applicable codes, 

ordinances and regulations.

• When wiring the input power, apply only one source 

of power to the CR7505A.

• With line-voltage loads, the power and load voltage 

must be the same.

Refer to chart on the inside of the controller cover or Fig. 3 for 

locating the power inputs, photocell sensor inputs, TOD and 

load relay terminals. Refer to Fig. 4 through 7 for typical wiring 

and application examples.

NOTES:

The photocell sensor has no polarity.

Wire to terminal strip T2, terminals 4 and 5.

Access to the terminals can be gained through 

standard conduit knockouts (A-E) located around 

the perimeter of the enclosure.

Use knockout A only for the photocell sensor 

and TOD wiring.

Photocell wires should be at least 18 AWG two 

conductor. If not run in watertight conduit, use 

suitable insulation for outdoor wiring.

Shielded wiring is not required.

The Two-Stage Lighting Control System consists of 

two components:

— CR7075 Two-Stage Lighting Controller.

— C7057 Cadmium Sulfide Photocell Sensor.

This system offers independent series 60 control of two 

separate lighting banks based on user determined ambient 

light intensity level via a single sensor.

Set point indexing is relative. The SET-RUN switch removes 

the integrating time delay (short cycle protection) circuitry in 

the SET position. In the RUN position (normal operation) there 

is a 30 ±10 second time delay for both light fall and light rise 

initiated relay action.

Two independent Time Of Day (TOD) inputs are provided to 

override a relay energized condition of either output. This 

function is generated by a contact closure from an EMS 

controller or time clock with normally open contacts, i.e., 

W7505, S7005, etc., between terminals 1 and 2 (stage 1) and 

terminals 2 and 3 (stage 2) of terminal strip T2 (Fig. 6 and 7). 

These inputs have priority over any time delay action.

Fig. 3. Knockout locations and internal device layout.

Fig. 4. Wiring for 120 or 240 Vac input and load.

CAUTION

ONE POWER SOURCE ONLY

LINE POWER

OUTPUT 1

OUTPUT 2

120

VAC

240

VAC

COM

N0

COM NC

N0 COM NC

M1040

LIGHT LEVEL

SET

RUN

POWER STAGE 1

STAGE 2

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

T.O.D. 1
T.O.D. 2

SENSOR

A

B

C

D

E

CAUTION

ONE POWER SOURCE ONLY

LINE POWER

OUTPUT 1

OUTPUT 2

120

VAC

240

VAC

COM

N0

COM NC

N0 COM NC

M1043

LIGHT LEVEL

SET

RUN

POWER STAGE 1

STAGE 2

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

T.O.D. 1
T.O.D. 2

SENSOR

1
2
3
4

5

T2

T.O.D. 1

T.O.D. 2

WHITE

BLACK

LOAD 2

LOAD 1

L1

L2

1

1

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED.

Содержание CR7075

Страница 1: ...de outdoor cosmetic and parking lot lighting in fast food restaurants retail establishments supermarkets banks and lighted billboards FEATURES Light intensity threshold levels field adjustable by user Independent Time of Day TOD override inputs Optimum start stop of lighting loads Tamper proof cover LED annunciation for power on and relay state Wide ambient temperature range Up to 1000 foot separa...

Страница 2: ...s Spain Taiwan United Kingdom U S A SPECIFICATIONS Model CR7075A1000 Two Stage Lighting Controller Dimensions See Fig 1 Electrical Ratings Voltage Input 120 240 Vac 50 60 Hz Power Consumption 5 VA Maximum Switching Single Pole Double Throw SPDT Sensor Cadmium sulfide photocell C7057A1000 1000 ft maximum distance between sensor and controller shielded wire not required Indicators LED annunciation p...

Страница 3: ...ulfide photocell sensor C7057A1000 supplied with this controller so that the lens is exposed to full daylight See Fig 2 NOTES Select an area which will not become shaded Mount only with light entrance facing horizontally Avoid overexposure to direct east west sunlight Fig 2 Vertical mounting configuration Mounting IMPORTANT Mount the photocell sensor to the top of a watertight outdoor FS junction ...

Страница 4: ...es 60 control of two separate lighting banks based on user determined ambient light intensity level via a single sensor Set point indexing is relative The SET RUN switch removes the integrating time delay short cycle protection circuitry in the SET position In the RUN position normal operation there is a 30 10 second time delay for both light fall and light rise initiated relay action Two independ...

Страница 5: ...RLOAD PROTECTION AS REQUIRED WHEN SWITCHING 24 VOLT LOADS MAKE SURE BARRIER IS INSTALLED L1 HOT L2 1 CAUTION ONE POWER SOURCE ONLY LINE POWER OUTPUT 1 OUTPUT 2 120 VAC 240 VAC COM N0 COM NC N0 COM NC M1088 LIGHT LEVEL SET RUN POWER STAGE 1 STAGE 2 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 T O D 1 T O D 2 SENSOR 1 2 3 4 5 T2 WHITE BLACK L1 L2 LOAD 2 LOAD 1 S7005 T3 T4 T5 1 1 POWER SUPPLY PROVIDE DI...

Страница 6: ...can require changing the light level potentiometer settings Refer to the Checkout section for calibration instructions Typical Sequencing The following is an example of a typical on off sequence NOTES Refer to Fig 8 for sequence of operation For 24 hour stores lights simply remain on unless sufficient light exists to warrant their shut off As operation in such an arrangement depends only on the ph...

Страница 7: ...ear the light conditions required for switching the equipment Attempting calibration at extreme light conditions can cause switching to be unachievable 1 At the desired outdoor light level place SET RUN switch to the SET position 2 Slowly rotate stage 1 light level potentiometer counter clockwise until the stage 1 LED lights 3 Stage 1 is now calibrated to the light level existing at the sensor and...

Страница 8: ...ational Honeywell Europe Honeywell Latin American Honeywell Honeywell Limited Honeywell Limitée Home and Building Control S A Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 3 Avenue du Bourget 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 1140 Brussels Suite 200 M1V 4Z9 Singapore 486073 Belgium Sunrise FL 33325 ...

Отзывы: